28156A Datasheet
The Belden 28156A is a UL Type TC power and control cable with three 4 AWG bare copper conductors and one 8 AWG bare copper ground conductor, insulated with PVC/nylon and covered by a black PVC jacket with a ripcord. It is rated 600 V (TC-ER), 90 °C dry and wet, and is suitable for power and control applications up to 600 V and Class 1 Division 2 hazardous locations. The cable is sunlight resistant and rated for direct burial.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28156A Key Specifications
- Max Current
- 95 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 25ºC (ground)
- UL Voltage Rating
- 600 V (TC-ER)
- Temperature Rating
- 90°C Dry, 90°C Wet; Wet/Dry Operating -30°C to 90°C
- Conductors
- 3 x 4 AWG bare copper, 7x12 stranding; Ground: 1 x 8 AWG bare copper, 7x16 stranding
- Max Pull Tension
- 1877.4 lbs (851.57 kg)
- Nom. Insulation Thickness
- 0.042 in (1.1 mm)
- Nom. Outer Diameter
- 0.822 in (20.9 mm)
- Nom. Outer Jacket Thickness
- 0.063 in (1.6 mm)
Characteristics (datasheet)
- UL Voltage Rating
- 600 V (TC-ER)
- Conductors
- 3 x 4 AWG bare copper, 7x12 stranding; Ground: 1 x 8 AWG bare copper, 7x16 stranding
- Max Current
- 95 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 25ºC (ground)
- Nom. Insulation Thickness
- 0.042 in (1.1 mm)
- Nom. Outer Jacket Thickness
- 0.063 in (1.6 mm)
- Nom. Outer Diameter
- 0.822 in (20.9 mm)
- Temperature Rating
- 90°C Dry, 90°C Wet; Wet/Dry Operating -30°C to 90°C
- Max Pull Tension
- 1877.4 lbs (851.57 kg)
28156A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 85224CY — The Belden 85224CY is a four-conductor, 22 AWG bare copper XTRAGUARD FLEX contin...
- 7814A — The Belden 7814A is a Category 6 indoor horizontal cable featuring four pairs of...
- 28338A — Belden 28338A is a UL Type TC (1277) power/control cable with four 16 AWG (7x24)...
- 29016 — The Belden 29016 is a Canadian Instrumentation Cable (TC-ACIC) rated 600 V RMS w...
- 8455 — The Belden 8455 is a portable 5-conductor cordage featuring 20 AWG and 18 AWG ti...
- 37504 — Belden 37504 is a rubber lead wire built with a 4 AWG (105x24) tinned copper con...
- 1037A — The 1037A is a black-jacketed instrumentation cable designed for industrial cont...
- 5934 — The Belden 5934 is an XTRAGUARD 1 shielded cable featuring 4 conductors of 28 AW...
More Bulk Wire Cable
- 9803 — The Belden 9803 is a 3-conductor, 20 AWG solid tinned copper electronic cable fe...
- 86004 — The Belden 86004 is a flexible, 4-conductor 28 AWG tinned copper cable with semi...
- 9539 — The Belden 9539 is a computer EIA RS-232 cable featuring 9 stranded tinned coppe...
- 80133 — The part 80133 is an ECOFLEX PUR multi-conductor cable consisting of 3 conductor...
- 7424W — The Belden 7424W is a highly flexible MachFlex™ multi-conductor cable featuring...
- 80126 — The Belden 80126 is a 12-conductor, 20 AWG tinned copper cable with modified pol...
- 77050 — The Belden 77050 is a 6-conductor, 26 AWG tinned copper cable with mPPE insulati...
- 1365 — The Belden 1365 is a RWU90 1000V power and control cable featuring a 10 AWG bare...
28156A FAQ
What is 28156A?
28156A is a Bulk Wire Cable from Belden. The Belden 28156A is a UL Type TC power and control cable with three 4 AWG bare copper conductors and one 8 AWG bare copper ground conductor, insulated with PVC/nylon and covered by a black PVC jacket with a ripcord. It is rated 600 V (TC-ER), 90 °C dry and wet, and is suitable for power and control applications up to 600 V and Class 1 Division 2 hazardous locations. The cable is sunlight resistant and rated for direct burial.
Who manufactures 28156A?
28156A is manufactured by Belden.
Where can I download the 28156A datasheet PDF?
The 28156A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28156A specifications
Click to ask a quick question:
Parameters
| Conductors | 3 x 4 AWG bare copper, 7x12 stranding; Ground: 1 x 8 AWG bare copper, 7x16 stranding |
| Max Current | 95 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 25ºC (ground) |
| Max Pull Tension | 1877.4 lbs (851.57 kg) |
| Nom. Insulation Thickness | 0.042 in (1.1 mm) |
| Nom. Outer Diameter | 0.822 in (20.9 mm) |
| Nom. Outer Jacket Thickness | 0.063 in (1.6 mm) |
| Temperature Rating | 90°C Dry, 90°C Wet; Wet/Dry Operating -30°C to 90°C |
| UL Voltage Rating | 600 V (TC-ER) |