1037A Datasheet
The 1037A is a black-jacketed instrumentation cable designed for industrial control, digital instruments, and programmable logic controllers (PLCs). It features three pairs of 16 AWG bare copper conductors with PVC-nylon insulation, individual and overall Beldfoil shields, and a black PVC outer jacket. The cable is rated for 600V TC-ER / 150V NPLF, supports a temperature of up to 90°C dry/wet, and is suitable for indoor, outdoor, burial, and sunlight-resistant environments.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
1037A Key Specifications
- Max Current
- 14 Amps per conductor @ 30°C
- Voltage Rating
- 600 V (TC-ER), 150 V (NPLF)
- Temperature Rating
- 90°C Dry, 90°C Wet; Operating: -30°C to 90°C Dry/Wet
- Bend Radius
- 5.7 in (140 mm) stationary and installation min.
- Bulk Cable Weight
- 127 lbs/1000ft
- Conductor
- 3 pairs, 16 AWG 7x24 bare copper (BC)
- Max Pull Tension
- 272 lbs (123 kg)
- Nom. Conductor DCR
- 4.2 Ohm/1000ft
Characteristics (datasheet)
- Conductor
- 3 pairs, 16 AWG 7x24 bare copper (BC)
- Voltage Rating
- 600 V (TC-ER), 150 V (NPLF)
- Temperature Rating
- 90°C Dry, 90°C Wet; Operating: -30°C to 90°C Dry/Wet
- Shielding
- Inner shield (tape, bi-laminate Alum+Poly, 100% coverage, 18 AWG drain wire per pair) and Outer shield (tape, bi-laminate Alum+Poly, 100% coverage, 16 AWG drain wire)
- Max Current
- 14 Amps per conductor @ 30°C
- Nom. Conductor DCR
- 4.2 Ohm/1000ft
- Nom. Outer Shield DCR
- 3.20 Ohm/1000ft (10.5 Ohm/km)
- Outer Jacket & Diameter
- Black PVC, nominal thickness 0.048 in (1.2 mm), nominal overall diameter 0.476 in (12.1 mm)
- Bend Radius
- 5.7 in (140 mm) stationary and installation min.
- Max Pull Tension
- 272 lbs (123 kg)
- Bulk Cable Weight
- 127 lbs/1000ft
1037A Applications
- Industrial control
- Raceways, cable trays, and ducts
- Digital control
- Instruments (4-20ma, 0-10v)
- Low voltage digital control (24v)
- Encoders
- Control circuits
- Distributed control system (DCS)
- Programmable logic controller (PLC)
- Solenoids
- Valves
- Actuators
- Positioners
Other Belden parts
- 1117A — The Belden 1117A is a Type TX thermocouple cable designed with a single pair of...
- 934077109 — TEST LEAD, VIOLET, 4MM
- 86502CY — The Belden 86502CY is a flexible, shielded two-pair data cable designed for low-...
- 79844ELZ — The Belden 79844ELZ is a high-performance RS-485 communication cable constructed...
- 6071 — The Belden 6071 is a Teck90 1000V power and control cable featuring three 10 AWG...
- 79046 — The Belden 79046 is an ECOFLEX multi-conductor cable featuring four 22 AWG tinne...
- 9250 — The Belden 9250 is a 95Ω twinaxial cable of the RG-22B/U type, constructed with...
- 2211C — The Belden 2211C is a shielded communication and control cable with one pair of...
More Bulk Wire Cable
- 7136WS — The Belden 7136WS is a high-flex, heavy-duty cable designed for continuous flexi...
- 1328A — The Belden 1328A is a high-performance 5-pair 18AWG tinned copper fieldbus cable...
- 78339 — The Belden 78339 is a shielded multi-conductor cable (ECOCABLE) consisting of 9...
- 46383NH — The Belden 46383NH is a 4-conductor speaker cable using 4.0 mm² (56 x 0.30 mm) o...
- 35416 — Belden 35416 is a 16 AWG (26x30) tinned copper lead wire with XLPO thermoset ins...
- 1527A — The Belden 1527A is a UL-listed instrumentation cable consisting of three 16 AWG...
- 27331AS — The Belden 27331AS is a UL Type TC power and control cable with three 16 AWG (7x...
- 79019 — The Belden 79019 is a 2-conductor 16 AWG tinned copper cable with modified polyp...
1037A FAQ
What is 1037A?
1037A is a Bulk Wire Cable from Belden. The 1037A is a black-jacketed instrumentation cable designed for industrial control, digital instruments, and programmable logic controllers (PLCs). It features three pairs of 16 AWG bare copper conductors with PVC-nylon insulation, individual and overall Beldfoil shields, and a black PVC outer jacket. The cable is rated for 600V TC-ER / 150V NPLF, supports a temperature of up to 90°C dry/wet, and is suitable for indoor, outdoor, burial, and sunlight-resistant environments.
Who manufactures 1037A?
1037A is manufactured by Belden.
Where can I download the 1037A datasheet PDF?
The 1037A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 1037A specifications
Click to ask a quick question:
Parameters
| Bend Radius | 5.7 in (140 mm) stationary and installation min. |
| Bulk Cable Weight | 127 lbs/1000ft |
| Conductor | 3 pairs, 16 AWG 7x24 bare copper (BC) |
| Max Current | 14 Amps per conductor @ 30°C |
| Max Pull Tension | 272 lbs (123 kg) |
| Nom. Conductor DCR | 4.2 Ohm/1000ft |
| Nom. Outer Shield DCR | 3.20 Ohm/1000ft (10.5 Ohm/km) |
| Outer Jacket & Diameter | Black PVC, nominal thickness 0.048 in (1.2 mm), nominal overall diameter 0.476 in (12.1 mm) |
| Shielding | Inner shield (tape, bi-laminate Alum+Poly, 100% coverage, 18 AWG drain wire per pair) and Outer shield (tape, bi-laminate Alum+Poly, 100% coverage, 16 AWG drain wire) |
| Temperature Rating | 90°C Dry, 90°C Wet; Operating: -30°C to 90°C Dry/Wet |
| Voltage Rating | 600 V (TC-ER), 150 V (NPLF) |