8318 Datasheet
The Belden 8318 is a computer EIA RS-232 low-capacitance cable featuring 18 twisted pairs of 22 AWG stranded tinned copper conductors with semi-rigid PVC insulation. It is shielded with overall Beldfoil and a tinned copper braid, enclosed in a PVC jacket. This cable is designed for RS-232 extended distance applications, computer communications, low voltage analog and digital control signals, as well as audio and panel wiring.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
8318 Key Specifications
- Max. Current
- 1.4 Amps per Conductor at 25ºC
- Nom. Capacitance Cond-to-Cond
- 35 pF/ft (110 pF/m)
- Nom. Capacitance Cond-to-Other
- 63 pF/ft (210 pF/m)
- UL Voltage Rating
- 300 V (CMG), 300 V (UL AWM 2464)
- Operating Temperature
- -30°C to +80°C
- UL Temperature
- 80°C
- Conductor configuration
- 18 pairs, 22 AWG 7x30 stranded tinned copper
- Max. Pull Tension
- 327.6 lbs (148.6 kg)
Characteristics (datasheet)
- Conductor configuration
- 18 pairs, 22 AWG 7x30 stranded tinned copper
- Nom. Conductor DCR
- 18.2 Ohm/1000ft
- Nom. Capacitance Cond-to-Cond
- 35 pF/ft (110 pF/m)
- Nom. Capacitance Cond-to-Other
- 63 pF/ft (210 pF/m)
- Max. Current
- 1.4 Amps per Conductor at 25ºC
- UL Voltage Rating
- 300 V (CMG), 300 V (UL AWM 2464)
- Operating Temperature
- -30°C to +80°C
- Overall Cable Diameter (Nominal)
- 0.540 in (13.7 mm)
Absolute Maximum Ratings
- UL Voltage Rating
- 300 V (CMG), 300 V (UL AWM 2464)
- Max. Current
- 1.4 Amps per Conductor at 25ºC
- UL Temperature
- 80°C
- Operating Temperature
- -30°C to +80°C
- Max. Pull Tension
- 327.6 lbs (148.6 kg)
8318 Applications
- RS-232 Extended Distance Applications
- Computer Communications
- Low Voltage Analog Signals (4-20ma, 0-10v, ...)
- Low Voltage Digital Control (24v, ...)
- Audio
- Panel Wiring
Other Belden parts
- 5342FE — The Belden 5342FE is a riser-CMR security and sound cable containing three 18 AW...
- 25506D — Belden 25506D is a Canadian TC-ACIC 600 V instrumentation cable built with one 1...
- 89705 — The Belden 89705 is a plenum-rated, 5-pair digital audio and computer communicat...
- 78035 — The Belden 78035 is an ECOCABLE consisting of 5 pairs of 22 AWG stranded tinned...
- 89292 — The Belden 89292 is a plenum-rated, RG11 analog video cable featuring a 14 AWG s...
- 24516D — Belden 24516D is a Canadian Instrumentation Cable (TC-ACIC) rated 600 V RMS, wit...
- 934060100 — 60V 16A Black Insulated Cable Plug, 500mm Long, -15°C to 70°C
- 5482C — The Belden 5482C is a XTRAGUARD 1 shielded multi-conductor cable featuring 2 pai...
More Bulk Wire Cable
- 6376 — The Belden 6376 is a communication and control cable with 5 pairs of 22 AWG tinn...
- 70038 — The Belden 70038 is a discontinued analog audio cable consisting of 10 pairs of...
- 5859 — The Belden 5859 is a single-conductor 14 AWG hook-up wire featuring silver-plate...
- 1403A — The Belden 1403A is a SCSI cable designed for SCSI II applications. It features...
- 8649 — The Belden 8649 is an unshielded, 2-conductor 20 AWG speaker cable featuring par...
- 86182CY — The Belden 86182CY is a XTRAGUARD FLEX two-conductor 18 AWG tinned copper cable...
- 88106 — The Belden 88106 is a plenum-rated, 6-pair EIA RS-232/422 cable designed for com...
- 1055A — The Belden 1055A is a UL-listed instrumentation cable featuring two 16 AWG bare...
8318 FAQ
What is 8318?
8318 is a Bulk Wire Cable from Belden. The Belden 8318 is a computer EIA RS-232 low-capacitance cable featuring 18 twisted pairs of 22 AWG stranded tinned copper conductors with semi-rigid PVC insulation. It is shielded with overall Beldfoil and a tinned copper braid, enclosed in a PVC jacket. This cable is designed for RS-232 extended distance applications, computer communications, low voltage analog and digital control signals, as well as audio and panel wiring.
Who manufactures 8318?
8318 is manufactured by Belden.
Where can I download the 8318 datasheet PDF?
The 8318 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 8318 specifications
Click to ask a quick question:
Parameters
| Conductor configuration | 18 pairs, 22 AWG 7x30 stranded tinned copper |
| Max. Current | 1.4 Amps per Conductor at 25ºC |
| Max. Pull Tension | 327.6 lbs (148.6 kg) |
| Nom. Capacitance Cond-to-Cond | 35 pF/ft (110 pF/m) |
| Nom. Capacitance Cond-to-Other | 63 pF/ft (210 pF/m) |
| Nom. Conductor DCR | 18.2 Ohm/1000ft |
| Operating Temperature | -30°C to +80°C |
| Overall Cable Diameter (Nominal) | 0.540 in (13.7 mm) |
| UL Temperature | 80°C |