29506 Datasheet

BeldenBulk Wire Cable

Belden 29506 is a flexible 600/1000 V motor supply cable designed for Variable Frequency Drives (VFD), AC motor and drive systems, and Class 1 Division 2 hazardous locations. It contains three 4 AWG tinned copper conductors with XLPE insulation, an insulated 4 AWG ground, four uninsulated 10 AWG tinned copper ground/drain wires, an overall shielded construction, and a black PVC jacket rated 90 °C dry/wet. The cable complies with TC-ER, WTTC, UL flexible motor supply cable, AWM, CIC/TC, and RoHS/CE requirements.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

29506 Key Specifications

Max Current
95 Amps per Conductor at 30ºC
Voltage Rating
1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) 1000 V (AWM I/II A/B)
Temperature Rating
UL Temperature: 90°C Dry, 90°C Wet; Operating: -40°C To +90°C
Bulk Cable Weight
1061 lbs/1000ft (1579 kg/km)
Conductors
3 x 4 AWG (7x19x25) Tinned Copper
Insulated Ground
1 x 4 AWG (7x19x25) Tinned Copper
Max Pull Tension
2420 lbs (1100 kg)
Overall Cable Diameter
1.113 in (28.27 mm)

Characteristics (datasheet)

Voltage Rating
1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) 1000 V (AWM I/II A/B)
Temperature Rating
UL Temperature: 90°C Dry, 90°C Wet; Operating: -40°C To +90°C
Conductors
3 x 4 AWG (7x19x25) Tinned Copper
Insulated Ground
1 x 4 AWG (7x19x25) Tinned Copper
Uninsulated Ground Wires
4 x 10 AWG (105x30) Tinned Copper (4 Totaling 4 AWG)
Shield
Tri-Laminate (Alum+Poly+Alum) Tape 100% + Tinned Copper Braid 86%; Drainwire 10 AWG (105x30) TC
Overall Cable Diameter
1.113 in (28.27 mm)
Max Current
95 Amps per Conductor at 30ºC
Max Pull Tension
2420 lbs (1100 kg)
Bulk Cable Weight
1061 lbs/1000ft (1579 kg/km)

29506 Applications

  • Variable Frequency Drives (VFD)
  • AC Motor and Drive Systems
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 934521100 — Y-SPLITTER, 1 SOCKET, 2 PLUG, SUNCON; Insulator Colour: Black; Test Connector Ty...
  • 1389 — The Belden 1389 is a heavy-duty, 2-conductor, 2 AWG bare copper cable with XLPE...
  • 5523 — The Belden 5523 is a shielded 3-conductor, 18 AWG stranded tinned copper cable w...
  • 8233 — The Belden 8233 is a video triax cable of RG11 type, featuring a 14 AWG solid ba...
  • 80119 — The Belden 80119 is a 10-conductor, 22 AWG tinned copper cable with MPPE insulat...
  • 8732 — The Belden 8732 is a shielded, 2-pair 22 AWG tinned copper electronic cable with...
  • 3543 — The Belden 3543 is a 30-conductor hook-up wire cable featuring 24 AWG stranded t...
  • 58903 — The Belden 58903 is a shielded communication and control cable designed for indo...

More Bulk Wire Cable

  • 5383C — The 5383C is a 3-conductor, 18 AWG tinned copper shielded cable with PVC insulat...
  • 1685ANH — The Belden 1685ANH is an indoor, Category 6A shielded horizontal and building ba...
  • 5329UL — The Belden 5329UL is a riser-grade (FPLR) indoor fire alarm cable featuring 12 s...
  • 2414C — The 2414C is a 4-conductor, 20 AWG tinned copper communication and control cable...
  • 1887ELV — The Belden 1887ELV is a Category 7 enhanced premise horizontal and building back...
  • 35614 — Belden 35614 is a 14 AWG stranded tinned copper lead wire with XLPO/XLPE thermos...
  • 25493 — The Belden 25493 is an XTRAGUARD 2 cable consisting of 3 pairs of 24 AWG (7x32)...
  • 79245 — The Belden 79245 is a 3-conductor, 22 AWG tinned copper cable with mPPE insulati...

29506 FAQ

What is 29506?

29506 is a Bulk Wire Cable from Belden. Belden 29506 is a flexible 600/1000 V motor supply cable designed for Variable Frequency Drives (VFD), AC motor and drive systems, and Class 1 Division 2 hazardous locations. It contains three 4 AWG tinned copper conductors with XLPE insulation, an insulated 4 AWG ground, four uninsulated 10 AWG tinned copper ground/drain wires, an overall shielded construction, and a black PVC jacket rated 90 °C dry/wet. The cable complies with TC-ER, WTTC, UL flexible motor supply cable, AWM, CIC/TC, and RoHS/CE requirements.

Who manufactures 29506?

29506 is manufactured by Belden.

Where can I download the 29506 datasheet PDF?

The 29506 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 29506 specifications

AI Powered

Click to ask a quick question:

Parameters

Bulk Cable Weight1061 lbs/1000ft (1579 kg/km)
Conductors3 x 4 AWG (7x19x25) Tinned Copper
Insulated Ground1 x 4 AWG (7x19x25) Tinned Copper
Max Current95 Amps per Conductor at 30ºC
Max Pull Tension2420 lbs (1100 kg)
Overall Cable Diameter1.113 in (28.27 mm)
ShieldTri-Laminate (Alum+Poly+Alum) Tape 100% + Tinned Copper Braid 86%; Drainwire 10 AWG (105x30) TC
Temperature RatingUL Temperature: 90°C Dry, 90°C Wet; Operating: -40°C To +90°C
Uninsulated Ground Wires4 x 10 AWG (105x30) Tinned Copper (4 Totaling 4 AWG)
Voltage Rating1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) 1000 V (AWM I/II A/B)