5329UL Datasheet
The Belden 5329UL is a riser-grade (FPLR) indoor fire alarm cable featuring 12 solid bare copper conductors of 18 AWG size with polypropylene insulation and a PVC outer jacket with a ripcord. It is designed for use in fire alarm, monitor/detection, and audio, control, initiating, and notification circuits. The cable is rated for a UL voltage of 300 V, a maximum current of 3.5 Amps per conductor, and an operating temperature range of -20°C to +75°C.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
5329UL Key Specifications
- Max. Current
- 3.5 Amps per Conductor at 25ºC
- Nom. Capacitance Cond-to-Cond
- 22 pF/ft (72 pF/m)
- UL Voltage Rating
- 300 V
- Operating temperature
- -20°C To +75°C (UL Temperature: 75°C)
- Conductor size and material
- 18 AWG solid Bare Copper (BC), 12 conductors
- Flammability / Compliance
- UL1666 Riser, NEC Article 760, FPLR
- Nom. Conductor DCR
- 6.4 Ohm/1000ft
- Nominal overall diameter
- 0.262 in
Characteristics (datasheet)
- Conductor size and material
- 18 AWG solid Bare Copper (BC), 12 conductors
- Nominal overall diameter
- 0.262 in
- UL Voltage Rating
- 300 V
- Max. Current
- 3.5 Amps per Conductor at 25ºC
- Nom. Conductor DCR
- 6.4 Ohm/1000ft
- Nom. Capacitance Cond-to-Cond
- 22 pF/ft (72 pF/m)
- Operating temperature
- -20°C To +75°C (UL Temperature: 75°C)
- Flammability / Compliance
- UL1666 Riser, NEC Article 760, FPLR
5329UL Applications
- Fire Alarm
- Monitor/Detection
- Audio Circuits
- Control Circuits
- Initiating Circuits
- Notification Circuits
Other Belden parts
- 1892C — The Belden 1892C is a communication and control cable featuring two 12 AWG stran...
- 6163 — The Belden 6163 is a Teck90 1000V cable with 3+G bare copper conductors (3/0+6 A...
- 1815P — The Belden 1815P is a plenum-rated (CMP) audio snake cable featuring 4 pairs of...
- 37501 — Belden 37501 is a #1 AWG (210x24) tinned copper rubber lead wire with EPDM insul...
- 80144 — The Belden 80144 is a zero-halogen, 5-conductor 16 AWG tinned copper cable featu...
- 78202 — The Belden 78202 ECOCABLE is a 2-pair, 28 AWG tinned copper conductor cable with...
- 28324A — The Belden 28324A is a 25-conductor, 16 AWG (7x24 bare copper) power and control...
- 45483 — The Belden 45483 is an XTRAGUARD 4 cable with 3 pairs of 22 AWG (7x30) stranded...
More Bulk Wire Cable
- 9250 — The Belden 9250 is a 95Ω twinaxial cable of the RG-22B/U type, constructed with...
- 21606 — Belden 21606 is a CSA Type TC-CIC 600 V tray cable with eight 10 AWG bare copper...
- 8748 — The Belden 8748 is a 9-pair, 22 AWG tinned copper multi-conductor cable with PVC...
- 86205 — The Belden 86205 is a 5-conductor, 24 AWG tinned copper cable with semi-rigid PV...
- 83719 — The Belden 83719 is a high-temperature, shielded multi-conductor cable featuring...
- 70069CH — The Belden 70069CH is a 2-pair AES/EBU digital audio cable with a 22AWG conducto...
- 78329 — The Belden 78329 is an ECOCABLE featuring 9 pairs of 24 AWG tinned copper conduc...
- 8670 — The Belden 8670 is a tinned copper braided cable (TC Braid) with a 3.4 AWG equiv...
5329UL FAQ
What is 5329UL?
5329UL is a Bulk Wire Cable from Belden. The Belden 5329UL is a riser-grade (FPLR) indoor fire alarm cable featuring 12 solid bare copper conductors of 18 AWG size with polypropylene insulation and a PVC outer jacket with a ripcord. It is designed for use in fire alarm, monitor/detection, and audio, control, initiating, and notification circuits. The cable is rated for a UL voltage of 300 V, a maximum current of 3.5 Amps per conductor, and an operating temperature range of -20°C to +75°C.
Who manufactures 5329UL?
5329UL is manufactured by Belden.
Where can I download the 5329UL datasheet PDF?
The 5329UL datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 5329UL specifications
Click to ask a quick question:
Parameters
| Conductor size and material | 18 AWG solid Bare Copper (BC), 12 conductors |
| Flammability / Compliance | UL1666 Riser, NEC Article 760, FPLR |
| Max. Current | 3.5 Amps per Conductor at 25ºC |
| Nom. Capacitance Cond-to-Cond | 22 pF/ft (72 pF/m) |
| Nom. Conductor DCR | 6.4 Ohm/1000ft |
| Nominal overall diameter | 0.262 in |
| Operating temperature | -20°C To +75°C (UL Temperature: 75°C) |
| UL Voltage Rating | 300 V |