28160A Datasheet
The Belden 28160A is a UL Type TC power and control cable consisting of four 2 AWG bare copper conductors plus one 6 AWG bare copper ground conductor. It has PVC/nylon insulation and a black PVC outer jacket, is rated 600 V and 90 °C dry/wet, and is suitable for indoor, outdoor, sunlight-resistant, and direct burial use including Class 1 Division 2 hazardous locations. A 5,000 ft reel put-up (item 28160A 0105000) is available with a ripcord in the jacket.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28160A Key Specifications
- Voltage rating
- 600 V (TC-ER)
- Temperature rating
- 90°C Dry, 90°C Wet; operating -30°C to 90°C wet/dry
- Bulk cable weight
- 1211 lbs/1000 ft
- Conductor(s)
- 4 x 2 AWG, 7x10 stranding, bare copper, 0.16 Ohm/1000ft DCR, 104 Amps per conductor at 30°C
- Ground conductor
- 1 x 6 AWG, 7x14 stranding, bare copper, 0.4 Ohm/1000ft (1.3 Ohm/km) DCR, 78 Amps at 25°C
- Insulation
- PVC/Nylon, 0.042 in (1.1 mm) nominal thickness, 0.367 in (9.32 mm) nominal diameter, black and numbered
- Max. pull tension
- 3496.3 lbs (1585.9 kg)
- Outer jacket
- PVC, 0.083 in (2.1 mm) nominal thickness, 1.106 in (28.09 mm) nominal diameter, ripcord yes
Characteristics (datasheet)
- Conductor(s)
- 4 x 2 AWG, 7x10 stranding, bare copper, 0.16 Ohm/1000ft DCR, 104 Amps per conductor at 30°C
- Ground conductor
- 1 x 6 AWG, 7x14 stranding, bare copper, 0.4 Ohm/1000ft (1.3 Ohm/km) DCR, 78 Amps at 25°C
- Voltage rating
- 600 V (TC-ER)
- Temperature rating
- 90°C Dry, 90°C Wet; operating -30°C to 90°C wet/dry
- Insulation
- PVC/Nylon, 0.042 in (1.1 mm) nominal thickness, 0.367 in (9.32 mm) nominal diameter, black and numbered
- Outer jacket
- PVC, 0.083 in (2.1 mm) nominal thickness, 1.106 in (28.09 mm) nominal diameter, ripcord yes
- Max. pull tension
- 3496.3 lbs (1585.9 kg)
- Bulk cable weight
- 1211 lbs/1000 ft
28160A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 5670 — The Belden 5670 is a 7-conductor, 26 AWG tinned copper cable featuring semi-rigi...
- 78042 — The Belden 78042 is a 2-conductor, 20 AWG tinned copper ECOCABLE with modified p...
- 76506TS — The Belden 76506TS is a MachFlex™ high-flexibility cable designed for demanding...
- 27140A — Belden 27140A is a four-conductor UL Type TC power and control cable built with...
- 57015 — The Belden 57015 is a plenum-rated, overall shielded multi-conductor communicati...
- 933003001 — HIRSCHMANN TEST AND MEASUREMENT 933003001 TEST LEAD KIT, AUTOMOTIVE
- 35614 — Belden 35614 is a 14 AWG stranded tinned copper lead wire with XLPO/XLPE thermos...
- 1865A — The Belden 1865A is a sub-miniature serial digital coaxial cable (RG Type: Sub-m...
More Bulk Wire Cable
- 5078C — The Belden 5078C is an XTRAGUARD 1, 8-conductor 16 AWG stranded tinned copper ca...
- 70072CH — The Belden 70072CH is a 12-pair digital audio cable designed for professional st...
- 9118 — The Belden 9118 is a CATV video coaxial cable (RG6 type) featuring an 18 AWG sol...
- 5094C — The 5094C is a 4-conductor, 24 AWG tinned copper shielded cable with semi-rigid...
- 35620 — Belden 35620 is a 20 AWG stranded tinned copper rubber lead wire with XLPO insul...
- 65418 — The Belden 65418 is an XTRAGUARD FLEX 18-conductor 14 AWG bare copper control ca...
- 76303WS — The 76303WS is a MachFlex™ high-flex 3-conductor 22AWG tinned copper cable with...
- 6825 — The Belden 6825 is a single-conductor 18 AWG hook-up wire with a bare copper con...
28160A FAQ
What is 28160A?
28160A is a Bulk Wire Cable from Belden. The Belden 28160A is a UL Type TC power and control cable consisting of four 2 AWG bare copper conductors plus one 6 AWG bare copper ground conductor. It has PVC/nylon insulation and a black PVC outer jacket, is rated 600 V and 90 °C dry/wet, and is suitable for indoor, outdoor, sunlight-resistant, and direct burial use including Class 1 Division 2 hazardous locations. A 5,000 ft reel put-up (item 28160A 0105000) is available with a ripcord in the jacket.
Who manufactures 28160A?
28160A is manufactured by Belden.
Where can I download the 28160A datasheet PDF?
The 28160A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28160A specifications
Click to ask a quick question:
Parameters
| Bulk cable weight | 1211 lbs/1000 ft |
| Conductor(s) | 4 x 2 AWG, 7x10 stranding, bare copper, 0.16 Ohm/1000ft DCR, 104 Amps per conductor at 30°C |
| Ground conductor | 1 x 6 AWG, 7x14 stranding, bare copper, 0.4 Ohm/1000ft (1.3 Ohm/km) DCR, 78 Amps at 25°C |
| Insulation | PVC/Nylon, 0.042 in (1.1 mm) nominal thickness, 0.367 in (9.32 mm) nominal diameter, black and numbered |
| Max. pull tension | 3496.3 lbs (1585.9 kg) |
| Outer jacket | PVC, 0.083 in (2.1 mm) nominal thickness, 1.106 in (28.09 mm) nominal diameter, ripcord yes |
| Temperature rating | 90°C Dry, 90°C Wet; operating -30°C to 90°C wet/dry |
| Voltage rating | 600 V (TC-ER) |