27140A Datasheet
Belden 27140A is a four-conductor UL Type TC power and control cable built with 10 AWG (7x18) bare copper conductors, PVC-nylon insulation, and a black PVC jacket. It is rated for 600 V and 90 °C dry / 75 °C wet operation, with a wet/dry operating range of -30 °C to 90 °C. The cable is approved for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial use, including Class 1 Division 2 hazardous locations.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
27140A Key Specifications
- Max current
- 32 Amps per conductor at 30 °C
- Voltage rating
- 600 V
- Temperature rating
- 90 °C dry, 75 °C wet; wet/dry -30 °C to 90 °C
- Bend radius (stationary/installation)
- 1.956 in (49.68 mm) / 2.445 in
- Conductor configuration
- 4 conductors, 10 AWG, 7x18 stranding, bare copper
- Conductor DCR
- 1.06 Ohm/1000ft nominal
- Insulation diameter
- 0.164 in (4.17 mm) nominal
- Insulation material/thickness
- PVC/Nylon, 0.024 in (0.61 mm) nominal thickness
Characteristics (datasheet)
- Conductor configuration
- 4 conductors, 10 AWG, 7x18 stranding, bare copper
- Insulation material/thickness
- PVC/Nylon, 0.024 in (0.61 mm) nominal thickness
- Insulation diameter
- 0.164 in (4.17 mm) nominal
- Jacket material/thickness
- Black PVC, 0.047 in (1.2 mm) nominal thickness
- Overall cable diameter
- 0.489 in nominal
- Conductor DCR
- 1.06 Ohm/1000ft nominal
- Max current
- 32 Amps per conductor at 30 °C
- Voltage rating
- 600 V
- Temperature rating
- 90 °C dry, 75 °C wet; wet/dry -30 °C to 90 °C
- Bend radius (stationary/installation)
- 1.956 in (49.68 mm) / 2.445 in
- Max pull tension / weight
- 542 lbs (246 kg) / 197 lbs/1000ft
27140A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 2401C — The Belden 2401C is a 2-conductor, 22 AWG tinned copper communication and contro...
- 5875 — The Belden 5875 is a single-conductor, 22 AWG silver-plated copper hook-up wire...
- 5468C — The 5468C is an 8-conductor, 20 AWG tinned copper shielded cable with PVC insula...
- 70267PU — The Belden 70267PU is a PUR distribution box cable featuring 8 x 0.50 mm² and 3...
- 3066A — The Belden 3066A is a UL-listed instrumentation cable consisting of 16 triads of...
- 5677 — The Belden 5677 is a shielded, 6-conductor 26 AWG tinned copper cable with semi-...
- 1561 — The Belden 1561 is a single-conductor, 22 AWG solid tinned copper hook-up wire w...
- 1280 — The Belden 1280 is a heavy-duty power and control cable rated at 1000V, featurin...
More Bulk Wire Cable
- 25452 — The Belden 25452 is an XTRAGUARD 2 cable consisting of 2 pairs of 20 AWG (7x28)...
- 70034 — The Belden 70034 is a discontinued 12-pair analog audio cable featuring 26AWG ox...
- 9248 — The Belden 9248 is a 75 Ohm RG-6 analog video coaxial cable featuring an 18 AWG...
- 9260 — The Belden 9260 is a 6-conductor 20 AWG tinned copper cable with PVC insulation,...
- 35416 — Belden 35416 is a 16 AWG (26x30) tinned copper lead wire with XLPO thermoset ins...
- 8167 — The Belden 8167 is a computer EIA RS-232/422 digital audio cable containing 7 in...
- 58119 — The Belden 58119 is a plenum-rated communication and control cable featuring nin...
- 28160A — The Belden 28160A is a UL Type TC power and control cable consisting of four 2 A...
27140A FAQ
What is 27140A?
27140A is a Bulk Wire Cable from Belden. Belden 27140A is a four-conductor UL Type TC power and control cable built with 10 AWG (7x18) bare copper conductors, PVC-nylon insulation, and a black PVC jacket. It is rated for 600 V and 90 °C dry / 75 °C wet operation, with a wet/dry operating range of -30 °C to 90 °C. The cable is approved for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial use, including Class 1 Division 2 hazardous locations.
Who manufactures 27140A?
27140A is manufactured by Belden.
Where can I download the 27140A datasheet PDF?
The 27140A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 27140A specifications
Click to ask a quick question:
Parameters
| Bend radius (stationary/installation) | 1.956 in (49.68 mm) / 2.445 in |
| Conductor configuration | 4 conductors, 10 AWG, 7x18 stranding, bare copper |
| Conductor DCR | 1.06 Ohm/1000ft nominal |
| Insulation diameter | 0.164 in (4.17 mm) nominal |
| Insulation material/thickness | PVC/Nylon, 0.024 in (0.61 mm) nominal thickness |
| Jacket material/thickness | Black PVC, 0.047 in (1.2 mm) nominal thickness |
| Max current | 32 Amps per conductor at 30 °C |
| Max pull tension / weight | 542 lbs (246 kg) / 197 lbs/1000ft |
| Overall cable diameter | 0.489 in nominal |
| Temperature rating | 90 °C dry, 75 °C wet; wet/dry -30 °C to 90 °C |
| Voltage rating | 600 V |