28151A Datasheet
The Belden 28151A is a UL Type TC (1277) power and control cable with four 8 AWG bare copper conductors and one 10 AWG bare copper ground wire, insulated with PVC/nylon and covered by a black PVC jacket with ripcord. It is rated for 600 V and 90 °C dry/wet operation, with an operating range of -30 °C to 90 °C, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial use, including Class 1 Division 2 hazardous locations.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28151A Key Specifications
- UL Voltage Rating
- 600 V
- Temperature
- UL: 90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C
- Conductor(s)
- 4 x 8 AWG, 7x16 stranded bare copper
- Ground Wire
- 1 x 10 AWG, 7x18 stranded bare copper
- Insulation
- PVC/Nylon, 0.035 in (0.89 mm) nominal thickness
- Max. Pull Tension
- 990.4 lbs (449.2 kg)
- Outer Jacket
- Black PVC, 0.063 in (1.6 mm) nominal thickness, ripcord yes
- Overall Cable Diameter (Nominal)
- 0.647 in (16.4 mm)
Characteristics (datasheet)
- Conductor(s)
- 4 x 8 AWG, 7x16 stranded bare copper
- Ground Wire
- 1 x 10 AWG, 7x18 stranded bare copper
- Insulation
- PVC/Nylon, 0.035 in (0.89 mm) nominal thickness
- Outer Jacket
- Black PVC, 0.063 in (1.6 mm) nominal thickness, ripcord yes
- Overall Cable Diameter (Nominal)
- 0.647 in (16.4 mm)
- UL Voltage Rating
- 600 V
- Temperature
- UL: 90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C
- Max. Pull Tension
- 990.4 lbs (449.2 kg)
28151A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 2101A — The Belden 2101A is a 2-pair 18AWG tinned copper fieldbus cable with XLPO insula...
- 934059707 — HIRSCHMANN TEST AND MEASUREMENT 934059707 Test Lead, 4mm Banana Plug to 4mm...
- 79020 — The Belden 79020 is a 3-conductor, 16 AWG tinned copper cable with mPPE insulati...
- 6377 — The Belden 6377 is a communication and control cable consisting of 6 pairs of 22...
- 85247CY — The Belden 85247CY (Alpha Wire) is a 7-conductor, 24 AWG XTRAGUARD FLEX continuo...
- 5409 — The Belden 5409 is a 9-conductor, 22 AWG tinned copper cable with PVC insulation...
- 28110A — The Belden 28110A is a UL Type TC (1277) power and control cable with three 12 A...
- 8628 — The Belden 8628 is a heavy-duty electronic cable featuring seven 14 AWG stranded...
More Bulk Wire Cable
- 5425 — The Belden 5425 is a multi-conductor, 18 AWG tinned copper cable with PVC insula...
- 2423C — The Belden 2423C is a 3-conductor, 18 AWG tinned copper communication and contro...
- 25463 — Belden part 25463 is an XTRAGUARD 2 three-conductor 20 AWG (7/28) tinned-copper...
- 28611A — The Belden 28611A is a 25-conductor Type TC power and control cable with 18 AWG...
- 6820 — The Belden 6820 is a single-conductor, 28 AWG stranded bare copper hook-up wire...
- 70071CH — The Belden 70071CH is an 8-pair AES/EBU digital audio cable with 22AWG stranded...
- 9698MN — The 9698MN is a SpaceMaker™ multi-pair cable consisting of 6 pairs of 24AWG tinn...
- 6076 — The Belden 6076 is a Teck90 600V, 2+G conductor cable with 14 AWG bare copper wi...
28151A FAQ
What is 28151A?
28151A is a Bulk Wire Cable from Belden. The Belden 28151A is a UL Type TC (1277) power and control cable with four 8 AWG bare copper conductors and one 10 AWG bare copper ground wire, insulated with PVC/nylon and covered by a black PVC jacket with ripcord. It is rated for 600 V and 90 °C dry/wet operation, with an operating range of -30 °C to 90 °C, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial use, including Class 1 Division 2 hazardous locations.
Who manufactures 28151A?
28151A is manufactured by Belden.
Where can I download the 28151A datasheet PDF?
The 28151A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28151A specifications
Click to ask a quick question:
Parameters
| Conductor(s) | 4 x 8 AWG, 7x16 stranded bare copper |
| Ground Wire | 1 x 10 AWG, 7x18 stranded bare copper |
| Insulation | PVC/Nylon, 0.035 in (0.89 mm) nominal thickness |
| Max. Pull Tension | 990.4 lbs (449.2 kg) |
| Outer Jacket | Black PVC, 0.063 in (1.6 mm) nominal thickness, ripcord yes |
| Overall Cable Diameter (Nominal) | 0.647 in (16.4 mm) |
| Temperature | UL: 90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C |
| UL Voltage Rating | 600 V |