28151A Datasheet

BeldenBulk Wire Cable

The Belden 28151A is a UL Type TC (1277) power and control cable with four 8 AWG bare copper conductors and one 10 AWG bare copper ground wire, insulated with PVC/nylon and covered by a black PVC jacket with ripcord. It is rated for 600 V and 90 °C dry/wet operation, with an operating range of -30 °C to 90 °C, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial use, including Class 1 Division 2 hazardous locations.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

28151A Key Specifications

UL Voltage Rating
600 V
Temperature
UL: 90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C
Conductor(s)
4 x 8 AWG, 7x16 stranded bare copper
Ground Wire
1 x 10 AWG, 7x18 stranded bare copper
Insulation
PVC/Nylon, 0.035 in (0.89 mm) nominal thickness
Max. Pull Tension
990.4 lbs (449.2 kg)
Outer Jacket
Black PVC, 0.063 in (1.6 mm) nominal thickness, ripcord yes
Overall Cable Diameter (Nominal)
0.647 in (16.4 mm)

Characteristics (datasheet)

Conductor(s)
4 x 8 AWG, 7x16 stranded bare copper
Ground Wire
1 x 10 AWG, 7x18 stranded bare copper
Insulation
PVC/Nylon, 0.035 in (0.89 mm) nominal thickness
Outer Jacket
Black PVC, 0.063 in (1.6 mm) nominal thickness, ripcord yes
Overall Cable Diameter (Nominal)
0.647 in (16.4 mm)
UL Voltage Rating
600 V
Temperature
UL: 90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C
Max. Pull Tension
990.4 lbs (449.2 kg)

28151A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 2101A — The Belden 2101A is a 2-pair 18AWG tinned copper fieldbus cable with XLPO insula...
  • 934059707 — HIRSCHMANN TEST AND MEASUREMENT 934059707 Test Lead, 4mm Banana Plug to 4mm...
  • 79020 — The Belden 79020 is a 3-conductor, 16 AWG tinned copper cable with mPPE insulati...
  • 6377 — The Belden 6377 is a communication and control cable consisting of 6 pairs of 22...
  • 85247CY — The Belden 85247CY (Alpha Wire) is a 7-conductor, 24 AWG XTRAGUARD FLEX continuo...
  • 5409 — The Belden 5409 is a 9-conductor, 22 AWG tinned copper cable with PVC insulation...
  • 28110A — The Belden 28110A is a UL Type TC (1277) power and control cable with three 12 A...
  • 8628 — The Belden 8628 is a heavy-duty electronic cable featuring seven 14 AWG stranded...

More Bulk Wire Cable

  • 5425 — The Belden 5425 is a multi-conductor, 18 AWG tinned copper cable with PVC insula...
  • 2423C — The Belden 2423C is a 3-conductor, 18 AWG tinned copper communication and contro...
  • 25463 — Belden part 25463 is an XTRAGUARD 2 three-conductor 20 AWG (7/28) tinned-copper...
  • 28611A — The Belden 28611A is a 25-conductor Type TC power and control cable with 18 AWG...
  • 6820 — The Belden 6820 is a single-conductor, 28 AWG stranded bare copper hook-up wire...
  • 70071CH — The Belden 70071CH is an 8-pair AES/EBU digital audio cable with 22AWG stranded...
  • 9698MN — The 9698MN is a SpaceMaker™ multi-pair cable consisting of 6 pairs of 24AWG tinn...
  • 6076 — The Belden 6076 is a Teck90 600V, 2+G conductor cable with 14 AWG bare copper wi...

28151A FAQ

What is 28151A?

28151A is a Bulk Wire Cable from Belden. The Belden 28151A is a UL Type TC (1277) power and control cable with four 8 AWG bare copper conductors and one 10 AWG bare copper ground wire, insulated with PVC/nylon and covered by a black PVC jacket with ripcord. It is rated for 600 V and 90 °C dry/wet operation, with an operating range of -30 °C to 90 °C, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial use, including Class 1 Division 2 hazardous locations.

Who manufactures 28151A?

28151A is manufactured by Belden.

Where can I download the 28151A datasheet PDF?

The 28151A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 28151A specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor(s)4 x 8 AWG, 7x16 stranded bare copper
Ground Wire1 x 10 AWG, 7x18 stranded bare copper
InsulationPVC/Nylon, 0.035 in (0.89 mm) nominal thickness
Max. Pull Tension990.4 lbs (449.2 kg)
Outer JacketBlack PVC, 0.063 in (1.6 mm) nominal thickness, ripcord yes
Overall Cable Diameter (Nominal)0.647 in (16.4 mm)
TemperatureUL: 90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C
UL Voltage Rating600 V