The Belden 28150A is a UL Type TC (1277) power and control cable rated for 600 V, with three 8 AWG bare copper conductors and one 10 AWG bare copper ground wire, PVC/nylon insulation, and a black PVC outer jacket. It is rated 90 °C dry and 90 °C wet, is sunlight resistant and suitable for direct burial, and is listed for Class 1 Division 2 hazardous locations. Suitable applications are power and control applications up to 600 V.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

28150A Key Specifications

Max Current
55 Amps per Conductor at 30ºC (conductors); 40 Amps per Conductor at 30ºC (ground wire)
Rated Voltage
600 V
Temperature Rating
90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
Bend Radius
Stationary Min. 2.38 in (60.5 mm); Installation Min. 2.975 in (75.57 mm)
Conductors
3 x 8 AWG (7x16) bare copper + 1 x 10 AWG (7x18) bare copper ground wire
Max Pull Tension
772 lbs (350 kg)
Nominal Conductor DCR
0.64 Ohm/1000ft (conductors); 1.08 Ohm/1000ft (ground wire)
Overall Cable Diameter
0.595 in (15.1 mm)

Characteristics (datasheet)

Rated Voltage
600 V
Temperature Rating
90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
Conductors
3 x 8 AWG (7x16) bare copper + 1 x 10 AWG (7x18) bare copper ground wire
Max Current
55 Amps per Conductor at 30ºC (conductors); 40 Amps per Conductor at 30ºC (ground wire)
Nominal Conductor DCR
0.64 Ohm/1000ft (conductors); 1.08 Ohm/1000ft (ground wire)
Overall Cable Diameter
0.595 in (15.1 mm)
Max Pull Tension
772 lbs (350 kg)
Bend Radius
Stationary Min. 2.38 in (60.5 mm); Installation Min. 2.975 in (75.57 mm)

28150A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 79236 — The Belden 79236 is a heavy-duty, shielded 3-conductor 10 AWG tinned copper cabl...
  • 35416 — Belden 35416 is a 16 AWG (26x30) tinned copper lead wire with XLPO thermoset ins...
  • 9941 — The Belden 9941 is a computer EIA RS-232 cable with five 22 AWG stranded tinned...
  • 9318 — The Belden 9318 is a high-performance instrumentation cable consisting of a sing...
  • 9217 — The Belden 9217 is a heavy-duty 10 AWG solid bare copper coaxial cable (RG 217/U...
  • 89730 — The Belden 89730 is a 3-pair, 24 AWG stranded tinned copper conductor cable desi...
  • 23539D — The Belden 23539D is a Canadian instrumentation cable (TC-ACIC) rated at 300 V,...
  • 78384 — The part 78384 is a 4-pair 22 AWG tinned copper conductor ECOCABLE with modified...

More Bulk Wire Cable

  • 6402FE — The Belden 6402FE is a plenum-rated (CMP) security and sound cable featuring fou...
  • 8870MN — The Belden 8870MN is a SpaceMaker™ 5-conductor cable featuring 18 AWG tinned cop...
  • 2106A — The Belden 2106A is a 20-pair 18 AWG tinned copper fieldbus cable with cross-lin...
  • 1492A — The Belden 1492A is a UL-listed instrumentation and control cable featuring two...
  • 79052 — The Belden 79052 is a 4-conductor, 24 AWG tinned copper cable with modified poly...
  • 2112A — The Belden 2112A is an 8-pair 16AWG tinned copper fieldbus cable featuring XLPO...
  • 8741 — The Belden 8741 is an electronic cable consisting of 2 pairs of 22 AWG solid tin...
  • 89182 — The Belden 89182 is a 150Ω twinaxial cable featuring a single pair of 22 AWG tin...

28150A FAQ

What is 28150A?

28150A is a Bulk Wire Cable from Belden. The Belden 28150A is a UL Type TC (1277) power and control cable rated for 600 V, with three 8 AWG bare copper conductors and one 10 AWG bare copper ground wire, PVC/nylon insulation, and a black PVC outer jacket. It is rated 90 °C dry and 90 °C wet, is sunlight resistant and suitable for direct burial, and is listed for Class 1 Division 2 hazardous locations. Suitable applications are power and control applications up to 600 V.

Who manufactures 28150A?

28150A is manufactured by Belden.

Where can I download the 28150A datasheet PDF?

The 28150A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 28150A specifications

AI Powered

Click to ask a quick question:

Parameters

Bend RadiusStationary Min. 2.38 in (60.5 mm); Installation Min. 2.975 in (75.57 mm)
Conductors3 x 8 AWG (7x16) bare copper + 1 x 10 AWG (7x18) bare copper ground wire
Max Current55 Amps per Conductor at 30ºC (conductors); 40 Amps per Conductor at 30ºC (ground wire)
Max Pull Tension772 lbs (350 kg)
Nominal Conductor DCR0.64 Ohm/1000ft (conductors); 1.08 Ohm/1000ft (ground wire)
Overall Cable Diameter0.595 in (15.1 mm)
Rated Voltage600 V
Temperature Rating90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C