1074A Datasheet

BeldenBulk Wire Cable

The Belden 1074A is a 24-pair instrumentation cable featuring 16 AWG bare copper conductors with PVC-nylon insulation, an overall Beldfoil shield, and a black PVC outer jacket. It is rated for 600V TC-ER and 150V NPLF, and supports operating temperatures from -30°C to 90°C in dry and wet environments. This cable is designed for industrial control, digital control, instruments, solenoids, valves, and distributed control systems.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

1074A Key Specifications

Max Current
6 Amps per conductor @ 30°C
Voltage Rating
600 V (TC-ER), 150 V (NPLF)
Temperature Range
-30°C to 90°C Dry/Wet (UL 90°C Dry, 90°C Wet)
Conductor
24 pairs, 16 AWG (7x24) Bare Copper
Max Pull Tension / Weight
1749 lbs (793.3 kg) / 743 lbs/1000ft
Nom. Conductor DCR
4.36 Ohm/1000ft
Nominal Overall Diameter
1.147 in (29.13 mm)
Nom Outer Shield DCR
2.69 Ohm/1000ft (8.83 Ohm/km)

Characteristics (datasheet)

Conductor
24 pairs, 16 AWG (7x24) Bare Copper
Voltage Rating
600 V (TC-ER), 150 V (NPLF)
Temperature Range
-30°C to 90°C Dry/Wet (UL 90°C Dry, 90°C Wet)
Max Current
6 Amps per conductor @ 30°C
Nom. Conductor DCR
4.36 Ohm/1000ft
Nom Outer Shield DCR
2.69 Ohm/1000ft (8.83 Ohm/km)
Nominal Overall Diameter
1.147 in (29.13 mm)
Max Pull Tension / Weight
1749 lbs (793.3 kg) / 743 lbs/1000ft

1074A Applications

  • Industrial control
  • Raceways, cable trays and ducts
  • Digital control
  • Instruments (4-20ma, 0-10v)
  • Low voltage digital control (24v)
  • Encoders
  • Control circuits
  • Distributed control system (DCS)
  • Programmable logic controller (PLC)
  • Solenoids
  • Valves
  • Actuators
  • Positioners

Other Belden parts

  • 37190 — Belden 37190 is a 1/0 AWG (262x24) tinned copper lead wire with EPDM insulation,...
  • 5476C — The Belden 5476C is a communication and control cable featuring 6 pairs of 24 AW...
  • 28088A — The Belden 28088A is a UL Type TC power and control cable with 10 conductors of...
  • 6328 — The Belden 6328 is a 4-conductor, 24 AWG tinned copper communication and control...
  • 65103 — The part 65103 is a 3-conductor, 10 AWG XTRAGUARD FLEX flexible control cable wi...
  • 77006 — The Belden 77006 is a multi-conductor cable featuring 19 conductors of 24 AWG st...
  • 25110 — Belden part 25110 is an XTRAGUARD 2 cable with 10 conductors of 22 AWG stranded...
  • 21648 — The Belden 21648 is a CSA Type TC-CIC tray cable containing 50 conductors of 10...

More Bulk Wire Cable

  • 78083 — The Belden 78083 is a 3-pair 22 AWG tinned copper ECOCABLE with modified polyphe...
  • 5583C — The Belden 5583C is a 15-conductor, 22 AWG tinned copper cable with semi-rigid P...
  • 2107A — The Belden 2107A is a 24-pair 18 AWG tinned copper fieldbus cable with XLPO insu...
  • 2201ELV — The 2201ELV is a discontinued Category 6A premise horizontal and building backbo...
  • 1045A — The Belden 1045A is a UL-listed multi-pair instrumentation cable featuring 24 pa...
  • 79218 — The Belden 79218 is a high-flexibility, shielded 2-conductor 16 AWG cable with m...
  • 88105 — The Belden 88105 is a plenum-rated, overall Beldfoil-shielded EIA RS-232/422 com...
  • 6416 — The Belden 6416 is a communication and control cable consisting of two pairs of...

1074A FAQ

What is 1074A?

1074A is a Bulk Wire Cable from Belden. The Belden 1074A is a 24-pair instrumentation cable featuring 16 AWG bare copper conductors with PVC-nylon insulation, an overall Beldfoil shield, and a black PVC outer jacket. It is rated for 600V TC-ER and 150V NPLF, and supports operating temperatures from -30°C to 90°C in dry and wet environments. This cable is designed for industrial control, digital control, instruments, solenoids, valves, and distributed control systems.

Who manufactures 1074A?

1074A is manufactured by Belden.

Where can I download the 1074A datasheet PDF?

The 1074A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 1074A specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor24 pairs, 16 AWG (7x24) Bare Copper
Max Current6 Amps per conductor @ 30°C
Max Pull Tension / Weight1749 lbs (793.3 kg) / 743 lbs/1000ft
Nom. Conductor DCR4.36 Ohm/1000ft
Nominal Overall Diameter1.147 in (29.13 mm)
Nom Outer Shield DCR2.69 Ohm/1000ft (8.83 Ohm/km)
Temperature Range-30°C to 90°C Dry/Wet (UL 90°C Dry, 90°C Wet)
Voltage Rating600 V (TC-ER), 150 V (NPLF)