9487 Datasheet
The Belden 9487 is a high-performance instrumentation cable consisting of a single pair of 16 AWG tinned copper conductors insulated with PVC-nylon and jacketed in black PVC. It is rated for a voltage of 600V TC and is designed for use in industrial control, digital control, instrumentation, and actuator applications. The cable features a nominal overall diameter of 0.295 inches, a maximum current capacity of 6.2 Amps per conductor at 25°C, and supports an operating temperature range of -30°C to +90°C dry and 75°C wet.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
9487 Key Specifications
- Max Current
- 6.2 Amps per conductor at 25°C
- Voltage Rating
- 600 V (TC), 150 V (NPLF)
- Operating Temperature
- -30°C to +90°C Dry, 75°C wet
- Bulk Cable Weight
- 51 lbs/1000ft
- Conductor
- 1 Pair 16 AWG (19x29) Tinned Copper (TC)
- Insulation
- PVC/Nylon, nominal thickness 0.022 in (0.56 mm), color code Black, Red
- Nom. Conductor DCR
- 4.45 Ohm/1000ft
- Outer Jacket
- Black PVC, nominal thickness 0.048 in (1.2 mm), nominal diameter 0.295 in (7.49 mm)
Characteristics (datasheet)
- Conductor
- 1 Pair 16 AWG (19x29) Tinned Copper (TC)
- Insulation
- PVC/Nylon, nominal thickness 0.022 in (0.56 mm), color code Black, Red
- Outer Jacket
- Black PVC, nominal thickness 0.048 in (1.2 mm), nominal diameter 0.295 in (7.49 mm)
- Voltage Rating
- 600 V (TC), 150 V (NPLF)
- Max Current
- 6.2 Amps per conductor at 25°C
- Nom. Conductor DCR
- 4.45 Ohm/1000ft
- Operating Temperature
- -30°C to +90°C Dry, 75°C wet
- Bulk Cable Weight
- 51 lbs/1000ft
9487 Applications
- Industrial Control
- Raceways Cable trays and ducts
- Digital Control
- Instruments (4-20ma, 0-10v, ...)
- low voltage digital control (24v, ...)
- encoders
- control circuits
- distributed control system (DCS)
- programmable logic controller (PLC)
- Solenoids
- Valves
- Actuators
- Positioners
Other Belden parts
- 9165 — The Belden 9165 is a composite cable designed for ENG, EFP, and CCTV application...
- 8219 — The Belden 8219 is an RG-58 type 50 Ohm wireless transmission coaxial cable feat...
- 37114 — Belden 37114 is a 14 AWG (41x30) stranded tinned copper lead wire with EPDM insu...
- 1260 — The Belden 1260 is a 600V RW90 power and control cable featuring 12 AWG bare cop...
- 1063A — The Belden 1063A is a UL-listed instrumentation cable consisting of two 18 AWG b...
- 70082 — The Belden 70082 is a discontinued 75 Ohm SDI coaxial cable built with an RG-6 t...
- 78316 — The Belden 78316 is a 6-conductor, 26 AWG tinned copper cable with modified poly...
- 21588 — Belden 21588 is a Canadian Instrumentation Cable (TC-CIC) rated 600 V with 40 pl...
More Bulk Wire Cable
- 3018A — The Belden 3018A is a UL-listed instrumentation cable containing two triads of 2...
- 77804W — The Belden 77804W is a high-flexibility bulk cable featuring four 18 AWG bare co...
- 28605A — The Belden 28605A is a UL Type TC (1277) power and control cable with 15 bare co...
- 85612 — The Belden 85612 is an XTRAGUARD FLEX continuous flex control cable featuring 12...
- 6311 — The Belden 6311 is a 40-conductor, 24 AWG tinned copper communication and contro...
- 80020 — The Belden 80020 is a zero-halogen, flexible 2-conductor 20 AWG tinned copper co...
- 8261 — The Belden 8261 is an RG11 analog video coaxial cable designed for SDI coax appl...
- 31514 — The Belden 31514 is a low-temperature rubber lead wire constructed with 14 AWG (...
9487 FAQ
What is 9487?
9487 is a Bulk Wire Cable from Belden. The Belden 9487 is a high-performance instrumentation cable consisting of a single pair of 16 AWG tinned copper conductors insulated with PVC-nylon and jacketed in black PVC. It is rated for a voltage of 600V TC and is designed for use in industrial control, digital control, instrumentation, and actuator applications. The cable features a nominal overall diameter of 0.295 inches, a maximum current capacity of 6.2 Amps per conductor at 25°C, and supports an operating temperature range of -30°C to +90°C dry and 75°C wet.
Who manufactures 9487?
9487 is manufactured by Belden.
Where can I download the 9487 datasheet PDF?
The 9487 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 9487 specifications
Click to ask a quick question:
Parameters
| Bulk Cable Weight | 51 lbs/1000ft |
| Conductor | 1 Pair 16 AWG (19x29) Tinned Copper (TC) |
| Insulation | PVC/Nylon, nominal thickness 0.022 in (0.56 mm), color code Black, Red |
| Max Current | 6.2 Amps per conductor at 25°C |
| Nom. Conductor DCR | 4.45 Ohm/1000ft |
| Operating Temperature | -30°C to +90°C Dry, 75°C wet |
| Outer Jacket | Black PVC, nominal thickness 0.048 in (1.2 mm), nominal diameter 0.295 in (7.49 mm) |
| Voltage Rating | 600 V (TC), 150 V (NPLF) |