The Belden 9365 is a high-performance instrumentation cable featuring one 18 AWG triad tinned copper conductor with PVC insulation, an overall Beldfoil shield, and a PVC outer jacket. It is rated for 300 V (PLTC, CMG) and supports operating temperatures from -30°C to +105°C. This cable is designed for use in instrumentation, sensors, valves, positioners, RTDs, and signal transmission applications such as 4-20mA and 0-10V.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
9365 Key Specifications
- Max. Current
- 5 Amps per Conductor at 25ºC
- Nom. Capacitance Cond-to-Cond
- 54 pF/ft (180 pF/m)
- Nom. Capacitance Cond-to-Shield
- 101 pF/ft (331 pF/m)
- Nom. Inductance
- 0.17 µH/ft (0.56 µH/m)
- UL Voltage Rating
- 300 V (PLTC, CMG)
- Operating Temperature
- -30°C to +105°C
- UL Temperature
- 105°C
- Conductor
- 1 Triad 18 AWG (19x30) TC - Tinned Copper
Characteristics (datasheet)
- Conductor
- 1 Triad 18 AWG (19x30) TC - Tinned Copper
- Nom. Outer Diameter
- 0.269 in (6.83 mm)
- Nom. Conductor DCR
- 7.2 Ohm/1000ft
- Nom. Capacitance Cond-to-Cond
- 54 pF/ft (180 pF/m)
- Nom. Capacitance Cond-to-Shield
- 101 pF/ft (331 pF/m)
- Nom. Characteristic Impedance
- 45 Ohm
- Nom. Inductance
- 0.17 µH/ft (0.56 µH/m)
- Max. Current
- 5 Amps per Conductor at 25ºC
Absolute Maximum Ratings
- UL Voltage Rating
- 300 V (PLTC, CMG)
- UL Temperature
- 105°C
- Operating Temperature
- -30°C to +105°C
- Max. Pull Tension
- 89 lbs (40 kg)
- Min. Bend Radius (Stationary / Installation)
- 2.7 in (69 mm)
9365 Applications
- Instrumentation
- Sensors
- Valves
- Positioners
Other Belden parts
- 7036 — The Belden 7036 is a single-conductor, 12 AWG tinned copper hook-up wire with ir...
- 1715 — The Belden 1715 is a multi-conductor communication and control cable featuring f...
- 5685 — The Belden 5685 is a XTRAGUARD 1 shielded multi-conductor cable featuring 6 cond...
- 8427 — The Belden 8427 is a flexible, ruggedized 7-conductor 20 AWG tinned copper micro...
- 1411R — The Belden 1411R is an audio snake cable containing 12 pairs of 24 AWG tinned co...
- 35493 — Belden 35493 is an XTRAGUARD 3 cable with 3 pairs of 24 AWG stranded tinned copp...
- 85012 — The Belden 85012 is a 12-conductor, 20 AWG bare copper XTRAGUARD FLEX continuous...
- 23530D — The Belden 23530D is a Canadian Instrumentation Cable (TC-ACIC) rated 300 V, bui...
More Bulk Wire Cable
- 77201 — The Belden 77201 is a 4-conductor, 24 AWG tinned copper ECOCABLE with mPPE insul...
- 1175A — The Belden 1175A is a shielded, single-pair cable designed for T1/DS1 central of...
- 83265 — The Belden 83265 is a commercial, non-QPL mil-spec coaxial cable with a 50 Ohm c...
- 89901 — The Belden 89901 is an IEEE 802.3 Ethernet transceiver cable designed for 10BASE...
- 1349A — The Belden 1349A is a 5-conductor CC Link cable featuring bare copper conductors...
- 2219C — The Belden 2219C is a communication and control cable consisting of 9 pairs of 2...
- 1327A — The 1327A is a 2-pair 18AWG tinned copper fieldbus cable with polypropylene insu...
- 6194 — The Belden 6194 is a heavy-duty Teck90 600V cable designed with a 3+4+G bare cop...
9365 FAQ
What is 9365?
9365 is a Bulk Wire Cable from Belden. The Belden 9365 is a high-performance instrumentation cable featuring one 18 AWG triad tinned copper conductor with PVC insulation, an overall Beldfoil shield, and a PVC outer jacket. It is rated for 300 V (PLTC, CMG) and supports operating temperatures from -30°C to +105°C. This cable is designed for use in instrumentation, sensors, valves, positioners, RTDs, and signal transmission applications such as 4-20mA and 0-10V.
Who manufactures 9365?
9365 is manufactured by Belden.
Where can I download the 9365 datasheet PDF?
The 9365 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 9365 specifications
Click to ask a quick question:
Parameters
| Conductor | 1 Triad 18 AWG (19x30) TC - Tinned Copper |
| Max. Current | 5 Amps per Conductor at 25ºC |
| Max. Pull Tension | 89 lbs (40 kg) |
| Min. Bend Radius (Stationary / Installation) | 2.7 in (69 mm) |
| Nom. Capacitance Cond-to-Cond | 54 pF/ft (180 pF/m) |
| Nom. Capacitance Cond-to-Shield | 101 pF/ft (331 pF/m) |
| Nom. Characteristic Impedance | 45 Ohm |
| Nom. Conductor DCR | 7.2 Ohm/1000ft |
| Nom. Inductance | 0.17 µH/ft (0.56 µH/m) |
| Nom. Outer Diameter | 0.269 in (6.83 mm) |
| Operating Temperature | -30°C to +105°C |
| UL Temperature | 105°C |
| UL Voltage Rating | 300 V (PLTC, CMG) |