1327A Datasheet
The 1327A is a 2-pair 18AWG tinned copper fieldbus cable with polypropylene insulation, individual and overall Beldfoil shielding, and a PVC outer jacket. It is designed for harsh environment digital and serial two-way communication, particularly in oil and gas extraction, petrochemical, and Profibus or Foundation FieldBus process automation sites. The cable has a characteristic impedance of 100 Ohm, a voltage rating of 300 V RMS, and supports an operating temperature range of -40°C to +105°C.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
1327A Key Specifications
- Max. Capacitance Unbalance
- 1.2 pF/ft
- Max. Current
- 5.2 Amps per conductor
- Nom. Capacitance Cond-to-Shield
- 45 pF/ft (150 pF/m)
- Nom. Inductance
- 0.19 µH/ft (0.62 µH/m)
- UL Voltage Rating
- 300 V RMS
- Operating temperature
- -40°C to +105°C
- UL Temperature
- 105°C
- Bulk Cable Weight
- 90 lbs/1000ft
Characteristics (datasheet)
- Conductor
- 2 pair 18 AWG (7x26) tinned copper
- Characteristic impedance
- 100 Ohm
- Nom. Capacitance Cond-to-Shield
- 45 pF/ft (150 pF/m)
- Max. Capacitance Unbalance
- 1.2 pF/ft
- Nom. Inductance
- 0.19 µH/ft (0.62 µH/m)
- Nom. Velocity of Prop.
- 66%
- Max. Current
- 5.2 Amps per conductor
- UL Voltage Rating
- 300 V RMS
- Operating temperature
- -40°C to +105°C
- UL Temperature
- 105°C
- Outer Jacket
- PVC, nominal thickness 0.053 in (1.3 mm), nominal diameter 0.44 in (11 mm)
- Bulk Cable Weight
- 90 lbs/1000ft
- Max. Pull Tension
- 89.6 lbs (40.6 kg)
1327A Applications
- harsh environment digital and serial two-way communication
- oil and gas extraction and refining sites
- petrochemical, Profibus process automation or Foundation FieldBus process automation
- extreme temperature environments
- exposure to humidity/moisture, dust, and oil
- remote locations long distance applications
Other Belden parts
- 77052 — The Belden 77052 is a 2-conductor 28 AWG stranded tinned copper ECOCABLE featuri...
- 83269 — The Belden 83269 is a commercial, non-QPL mil-spec coaxial cable with a 50 Ohm c...
- 5074C — The Belden 5074C is a 4-conductor, 16 AWG tinned copper control cable with PVC i...
- 9411 — The Belden 9411 is a high-performance instrumentation cable featuring a single p...
- 391280025000 — 28AWG Hook-Up Wire, 600V, 5000ft, Copper Conductor, PPO Insulation
- 29547 — Belden 29547 is a flexible VFD motor supply cable with three 4/0 AWG tinned copp...
- 9180 — The Belden 9180 is a 110 Ohm, 26 AWG stranded tinned copper audio cable with foa...
- 80004 — The Belden 80004 (ECOFLEX PUR) is a 3-conductor, 26 AWG tinned copper cable with...
More Bulk Wire Cable
- 47636AS — Belden 47636AS is a UL-listed instrumentation cable with one pair (two conductor...
- 2616 — The Belden 2616 is a single-conductor hook-up wire featuring a 16 AWG nickel-pla...
- 7810A — The Belden 7810A is a 50 Ohm wireless transmission coaxial cable (RG-8, 10 AWG)...
- 65009 — The 65009 is a 9-conductor, 20 AWG bare copper control cable with PVC insulation...
- 8467 — The Belden 8467 is a 7-conductor electronic cable made of 18 AWG (19x30) tinned...
- 50001L — The Belden 50001L is an RS-485 fire resistant cable with one pair of 22 AWG stra...
- 1370P — The Belden 1370P is a serial digital coaxial cable of RG-59 type designed for co...
- 9681 — The Belden 9681 is a computer EIA RS-232/422 low-capacitance cable featuring fou...
1327A FAQ
What is 1327A?
1327A is a Bulk Wire Cable from Belden. The 1327A is a 2-pair 18AWG tinned copper fieldbus cable with polypropylene insulation, individual and overall Beldfoil shielding, and a PVC outer jacket. It is designed for harsh environment digital and serial two-way communication, particularly in oil and gas extraction, petrochemical, and Profibus or Foundation FieldBus process automation sites. The cable has a characteristic impedance of 100 Ohm, a voltage rating of 300 V RMS, and supports an operating temperature range of -40°C to +105°C.
Who manufactures 1327A?
1327A is manufactured by Belden.
Where can I download the 1327A datasheet PDF?
The 1327A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 1327A specifications
Click to ask a quick question:
Parameters
| Bulk Cable Weight | 90 lbs/1000ft |
| Characteristic impedance | 100 Ohm |
| Conductor | 2 pair 18 AWG (7x26) tinned copper |
| Max. Capacitance Unbalance | 1.2 pF/ft |
| Max. Current | 5.2 Amps per conductor |
| Max. Pull Tension | 89.6 lbs (40.6 kg) |
| Nom. Capacitance Cond-to-Shield | 45 pF/ft (150 pF/m) |
| Nom. Inductance | 0.19 µH/ft (0.62 µH/m) |
| Nom. Velocity of Prop. | 66% |
| Operating temperature | -40°C to +105°C |
| Outer Jacket | PVC, nominal thickness 0.053 in (1.3 mm), nominal diameter 0.44 in (11 mm) |
| UL Temperature | 105°C |
| UL Voltage Rating | 300 V RMS |