9341 Datasheet

BeldenBulk Wire Cable

The Belden 9341 is a high-performance instrumentation cable featuring a single pair of 18 AWG (19x30) tinned copper conductors with PVC-Nylon insulation and a black PVC outer jacket. It provides 100% overall Bi-Laminate (Alum+Poly) shielding and is rated for 600V (TC) and 150V (NPLF). Designed for industrial environments, it supports a temperature range of -30°C to +90°C and is suitable for use in control systems, PLCs, solenoids, and low-voltage digital circuits.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

9341 Key Specifications

Max Current
5 Amps per Conductor at 25ºC
Nom. Capacitance Cond-to-Cond
43 pF/ft (140 pF/m)
Nom. Capacitance Cond-to-Other
74 pF/ft (240 pF/m)
Nom. Inductance
0.19 µH/ft (0.62 µH/m)
UL Voltage Rating
600 V (TC), 150 V (NPLF)
Operating Temperature
-30°C to +90°C Dry, 75°C wet
Bend Radius (Min. Stationary / Installation)
2.7 in (69 mm)
Bulk Cable Weight
40 lbs/1000ft

Characteristics (datasheet)

Conductor
1 Pair, 18 AWG 19x30 Stranding, TC - Tinned Copper
Insulation
PVC/Nylon - Polyvinyl Chloride + Nylon, Nom. Thickness 0.022 in (0.56 mm), Nom. Diameter 0.088 in (2.2 mm), ICEA Chart E2
Outer Shield
Tape, Bi-Laminate (Alum+Poly), 100% Coverage, Drainwire 18 AWG (19x30) TC
Outer Jacket
PVC - Polyvinyl Chloride, Nom. Thickness 0.047 in (1.2 mm), Nom. Diameter 0.274 in (6.96 mm), Ripcord Yes
Overall Cable Diameter (Nominal)
0.274 in (6.96 mm)
UL Voltage Rating
600 V (TC), 150 V (NPLF)
Operating Temperature
-30°C to +90°C Dry, 75°C wet
Max Current
5 Amps per Conductor at 25ºC
Nom. Conductor DCR
7.06 Ohm/1000ft
Nom Outer Shield DCR
5.14 Ohm/1000ft (16.9 Ohm/km)
Nom. Capacitance Cond-to-Cond
43 pF/ft (140 pF/m)
Nom. Capacitance Cond-to-Other
74 pF/ft (240 pF/m)
Nom. Inductance
0.19 µH/ft (0.62 µH/m)
Bend Radius (Min. Stationary / Installation)
2.7 in (69 mm)
Max. Pull Tension
74.1 lbs (33.6 kg)
Bulk Cable Weight
40 lbs/1000ft

9341 Applications

  • Industrial Control
  • Raceways, Cable trays and ducts
  • Digital Control
  • Instruments (4-20ma, 0-10v, ...)
  • Low voltage digital control (24v, …)
  • Encoders
  • Control circuits
  • Distributed control system (DCS)
  • Programmable logic controller (PLC)
  • Solenoids, Valves, Actuators, Positioners

Other Belden parts

  • 85207CY — The 85207CY is a 7-conductor, 12 AWG XTRAGUARD FLEX continuous flex control cabl...
  • 28157A — Belden 28157A is a UL Type TC power and control cable with four 4 AWG bare coppe...
  • 85404 — The Belden 85404 is a highly flexible, 4-conductor 14 AWG control cable with bar...
  • 7953A — The Belden 7953A is an Industrial Ethernet Category 6 cable constructed with fou...
  • 8315 — The Belden 8315 is a computer EIA RS-232 cable designed for extended distance ap...
  • 45054 — Belden part 45054 is an XTRAGUARD 4 cable containing 4 conductors of 20 AWG (7/2...
  • 45178 — Belden part 45178 is an XTRAGUARD 4 cable with eight 16 AWG stranded tinned copp...
  • 5946 — The Belden 5946 is an XTRAGUARD 1 shielded cable consisting of 5 pairs of 28 AWG...

More Bulk Wire Cable

  • 79228 — The Belden / Alpha Wire 79228 is a 5-conductor, 14 AWG stranded tinned copper ca...
  • 65802 — The Belden 65802 is an XTRAGUARD FLEX flexible control cable featuring two 18 AW...
  • 1023A — The Belden 1023A is a single-pair TX thermocouple cable featuring 16 AWG solid c...
  • 5586C — The Belden 5586C is a 37-conductor, 22 AWG tinned copper cable with semi-rigid P...
  • 77252 — The Belden 77252 is a 2-conductor 28 AWG tinned copper ECOCABLE featuring MPPE i...
  • 9843 — The Belden 9843 is an RS-485 communication cable featuring three 24 AWG tinned c...
  • 5508FE — The 5508FE is a security and sound cable with a riser-CMR rating, suitable for s...
  • 8618 — The Belden 8618 is a 3-conductor, 16 AWG tinned copper electronic cable featurin...

9341 FAQ

What is 9341?

9341 is a Bulk Wire Cable from Belden. The Belden 9341 is a high-performance instrumentation cable featuring a single pair of 18 AWG (19x30) tinned copper conductors with PVC-Nylon insulation and a black PVC outer jacket. It provides 100% overall Bi-Laminate (Alum+Poly) shielding and is rated for 600V (TC) and 150V (NPLF). Designed for industrial environments, it supports a temperature range of -30°C to +90°C and is suitable for use in control systems, PLCs, solenoids, and low-voltage digital circuits.

Who manufactures 9341?

9341 is manufactured by Belden.

Where can I download the 9341 datasheet PDF?

The 9341 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 9341 specifications

AI Powered

Click to ask a quick question:

Parameters

Bend Radius (Min. Stationary / Installation)2.7 in (69 mm)
Bulk Cable Weight40 lbs/1000ft
Conductor1 Pair, 18 AWG 19x30 Stranding, TC - Tinned Copper
InsulationPVC/Nylon - Polyvinyl Chloride + Nylon, Nom. Thickness 0.022 in (0.56 mm), Nom. Diameter 0.088 in (2.2 mm), ICEA Chart E2
Max Current5 Amps per Conductor at 25ºC
Max. Pull Tension74.1 lbs (33.6 kg)
Nom. Capacitance Cond-to-Cond43 pF/ft (140 pF/m)
Nom. Capacitance Cond-to-Other74 pF/ft (240 pF/m)
Nom. Conductor DCR7.06 Ohm/1000ft
Nom. Inductance0.19 µH/ft (0.62 µH/m)
Nom Outer Shield DCR5.14 Ohm/1000ft (16.9 Ohm/km)
Operating Temperature-30°C to +90°C Dry, 75°C wet
Outer JacketPVC - Polyvinyl Chloride, Nom. Thickness 0.047 in (1.2 mm), Nom. Diameter 0.274 in (6.96 mm), Ripcord Yes
Outer ShieldTape, Bi-Laminate (Alum+Poly), 100% Coverage, Drainwire 18 AWG (19x30) TC
Overall Cable Diameter (Nominal)0.274 in (6.96 mm)
UL Voltage Rating600 V (TC), 150 V (NPLF)