28157A Datasheet
Belden 28157A is a UL Type TC power and control cable with four 4 AWG bare copper conductors plus one 8 AWG bare copper ground wire, insulated with PVC/nylon and jacketed in black PVC. It is rated 600 V, 90°C dry and wet, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial installations including Class 1 Division 2 hazardous locations.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28157A Key Specifications
- Max Current
- 76 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 30ºC (ground)
- UL Voltage Rating
- 600 V
- Temperature Rating
- 90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
- Bend Radius
- Stationary Min. 3.82 in (97.0 mm); Installation Min. 4.775 in (121.3 mm)
- Conductor DCR
- 0.26 Ohm/1000ft
- Conductors
- 4 AWG 7x12 BC - Bare Copper (4 elements)
- Ground Wire
- 8 AWG 7x16 BC - Bare Copper (1 element)
- Insulation
- PVC/Nylon - Polyvinyl Chloride + Nylon, 0.046 in (1.2 mm) nominal thickness
Characteristics (datasheet)
- UL Voltage Rating
- 600 V
- Conductors
- 4 AWG 7x12 BC - Bare Copper (4 elements)
- Ground Wire
- 8 AWG 7x16 BC - Bare Copper (1 element)
- Insulation
- PVC/Nylon - Polyvinyl Chloride + Nylon, 0.046 in (1.2 mm) nominal thickness
- Outer Jacket
- PVC - Polyvinyl Chloride, 0.083 in (2.1 mm) nominal thickness, ripcord
- Overall Cable Diameter
- 0.955 in (24.3 mm) nominal
- Conductor DCR
- 0.26 Ohm/1000ft
- Max Current
- 76 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 30ºC (ground)
- Temperature Rating
- 90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
- Max Pull Tension
- 2430.4 lbs (1102.4 kg)
- Bend Radius
- Stationary Min. 3.82 in (97.0 mm); Installation Min. 4.775 in (121.3 mm)
28157A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 9812 — The Belden 9812 is a computer EIA RS-232/422 low-capacitance cable with 12 pairs...
- 82641 — The Belden 82641 is a plenum-rated, 1-pair RS-232 cable designed for computer co...
- 6012C — The Belden 6012C is a shielded multi-conductor communication and control cable c...
- 1385 — The Belden 1385 is a heavy-duty, 1000V rated power and control cable featuring 6...
- 58126 — The Belden 58126 is a plenum-rated, shielded multi-conductor communication and c...
- 934087188 — HIRSCHMANN TEST AND MEASUREMENT 934087188 TEST LEAD, GRN, YELLOW, 500MM, 1KV...
- 45464 — Belden 45464 is a 4-conductor, 20 AWG (7/28) tinned copper cable with TPE insula...
- 3410 — The Belden 3410 is a 10-conductor, 18 AWG tinned copper control cable with PVC i...
More Bulk Wire Cable
- 29544 — Belden 29544 is a flexible 2000 V VFD motor supply cable with three 1/0 AWG tinn...
- 7950A — The 7950A is a Siamese composite cable consisting of one Cat 5 4-pair, 24 AWG un...
- 65812 — The Belden 65812 is a flexible 12-conductor control cable featuring 18 AWG bare...
- 65605 — The Belden 65605 is a flexible 5-conductor control cable made of 16 AWG stranded...
- 4731P — The Belden 4731P is a high-performance 12 GHz, 4K UHD precision video coaxial ca...
- 4281MDW — The Belden 4281MDW is an OSDP reader cable designed for access control, OSDP rea...
- 5474C — The Belden 5474C is a shielded, 4-pair 24 AWG tinned copper communication and co...
- 78205 — The Belden 78205 is an ECOCABLE consisting of 5 pairs of 28 AWG stranded tinned...
28157A FAQ
What is 28157A?
28157A is a Bulk Wire Cable from Belden. Belden 28157A is a UL Type TC power and control cable with four 4 AWG bare copper conductors plus one 8 AWG bare copper ground wire, insulated with PVC/nylon and jacketed in black PVC. It is rated 600 V, 90°C dry and wet, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial installations including Class 1 Division 2 hazardous locations.
Who manufactures 28157A?
28157A is manufactured by Belden.
Where can I download the 28157A datasheet PDF?
The 28157A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28157A specifications
Click to ask a quick question:
Parameters
| Bend Radius | Stationary Min. 3.82 in (97.0 mm); Installation Min. 4.775 in (121.3 mm) |
| Conductor DCR | 0.26 Ohm/1000ft |
| Conductors | 4 AWG 7x12 BC - Bare Copper (4 elements) |
| Ground Wire | 8 AWG 7x16 BC - Bare Copper (1 element) |
| Insulation | PVC/Nylon - Polyvinyl Chloride + Nylon, 0.046 in (1.2 mm) nominal thickness |
| Max Current | 76 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 30ºC (ground) |
| Max Pull Tension | 2430.4 lbs (1102.4 kg) |
| Outer Jacket | PVC - Polyvinyl Chloride, 0.083 in (2.1 mm) nominal thickness, ripcord |
| Overall Cable Diameter | 0.955 in (24.3 mm) nominal |
| Temperature Rating | 90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C |
| UL Voltage Rating | 600 V |