Belden 28157A is a UL Type TC power and control cable with four 4 AWG bare copper conductors plus one 8 AWG bare copper ground wire, insulated with PVC/nylon and jacketed in black PVC. It is rated 600 V, 90°C dry and wet, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial installations including Class 1 Division 2 hazardous locations.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

28157A Key Specifications

Max Current
76 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 30ºC (ground)
UL Voltage Rating
600 V
Temperature Rating
90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
Bend Radius
Stationary Min. 3.82 in (97.0 mm); Installation Min. 4.775 in (121.3 mm)
Conductor DCR
0.26 Ohm/1000ft
Conductors
4 AWG 7x12 BC - Bare Copper (4 elements)
Ground Wire
8 AWG 7x16 BC - Bare Copper (1 element)
Insulation
PVC/Nylon - Polyvinyl Chloride + Nylon, 0.046 in (1.2 mm) nominal thickness

Characteristics (datasheet)

UL Voltage Rating
600 V
Conductors
4 AWG 7x12 BC - Bare Copper (4 elements)
Ground Wire
8 AWG 7x16 BC - Bare Copper (1 element)
Insulation
PVC/Nylon - Polyvinyl Chloride + Nylon, 0.046 in (1.2 mm) nominal thickness
Outer Jacket
PVC - Polyvinyl Chloride, 0.083 in (2.1 mm) nominal thickness, ripcord
Overall Cable Diameter
0.955 in (24.3 mm) nominal
Conductor DCR
0.26 Ohm/1000ft
Max Current
76 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 30ºC (ground)
Temperature Rating
90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
Max Pull Tension
2430.4 lbs (1102.4 kg)
Bend Radius
Stationary Min. 3.82 in (97.0 mm); Installation Min. 4.775 in (121.3 mm)

28157A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 9812 — The Belden 9812 is a computer EIA RS-232/422 low-capacitance cable with 12 pairs...
  • 82641 — The Belden 82641 is a plenum-rated, 1-pair RS-232 cable designed for computer co...
  • 6012C — The Belden 6012C is a shielded multi-conductor communication and control cable c...
  • 1385 — The Belden 1385 is a heavy-duty, 1000V rated power and control cable featuring 6...
  • 58126 — The Belden 58126 is a plenum-rated, shielded multi-conductor communication and c...
  • 934087188 — HIRSCHMANN TEST AND MEASUREMENT 934087188 TEST LEAD, GRN, YELLOW, 500MM, 1KV...
  • 45464 — Belden 45464 is a 4-conductor, 20 AWG (7/28) tinned copper cable with TPE insula...
  • 3410 — The Belden 3410 is a 10-conductor, 18 AWG tinned copper control cable with PVC i...

More Bulk Wire Cable

  • 29544 — Belden 29544 is a flexible 2000 V VFD motor supply cable with three 1/0 AWG tinn...
  • 7950A — The 7950A is a Siamese composite cable consisting of one Cat 5 4-pair, 24 AWG un...
  • 65812 — The Belden 65812 is a flexible 12-conductor control cable featuring 18 AWG bare...
  • 65605 — The Belden 65605 is a flexible 5-conductor control cable made of 16 AWG stranded...
  • 4731P — The Belden 4731P is a high-performance 12 GHz, 4K UHD precision video coaxial ca...
  • 4281MDW — The Belden 4281MDW is an OSDP reader cable designed for access control, OSDP rea...
  • 5474C — The Belden 5474C is a shielded, 4-pair 24 AWG tinned copper communication and co...
  • 78205 — The Belden 78205 is an ECOCABLE consisting of 5 pairs of 28 AWG stranded tinned...

28157A FAQ

What is 28157A?

28157A is a Bulk Wire Cable from Belden. Belden 28157A is a UL Type TC power and control cable with four 4 AWG bare copper conductors plus one 8 AWG bare copper ground wire, insulated with PVC/nylon and jacketed in black PVC. It is rated 600 V, 90°C dry and wet, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial installations including Class 1 Division 2 hazardous locations.

Who manufactures 28157A?

28157A is manufactured by Belden.

Where can I download the 28157A datasheet PDF?

The 28157A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 28157A specifications

AI Powered

Click to ask a quick question:

Parameters

Bend RadiusStationary Min. 3.82 in (97.0 mm); Installation Min. 4.775 in (121.3 mm)
Conductor DCR0.26 Ohm/1000ft
Conductors4 AWG 7x12 BC - Bare Copper (4 elements)
Ground Wire8 AWG 7x16 BC - Bare Copper (1 element)
InsulationPVC/Nylon - Polyvinyl Chloride + Nylon, 0.046 in (1.2 mm) nominal thickness
Max Current76 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 30ºC (ground)
Max Pull Tension2430.4 lbs (1102.4 kg)
Outer JacketPVC - Polyvinyl Chloride, 0.083 in (2.1 mm) nominal thickness, ripcord
Overall Cable Diameter0.955 in (24.3 mm) nominal
Temperature Rating90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
UL Voltage Rating600 V