7896A Datasheet

BeldenBulk Wire Cable

The Belden 7896A is a DeviceBus® communication cable designed for ODVA DeviceNet™ systems in harsh industrial environments. It features a two-pair design with 16 AWG power and 18 AWG data tinned copper conductors, individually shielded with Beldfoil® and overall 70% tinned copper braid shielding. This 600V TC-ER cable is built for control, configuration, and data collection between sensors, actuators, and higher-level devices like PLCs and PCs in industrial automation bus topologies.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

7896A Key Specifications

Max Current
8 Amps per Conductor at 25°C (Power pair)
Voltage Rating
600 V (TC-ER)
Operating Temperature
-40°C to +75°C
Characteristic Impedance
120 Ohm (Data pair)
Conductors
1 Power Pair 16 AWG (19x29) TC, 1 Data Pair 18 AWG (19x30) TC
Max Pull Tension
190 lbs (86 kg)
Nominal Outer Diameter
0.525 in (13.3 mm)
Outer Shield
Tinned copper braid with 70% coverage, 16 AWG drain wire

Characteristics (datasheet)

Voltage Rating
600 V (TC-ER)
Conductors
1 Power Pair 16 AWG (19x29) TC, 1 Data Pair 18 AWG (19x30) TC
Max Current
8 Amps per Conductor at 25°C (Power pair)
Characteristic Impedance
120 Ohm (Data pair)
Operating Temperature
-40°C to +75°C
Outer Shield
Tinned copper braid with 70% coverage, 16 AWG drain wire
Nominal Outer Diameter
0.525 in (13.3 mm)
Max Pull Tension
190 lbs (86 kg)

7896A Applications

  • ODVA device-level communication in harsh environments
  • Control, configuration, and data collection between sensors and actuators
  • Industrial automation communication with higher-level devices like PLCs and PCs

Other Belden parts

  • 7126W — The 7126W is a MachFlex™ high-flex cable designed with eight 16 AWG bare copper...
  • 7916AP 8771000 — COAX 75 OHM RG6 18AWG PLENUM
  • 5299C — The Belden 5299C is an XTRAGUARD 1 shielded cable consisting of 9 pairs of 20 AW...
  • 79258 — The 79258 is a 4-conductor, 26 AWG stranded tinned copper cable with mPPE insula...
  • 2628 — The Belden 2628 is a single-conductor hook-up wire featuring a 28 AWG nickel-pla...
  • 8730 — The Belden 8730 is a shielded audio, control, and instrumentation cable consisti...
  • 3027A — The 3027A is a UL-listed instrumentation cable featuring two 18 AWG triad bare c...
  • 25129 — Belden part 25129 is an XTRAGUARD 2 cable with nine 22 AWG (7/30) tinned copper...

More Bulk Wire Cable

  • 1319C — The Belden 1319C is a multi-conductor communication and control cable consisting...
  • 8355 — The Belden 8355 is a 25-pair computer EIA RS-232 cable featuring 24 AWG stranded...
  • 79216 — The Belden 79216 is a 12-conductor ECOFLEX cable with 18 AWG (19/30) stranded ti...
  • 28339A — The Belden 28339A is a 5-conductor, 16 AWG (7x24) bare copper power and control...
  • 70259PU — The 70259PU is a flexible, flame-retardant, and halogen-free PUR sensor and actu...
  • 45272 — Belden part 45272 is an XTRAGUARD 4 cable with two 24 AWG (7x32) stranded tinned...
  • 5691 — The Belden 5691 is a shielded, 3-pair 26 AWG tinned copper cable with semi-rigid...
  • 1716 — The Belden 1716 is a 5-conductor, 20 AWG tinned copper communication and control...

7896A FAQ

What is 7896A?

7896A is a Bulk Wire Cable from Belden. The Belden 7896A is a DeviceBus® communication cable designed for ODVA DeviceNet™ systems in harsh industrial environments. It features a two-pair design with 16 AWG power and 18 AWG data tinned copper conductors, individually shielded with Beldfoil® and overall 70% tinned copper braid shielding. This 600V TC-ER cable is built for control, configuration, and data collection between sensors, actuators, and higher-level devices like PLCs and PCs in industrial automation bus topologies.

Who manufactures 7896A?

7896A is manufactured by Belden.

Where can I download the 7896A datasheet PDF?

The 7896A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 7896A specifications

AI Powered

Click to ask a quick question:

Parameters

Characteristic Impedance120 Ohm (Data pair)
Conductors1 Power Pair 16 AWG (19x29) TC, 1 Data Pair 18 AWG (19x30) TC
Max Current8 Amps per Conductor at 25°C (Power pair)
Max Pull Tension190 lbs (86 kg)
Nominal Outer Diameter0.525 in (13.3 mm)
Operating Temperature-40°C to +75°C
Outer ShieldTinned copper braid with 70% coverage, 16 AWG drain wire
Voltage Rating600 V (TC-ER)