28339A Datasheet
The Belden 28339A is a 5-conductor, 16 AWG (7x24) bare copper power and control cable with PVC/nylon insulation (E2 color code: black, red, blue, orange, yellow) and a black PVC outer jacket with a ripcord. It is rated 600 V (TC-ER) and 150 V (NPLF) and is suitable for power and control applications up to 600 V, including Class 1 Division 2 hazardous locations. The unshielded cable is rated 90 °C dry/wet with an operating range of -30 °C to 90 °C wet/dry and is suitable for indoor, outdoor, sunlight-resistant, and direct-burial use.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28339A Key Specifications
- Max Current
- 14.4 Amps per Conductor at 30ºC
- Voltage Rating
- 600 V (TC-ER), 150 V (NPLF)
- Temperature Rating
- 90°C Dry, 90°C Wet; operating Wet/Dry: -30°C to 90°C
- Conductor
- 5 conductors, 16 AWG (7x24) bare copper
- Insulation
- PVC/Nylon - Polyvinyl Chloride + Nylon, 0.020 in (0.51 mm) nominal thickness
- Mechanical
- Overall diameter 0.359 in (9.12 mm); max pull tension 175 lbs (79.4 kg); bulk weight 85 lbs/1000ft
- Nominal Conductor DCR
- 4.2 Ohm/1000ft
- Outer Jacket
- PVC - Polyvinyl Chloride, 0.047 in (1.2 mm) nominal thickness, ripcord: Yes
Characteristics (datasheet)
- Conductor
- 5 conductors, 16 AWG (7x24) bare copper
- Insulation
- PVC/Nylon - Polyvinyl Chloride + Nylon, 0.020 in (0.51 mm) nominal thickness
- Outer Jacket
- PVC - Polyvinyl Chloride, 0.047 in (1.2 mm) nominal thickness, ripcord: Yes
- Voltage Rating
- 600 V (TC-ER), 150 V (NPLF)
- Temperature Rating
- 90°C Dry, 90°C Wet; operating Wet/Dry: -30°C to 90°C
- Nominal Conductor DCR
- 4.2 Ohm/1000ft
- Max Current
- 14.4 Amps per Conductor at 30ºC
- Mechanical
- Overall diameter 0.359 in (9.12 mm); max pull tension 175 lbs (79.4 kg); bulk weight 85 lbs/1000ft
28339A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 3018A — The Belden 3018A is a UL-listed instrumentation cable containing two triads of 2...
- 2831 — The Belden 2831 is a single-conductor communication and control cable featuring...
- 39122 — Belden 39122 is a 22 AWG (7x30) stranded tinned copper lead wire with PPO (polyp...
- 88442 — The Belden 88442 is a high-temperature, plenum-rated (CMP) electronic cable feat...
- 80052 — The Belden 80052 (ECOFLEX PUR) is a 3-conductor, 14 AWG tinned copper cable with...
- 7893A — The Belden 7893A is a digital audio snake cable with 16 individually shielded pa...
- 5698 — The Belden 5698 is a shielded multi-pair cable (XTRAGUARD 1) consisting of 5 pai...
- 28163A — The Belden 28163A is a 19-conductor, 10 AWG (7x18) bare copper cable with PVC/ny...
More Bulk Wire Cable
- 70105PU — The Belden 70105PU is a triple-shielded Profibus DP cable featuring a single pai...
- 9455 — The Belden 9455 is a multi-conductor electronic cable featuring nine 20 AWG stra...
- 35054 — Belden part 35054 is an XTRAGUARD 3 cable with four 20 AWG (7/28) stranded tinne...
- 8479 — The part 8479 is a 3-conductor portable cordage cable featuring 14AWG (41x30) ba...
- 3495C — The Belden 3495C is a 5-pair, 28 AWG tinned copper communication and control cab...
- 9941 — The Belden 9941 is a computer EIA RS-232 cable with five 22 AWG stranded tinned...
- 3086A — The 3086A is a DeviceBus® cable designed for Honeywell SDS, featuring one 16 AWG...
- 9925 — The Belden 9925 is a 3-conductor computer EIA RS-232/423 cable designed for exte...
28339A FAQ
What is 28339A?
28339A is a Bulk Wire Cable from Belden. The Belden 28339A is a 5-conductor, 16 AWG (7x24) bare copper power and control cable with PVC/nylon insulation (E2 color code: black, red, blue, orange, yellow) and a black PVC outer jacket with a ripcord. It is rated 600 V (TC-ER) and 150 V (NPLF) and is suitable for power and control applications up to 600 V, including Class 1 Division 2 hazardous locations. The unshielded cable is rated 90 °C dry/wet with an operating range of -30 °C to 90 °C wet/dry and is suitable for indoor, outdoor, sunlight-resistant, and direct-burial use.
Who manufactures 28339A?
28339A is manufactured by Belden.
Where can I download the 28339A datasheet PDF?
The 28339A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28339A specifications
Click to ask a quick question:
Parameters
| Conductor | 5 conductors, 16 AWG (7x24) bare copper |
| Insulation | PVC/Nylon - Polyvinyl Chloride + Nylon, 0.020 in (0.51 mm) nominal thickness |
| Max Current | 14.4 Amps per Conductor at 30ºC |
| Mechanical | Overall diameter 0.359 in (9.12 mm); max pull tension 175 lbs (79.4 kg); bulk weight 85 lbs/1000ft |
| Nominal Conductor DCR | 4.2 Ohm/1000ft |
| Outer Jacket | PVC - Polyvinyl Chloride, 0.047 in (1.2 mm) nominal thickness, ripcord: Yes |
| Temperature Rating | 90°C Dry, 90°C Wet; operating Wet/Dry: -30°C to 90°C |
| Voltage Rating | 600 V (TC-ER), 150 V (NPLF) |