5580C Datasheet
The Belden 5580C is a 5-conductor, 22 AWG tinned copper cable with semi-rigid PVC insulation, an overall aluminum/polyester shield, and a slate PVC outer jacket. It is rated for 300 V UL / 600 V CSA with an operating temperature range of -35 °C to +105 °C. This shielded cable is designed for industrial control systems, instrumentation, and analog/digital signal applications.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
5580C Key Specifications
- CSA Voltage Rating
- 600 V
- Nom. Capacitance Cond-to-Cond
- 35 pF/ft (110 pF/m)
- UL Voltage Rating
- 300 V
- Voltage Rating
- 300 V (UL) / 600 V (CSA AWM)
- Operating Temperature
- -35 °C to +105 °C (UL 105 °C)
- UL Temperature
- 105 °C
- Conductor
- 5 conductors, 22 AWG (7x30) TC - Tinned Copper
- Max Pull Tension
- 16.5 lbs (7.48 kg)
5580C Marking Code (SMD Code)
Top marking: Alpha Wire -* P/N 5580C 5C 22 AWG XTRAGUARD(R) 1 SHIELDED (UL) TYPE CM 105C SUN RES OR AWM 2343 80C 300V OR AWM 2517 105C 300V VW-1 --- LLXXXXXX · package Slate, Reel, 100 ft
Characteristics (datasheet)
- Conductor
- 5 conductors, 22 AWG (7x30) TC - Tinned Copper
- Voltage Rating
- 300 V (UL) / 600 V (CSA AWM)
- Operating Temperature
- -35 °C to +105 °C (UL 105 °C)
- Overall Cable Diameter (Nominal)
- 0.270 in (6.86 mm)
- Shielding
- Overall Aluminum/Polyester Bi-Laminate Tape Shield (100% coverage) with 22 AWG TC drainwire
- Max Pull Tension
- 16.5 lbs (7.48 kg)
- Min Bend Radius (Stationary)
- 2.7 in (69 mm)
- Nom. Capacitance Cond-to-Cond
- 35 pF/ft (110 pF/m)
Absolute Maximum Ratings
- UL Voltage Rating
- 300 V
- CSA Voltage Rating
- 600 V
- UL Temperature
- 105 °C
- Operating Temperature
- -35 °C to +105 °C
- Max Pull Tension
- 16.5 lbs (7.48 kg)
- Min Bend Radius (Stationary)
- 2.7 in (69 mm)
5580C Applications
- Industrial control systems, raceways, cable trays, and ducts
- Instrumentation and control circuits
- Analog and digital signals (4–20 mA, 0–10 V)
- PLC and DCS systems
- Sensors, encoders, solenoids, valves, actuators, and positioners
Other Belden parts
- 2834 — The Belden 2834 is a single-conductor, 22 AWG silver-plated copper communication...
- 8723 — The Belden 8723 is an individually shielded audio, control, and instrument cable...
- 934075101 — 1kV 32A Red Insulated Cable Assembly
- 25543 — The Belden 25543 is an XTRAGUARD 2 cable with three 14 AWG (41x30) tinned copper...
- 7789A — The Belden 7789A is a sub-miniature, riser-CMR rated digital coax snake cable co...
- 45104 — Belden part 45104 is an XTRAGUARD 4 cable with four 22 AWG (7x30) tinned copper...
- 6303UE — The Belden 6303UE is a plenum-rated security and sound cable (CMP) containing fi...
- 9562 — The Belden 9562 is an audio, control, and instrument cable featuring 24 AWG soli...
More Bulk Wire Cable
- 78035 — The Belden 78035 is an ECOCABLE consisting of 5 pairs of 22 AWG stranded tinned...
- 5388C — The 5388C is an XTRAGUARD 1 shielded cable with 8 conductors of 18 AWG tinned co...
- 78325 — The Belden 78325 is a shielded multi-conductor cable (ECOCABLE) featuring 5 pair...
- 79038 — The Belden 79038 (ECOFLEX) is a 4-conductor, 12 AWG tinned copper control cable...
- 9848 — The Belden 9848 is a single-conductor RG 58 coaxial cable featuring an 18 AWG so...
- 5545FE — The Belden 5545FE is a security and sound riser-CMR cable featuring six 22 AWG s...
- 5693 — The Belden 5693 is a shielded, multi-conductor cable containing five 26 AWG tinn...
- 2423C — The Belden 2423C is a 3-conductor, 18 AWG tinned copper communication and contro...
5580C FAQ
What is 5580C?
5580C is a Bulk Wire Cable from Belden. The Belden 5580C is a 5-conductor, 22 AWG tinned copper cable with semi-rigid PVC insulation, an overall aluminum/polyester shield, and a slate PVC outer jacket. It is rated for 300 V UL / 600 V CSA with an operating temperature range of -35 °C to +105 °C. This shielded cable is designed for industrial control systems, instrumentation, and analog/digital signal applications.
Who manufactures 5580C?
5580C is manufactured by Belden.
What is the marking code of 5580C?
According to its datasheet, 5580C in Slate, Reel, 100 ft is marked "Alpha Wire -* P/N 5580C 5C 22 AWG XTRAGUARD(R) 1 SHIELDED (UL) TYPE CM 105C SUN RES OR AWM 2343 80C 300V OR AWM 2517 105C 300V VW-1 --- LLXXXXXX".
Where can I download the 5580C datasheet PDF?
The 5580C datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 5580C specifications
Click to ask a quick question:
Parameters
| Conductor | 5 conductors, 22 AWG (7x30) TC - Tinned Copper |
| CSA Voltage Rating | 600 V |
| Max Pull Tension | 16.5 lbs (7.48 kg) |
| Min Bend Radius (Stationary) | 2.7 in (69 mm) |
| Nom. Capacitance Cond-to-Cond | 35 pF/ft (110 pF/m) |
| Operating Temperature | -35 °C to +105 °C (UL 105 °C) |
| Overall Cable Diameter (Nominal) | 0.270 in (6.86 mm) |
| Shielding | Overall Aluminum/Polyester Bi-Laminate Tape Shield (100% coverage) with 22 AWG TC drainwire |
| UL Temperature | 105 °C |
| UL Voltage Rating | 300 V |
| Voltage Rating | 300 V (UL) / 600 V (CSA AWM) |