28324A Datasheet
The Belden 28324A is a 25-conductor, 16 AWG (7x24 bare copper) power and control cable with PVC/nylon insulation and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF) for operation from -30°C to 90°C in wet/dry conditions, and is approved for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial installations. Listed applications include power and control applications up to 600 V and Class 1 Division 2 hazardous locations.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28324A Key Specifications
- Max current
- 8.1 Amps per Conductor at 30ºC
- Voltage rating
- 600 V (TC-ER), 150 V (NPLF)
- Operating temperature
- -30°C to 90°C (Wet/Dry)
- Bulk cable weight
- 357 lbs/1000ft
- Conductor construction
- 25 conductors, 16 AWG, 7x24 stranding, Bare Copper
- Max pull tension
- 892.5 lbs (404.8 kg)
- Nominal conductor DCR
- 4.2 Ohm/1000ft
- Overall cable diameter
- 0.714 in (18.1 mm)
Characteristics (datasheet)
- Conductor construction
- 25 conductors, 16 AWG, 7x24 stranding, Bare Copper
- Nominal conductor DCR
- 4.2 Ohm/1000ft
- Max current
- 8.1 Amps per Conductor at 30ºC
- Voltage rating
- 600 V (TC-ER), 150 V (NPLF)
- Operating temperature
- -30°C to 90°C (Wet/Dry)
- Overall cable diameter
- 0.714 in (18.1 mm)
- Max pull tension
- 892.5 lbs (404.8 kg)
- Bulk cable weight
- 357 lbs/1000ft
28324A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 4101FE — The Belden 4101FE is a security and commercial audio cable featuring three 14 AW...
- 9434 — The Belden 9434 is a 50-conductor electronic cable made of 22AWG (7x30) tinned c...
- 70082 — The Belden 70082 is a discontinued 75 Ohm SDI coaxial cable built with an RG-6 t...
- 9182 — The Belden 9182 is a 150Ω twinaxial cable consisting of a single pair of 22 AWG...
- 79254 — The Belden 79254 is an ECOFLEX multi-conductor cable featuring 8 conductors of 2...
- 5324UL — The 5324UL is a fire alarm riser cable (FPLR) containing six 18 AWG solid bare c...
- 27149A — Belden 27149A is a UL Type TC power and control cable with two 8 AWG bare copper...
- 5196C — The Belden 5196C (Alpha Wire) is a 6-conductor, 22 AWG tinned copper cable with...
More Bulk Wire Cable
- 4340FDW — The 4340FDW is a single-pair OSDP RS-485 transmission cable designed for use in...
- 65618 — The Belden 65618 is an 18-conductor, 16 AWG flexible control cable featuring bar...
- 5052C — The Belden 5052C is a 2-conductor, 20 AWG tinned copper control cable with PVC i...
- 26506D — The Belden 26506D is a Canadian Instrumentation Cable (TC-ACIC) rated 300 V, bui...
- 25013 — Belden part 25013 (XTRAGUARD 2) is a 3-conductor, 24 AWG (7x32 stranded tinned c...
- 28093A — The Belden 28093A is a UL Type TC (1277) power and control cable with 15 conduct...
- 82842 — The Belden 82842 is a plenum-rated (CMP) RS-485 cable featuring two pairs of 24...
- 80022 — The Belden 80022 (ECOFLEX PUR) is a 5-conductor, 20 AWG tinned copper cable with...
28324A FAQ
What is 28324A?
28324A is a Bulk Wire Cable from Belden. The Belden 28324A is a 25-conductor, 16 AWG (7x24 bare copper) power and control cable with PVC/nylon insulation and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF) for operation from -30°C to 90°C in wet/dry conditions, and is approved for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial installations. Listed applications include power and control applications up to 600 V and Class 1 Division 2 hazardous locations.
Who manufactures 28324A?
28324A is manufactured by Belden.
Where can I download the 28324A datasheet PDF?
The 28324A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28324A specifications
Click to ask a quick question:
Parameters
| Bulk cable weight | 357 lbs/1000ft |
| Conductor construction | 25 conductors, 16 AWG, 7x24 stranding, Bare Copper |
| Max current | 8.1 Amps per Conductor at 30ºC |
| Max pull tension | 892.5 lbs (404.8 kg) |
| Nominal conductor DCR | 4.2 Ohm/1000ft |
| Operating temperature | -30°C to 90°C (Wet/Dry) |
| Overall cable diameter | 0.714 in (18.1 mm) |
| Voltage rating | 600 V (TC-ER), 150 V (NPLF) |