28616A Datasheet
The Belden 28616A is an 8-conductor, 16 AWG (7x24) bare copper cable with PVC/nylon insulation (E2 color code) and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF) for power and control applications up to 600 V, including Class 1 Division 2 hazardous locations, and is suitable for indoor, outdoor, sunlight-resistant, direct-burial use at 90 °C dry/wet.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28616A Key Specifications
- Max current
- 12.6 Amps per conductor at 30°C
- Voltage rating
- 600 V (TC-ER), 150 V (NPLF)
- Temperature rating
- 90°C dry, 90°C wet; wet/dry operating -30°C to 90°C
- Conductors
- 8
- Conductor size / stranding / material
- 16 AWG 7x24 bare copper
- Max pull tension
- 285.6 lbs (129.5 kg)
- Nominal conductor DCR
- 4.45 Ohm/1000ft
- Overall cable diameter (nominal)
- 0.422 in (10.7 mm)
Characteristics (datasheet)
- Conductors
- 8
- Conductor size / stranding / material
- 16 AWG 7x24 bare copper
- Voltage rating
- 600 V (TC-ER), 150 V (NPLF)
- Temperature rating
- 90°C dry, 90°C wet; wet/dry operating -30°C to 90°C
- Nominal conductor DCR
- 4.45 Ohm/1000ft
- Max current
- 12.6 Amps per conductor at 30°C
- Overall cable diameter (nominal)
- 0.422 in (10.7 mm)
- Max pull tension
- 285.6 lbs (129.5 kg)
28616A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 5021C — The Belden 5021C is a XTRAGUARD 1, single-pair 22 AWG stranded tinned copper cab...
- 5413 — The Belden 5413 is an XTRAGUARD 1 multi-conductor cable featuring three 20 AWG s...
- 6549PA — The Belden 6549PA is a discontinued, plenum-rated multi-pair cable designed for...
- 70094A — The Belden 70094A is a discontinued Category 5e industrial Ethernet cable design...
- 7940A — The Belden 7940A is a DataTuff Cat 6 industrial Ethernet cable containing four b...
- 934062103 — 60V 16A Yellow Cable Test Probe
- 6453 — The Belden 6453 is a shielded, 1-pair 22 AWG tinned copper cable with foam HDPE...
- 5514 — The part 5514 is an XTRAGUARD 1 cable consisting of 4 conductors of 20 AWG tinne...
More Bulk Wire Cable
- 79207 — The 79207 is a 12-conductor, 20 AWG stranded tinned copper cable with mPPE insul...
- 31514 — The Belden 31514 is a low-temperature rubber lead wire constructed with 14 AWG (...
- 86602CY — The Belden 86602CY is an XTRAGUARD FLEX continuous flex data cable with 2 pairs...
- 5054C — The Belden 5054C is a 4-conductor, 20 AWG tinned copper control cable with PVC i...
- 88761 — The Belden 88761 is a high-temperature, plenum-rated (CMP) 2-conductor 22AWG tin...
- 5678 — The Belden 5678 is an XTRAGUARD 1 shielded multi-conductor cable featuring seven...
- 7924A — The Belden 7924A is an Industrial Ethernet Category 5e cable with four bonded pa...
- 1030A — The Belden 1030A is a UL-listed instrumentation cable designed for industrial co...
28616A FAQ
What is 28616A?
28616A is a Bulk Wire Cable from Belden. The Belden 28616A is an 8-conductor, 16 AWG (7x24) bare copper cable with PVC/nylon insulation (E2 color code) and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF) for power and control applications up to 600 V, including Class 1 Division 2 hazardous locations, and is suitable for indoor, outdoor, sunlight-resistant, direct-burial use at 90 °C dry/wet.
Who manufactures 28616A?
28616A is manufactured by Belden.
Where can I download the 28616A datasheet PDF?
The 28616A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28616A specifications
Click to ask a quick question:
Parameters
| Conductors | 8 |
| Conductor size / stranding / material | 16 AWG 7x24 bare copper |
| Max current | 12.6 Amps per conductor at 30°C |
| Max pull tension | 285.6 lbs (129.5 kg) |
| Nominal conductor DCR | 4.45 Ohm/1000ft |
| Overall cable diameter (nominal) | 0.422 in (10.7 mm) |
| Temperature rating | 90°C dry, 90°C wet; wet/dry operating -30°C to 90°C |
| Voltage rating | 600 V (TC-ER), 150 V (NPLF) |