1030A Datasheet

BeldenBulk Wire Cable

The Belden 1030A is a UL-listed instrumentation cable designed for industrial control, raceways, digital control, instruments, and control circuits. It features a single pair of 16 AWG stranded bare copper conductors with PVC insulation, a 100% Beldfoil shield with a drainwire, and a black PVC outer jacket. The cable is rated for an operating temperature of -30°C to +105°C, a maximum voltage of 300 V (PLTC, CMG, AWM 2464) / 150 V (ITC), and a maximum current of 18 Amps per conductor.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

1030A Key Specifications

Max. Current
18 Amps per conductor @ 30°C
UL Voltage Rating
300 V (PLTC, CMG, AWM 2464), 150 V (ITC)
Operating Temperature
-30°C to +105°C (UL Temperature 105°C)
Bulk Cable Weight
40 lbs/1000ft (60 kg/km)
Conductor
1 Pair 16 AWG 7x20 BC - Bare Copper
Insulation Material
PVC - Polyvinyl Chloride, Nom. Thickness 0.017 in (0.43 mm)
Max. Pull Tension
94 lbs (43 kg)
Nom. Conductor DCR
4.2 Ohm/1000ft (14 Ohm/km)

Characteristics (datasheet)

Conductor
1 Pair 16 AWG 7x20 BC - Bare Copper
Insulation Material
PVC - Polyvinyl Chloride, Nom. Thickness 0.017 in (0.43 mm)
Outer Shield
Tape, Bi-Laminate (Alum+Poly), Coverage 100%, Drainwire Type 18 AWG (7x26) TC
Outer Jacket
PVC - Polyvinyl Chloride, Nom. Thickness 0.037 in (0.94 mm), Black
Nominal Overall Cable Diameter
0.259 in (6.58 mm)
UL Voltage Rating
300 V (PLTC, CMG, AWM 2464), 150 V (ITC)
Max. Current
18 Amps per conductor @ 30°C
Nom. Conductor DCR
4.2 Ohm/1000ft (14 Ohm/km)
Operating Temperature
-30°C to +105°C (UL Temperature 105°C)
Max. Pull Tension
94 lbs (43 kg)
Bulk Cable Weight
40 lbs/1000ft (60 kg/km)

1030A Applications

  • Industrial Control
  • Raceways, cable trays and ducts
  • Digital Control
  • Instruments (4-20ma, 0-10v, ...)
  • Low voltage digital control (24v, ...)
  • Encoders
  • Control circuits
  • Distributed control system (DCS)
  • Programmable logic controller (PLC)
  • Solenoids, Valves, Actuators, Positioners

Other Belden parts

  • 8055 — The Belden 8055 is a #30 AWG solid bare copper magnet wire with PUR/Nylon insula...
  • 1504A — The Belden 1504A is a CM-rated parallel audio cable constructed with two 22 AWG...
  • 8175 — The Belden 8175 is a computer EIA RS-232/422 digital audio cable with 15 individ...
  • 29023 — Belden 29023 is a Canadian Instrumentation Cable type TC-ACIC rated for 600 V po...
  • 65807 — The Belden 65807 is a 7-conductor 18 AWG XTRAGUARD FLEX flexible control cable f...
  • 78218 — The Belden 78218 is an ECOCABLE consisting of 8 pairs of 26 AWG tinned copper co...
  • 5192C — The Belden 5192C is a 2-conductor, 22 AWG stranded tinned copper cable with semi...
  • 34402 — Belden 34402 is a 2 AWG stranded tinned copper lead wire with CSPE (chlorosulpho...

More Bulk Wire Cable

  • 86303 — The Belden 86303 is a flexible, 3-conductor, 22 AWG tinned copper data cable wit...
  • 8918 — The Belden 8918 is a low-temperature plastic lead wire with an 18 AWG tinned cop...
  • 88102 — The Belden 88102 is a plenum-rated, overall Beldfoil-shielded EIA RS-232/422 cab...
  • 9576 — The Belden 9576 is a 6-conductor, 22 AWG solid tinned copper cable with PVC insu...
  • 6084C — The 6084C is a 4-pair 24 AWG tinned copper shielded communication and control ca...
  • 6542FE — The Belden 6542FE is a plenum-rated (CMP) multi-pair cable designed for security...
  • 9806 — The Belden 9806 is a shielded, 4-pair, 28 AWG stranded tinned copper cable desig...
  • 6077 — The Belden 6077 is a Teck90 600V, 3+G conductor cable featuring 12+14 AWG bare c...

1030A FAQ

What is 1030A?

1030A is a Bulk Wire Cable from Belden. The Belden 1030A is a UL-listed instrumentation cable designed for industrial control, raceways, digital control, instruments, and control circuits. It features a single pair of 16 AWG stranded bare copper conductors with PVC insulation, a 100% Beldfoil shield with a drainwire, and a black PVC outer jacket. The cable is rated for an operating temperature of -30°C to +105°C, a maximum voltage of 300 V (PLTC, CMG, AWM 2464) / 150 V (ITC), and a maximum current of 18 Amps per conductor.

Who manufactures 1030A?

1030A is manufactured by Belden.

Where can I download the 1030A datasheet PDF?

The 1030A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 1030A specifications

AI Powered

Click to ask a quick question:

Parameters

Bulk Cable Weight40 lbs/1000ft (60 kg/km)
Conductor1 Pair 16 AWG 7x20 BC - Bare Copper
Insulation MaterialPVC - Polyvinyl Chloride, Nom. Thickness 0.017 in (0.43 mm)
Max. Current18 Amps per conductor @ 30°C
Max. Pull Tension94 lbs (43 kg)
Nom. Conductor DCR4.2 Ohm/1000ft (14 Ohm/km)
Nominal Overall Cable Diameter0.259 in (6.58 mm)
Operating Temperature-30°C to +105°C (UL Temperature 105°C)
Outer JacketPVC - Polyvinyl Chloride, Nom. Thickness 0.037 in (0.94 mm), Black
Outer ShieldTape, Bi-Laminate (Alum+Poly), Coverage 100%, Drainwire Type 18 AWG (7x26) TC
UL Voltage Rating300 V (PLTC, CMG, AWM 2464), 150 V (ITC)