28615A Datasheet

BeldenBulk Wire Cable

Belden 28615A is a UL Type TC (1277) power and control cable with 6 conductors of 16 AWG (7x24) bare copper, PVC/nylon insulation, and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF) at 90 °C dry/wet, is sunlight resistant and suitable for direct burial, and is recommended for power and control applications up to 600 V including Class 1 Division 2 hazardous locations.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

28615A Key Specifications

Voltage Rating
600 V (TC-ER), 150 V (NPLF)
Temperature
90 °C Dry, 90 °C Wet; Wet/Dry: -30 °C to 90 °C
Bend Radius
Stationary min 1.564 in (39.73 mm); Installation min 1.955 in (49.66 mm)
Conductor
6 conductors, 16 AWG, 7x24 stranding, bare copper
Electrical
Nom. conductor DCR 4.45 Ohm/1000ft; Max. current 14.4 Amps per Conductor at 30 ºC
Insulation
PVC/Nylon, nominal thickness 0.020 in (0.51 mm), nominal diameter 0.099 in (2.5 mm), colors Black, Red, Blue, Orange, Yellow, Brown
Mechanical
Max. pull tension 214.2 lbs (97.16 kg); Bulk cable weight 98 lbs/1000ft
Outer Jacket
Black PVC, nominal thickness 0.047 in (1.2 mm), nominal diameter 0.391 in (9.93 mm), ripcord: Yes

Characteristics (datasheet)

Conductor
6 conductors, 16 AWG, 7x24 stranding, bare copper
Insulation
PVC/Nylon, nominal thickness 0.020 in (0.51 mm), nominal diameter 0.099 in (2.5 mm), colors Black, Red, Blue, Orange, Yellow, Brown
Shield
No Shield
Outer Jacket
Black PVC, nominal thickness 0.047 in (1.2 mm), nominal diameter 0.391 in (9.93 mm), ripcord: Yes
Overall Cable Diameter
0.391 in (9.93 mm) nominal
Voltage Rating
600 V (TC-ER), 150 V (NPLF)
Electrical
Nom. conductor DCR 4.45 Ohm/1000ft; Max. current 14.4 Amps per Conductor at 30 ºC
Temperature
90 °C Dry, 90 °C Wet; Wet/Dry: -30 °C to 90 °C
Bend Radius
Stationary min 1.564 in (39.73 mm); Installation min 1.955 in (49.66 mm)
Mechanical
Max. pull tension 214.2 lbs (97.16 kg); Bulk cable weight 98 lbs/1000ft

28615A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 30806 — Belden 30806 is a 6 AWG rubber lead wire with an 84x25 tinned copper conductor,...
  • 7949A — The Belden 7949A is a composite cable designed for data, audio, video, security,...
  • 9979 — The part 9979 is a low-temp plastic lead wire featuring a 22 AWG solid tinned co...
  • 77803W — The Belden 77803W is a MachFlex™ high-flexibility cable designed with a 3+G cond...
  • 2213C — The Belden 2213C is a multi-conductor communication and control cable featuring...
  • 28090A — The Belden 28090A is a UL Type TC (1277) power and control cable with 12 conduct...
  • 74040NH — The Belden 74040NH is a DataTuff industrial Single Pair Ethernet (SPE) cable des...
  • 930317801 — HIRSCHMANN TEST AND MEASUREMENT 930317801 CROCODILE CLIP, 4MM, RED, 8A

More Bulk Wire Cable

  • 3242 — The Belden 3242 is a 3-conductor, 18 AWG tinned copper communication and control...
  • 5925 — The Belden 5925 is an 8-conductor 28 AWG tinned copper cable with semi-rigid PVC...
  • 5486C — The Belden 5486C is a XTRAGUARD 1 shielded multi-conductor cable featuring 6 pai...
  • 7919A — The 7919A is an industrial Ethernet Cat 5e cable featuring four pairs of 24 AWG...
  • 29504 — Belden 29504 is a flexible VFD motor supply cable with three 8 AWG tinned copper...
  • 6178 — The Belden 6178 is a Teck90 600V/1000V cable featuring two 4/0 AWG bare copper c...
  • 78352 — The Belden 78352 is an ECOCABLE shielded multi-pair cable designed for data, com...
  • 77404W — The Belden 77404W is a MachFlex™ high-flex cable designed with 4+G conductor 14A...

28615A FAQ

What is 28615A?

28615A is a Bulk Wire Cable from Belden. Belden 28615A is a UL Type TC (1277) power and control cable with 6 conductors of 16 AWG (7x24) bare copper, PVC/nylon insulation, and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF) at 90 °C dry/wet, is sunlight resistant and suitable for direct burial, and is recommended for power and control applications up to 600 V including Class 1 Division 2 hazardous locations.

Who manufactures 28615A?

28615A is manufactured by Belden.

Where can I download the 28615A datasheet PDF?

The 28615A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 28615A specifications

AI Powered

Click to ask a quick question:

Parameters

Bend RadiusStationary min 1.564 in (39.73 mm); Installation min 1.955 in (49.66 mm)
Conductor6 conductors, 16 AWG, 7x24 stranding, bare copper
ElectricalNom. conductor DCR 4.45 Ohm/1000ft; Max. current 14.4 Amps per Conductor at 30 ºC
InsulationPVC/Nylon, nominal thickness 0.020 in (0.51 mm), nominal diameter 0.099 in (2.5 mm), colors Black, Red, Blue, Orange, Yellow, Brown
MechanicalMax. pull tension 214.2 lbs (97.16 kg); Bulk cable weight 98 lbs/1000ft
Outer JacketBlack PVC, nominal thickness 0.047 in (1.2 mm), nominal diameter 0.391 in (9.93 mm), ripcord: Yes
Overall Cable Diameter0.391 in (9.93 mm) nominal
ShieldNo Shield
Temperature90 °C Dry, 90 °C Wet; Wet/Dry: -30 °C to 90 °C
Voltage Rating600 V (TC-ER), 150 V (NPLF)