28163A Datasheet

BeldenBulk Wire Cable

The Belden 28163A is a 19-conductor, 10 AWG (7x18) bare copper cable with PVC/nylon insulation and a black PVC outer jacket, rated 600 V TC-ER for 90 °C dry/wet use. It is intended for power and control applications up to 600 V, including Class 1 Division 2 hazardous locations, and is rated for indoor, outdoor, sunlight/UV resistance and direct burial. It has no overall shield and includes a ripcord.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

28163A Key Specifications

Max. current
20 Amps per Conductor at 30ºC
UL voltage rating
600 V
Temperature rating
90°C Dry, 90°C Wet; operating Wet/Dry -30°C To +90°C
Bulk cable weight
890 lbs/1000ft
Conductors / size / stranding / material
19 conductors, 10 AWG, 7x18 stranding, bare copper
Insulation
PVC/Nylon (Polyvinyl Chloride + Nylon), 0.028 in (0.71 mm) nominal thickness
Max. pull tension
2929.2 lbs (1328.7 kg)
Nominal conductor DCR
1.07 Ohm/1000ft

Characteristics (datasheet)

Conductors / size / stranding / material
19 conductors, 10 AWG, 7x18 stranding, bare copper
Insulation
PVC/Nylon (Polyvinyl Chloride + Nylon), 0.028 in (0.71 mm) nominal thickness
Outer jacket
PVC, 0.083 in (2.1 mm) nominal thickness, ripcord yes
Overall cable diameter (nominal)
0.986 in
UL voltage rating
600 V
Max. current
20 Amps per Conductor at 30ºC
Nominal conductor DCR
1.07 Ohm/1000ft
Temperature rating
90°C Dry, 90°C Wet; operating Wet/Dry -30°C To +90°C
Max. pull tension
2929.2 lbs (1328.7 kg)
Bulk cable weight
890 lbs/1000ft

28163A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 5373C — The Belden 5373C is a shielded, 3-pair, 18 AWG tinned copper cable with PVC insu...
  • 934077109 — TEST LEAD, VIOLET, 4MM
  • 48643AZ — The Belden 48643AZ is a UL Type TC power and control cable rated up to 600 V. It...
  • 8463MN — The Belden 8463MN SpaceMaker™ is a 3-conductor 18 AWG tinned copper cable with p...
  • 7818A — The Belden 7818A is a discontinued harsh environment SMPTE 311M cable designed f...
  • 8018 — The Belden 8018 is a solid, soft annealed aluminum bus bar wire with an 8 AWG co...
  • 83915 — The Belden 83915 is a Type E thermocouple cable consisting of a single pair of 2...
  • 78249 — The Belden 78249 is a high-performance 9-pair 20 AWG tinned copper cable with mo...

More Bulk Wire Cable

  • 8075 — The Belden 8075 is a class 200 magnet wire featuring a single solid 18 AWG bare...
  • 30802 — Belden 30802 is a 2 AWG rubber lead wire with 163x24 stranded tinned copper cond...
  • 9993 — The Belden 9993 is an audio, control, and instrument cable featuring 12 individu...
  • 65834 — The Belden 65834 is a 34-conductor, 18 AWG bare copper flexible control cable wi...
  • 5170C — The 5170C is an XTRAGUARD 1 shielded cable featuring 10 conductors of 18 AWG tin...
  • 9620 — The Belden 9620 is a multi-conductor cable featuring five 16 AWG stranded tinned...
  • 1595 — The Belden 1595 is a heavy-duty, single-conductor TW-75 rated cable designed for...
  • 9699MN — The Belden 9699MN is a SpaceMaker™ 4-pair, 24 AWG tinned copper cable with polyp...

28163A FAQ

What is 28163A?

28163A is a Bulk Wire Cable from Belden. The Belden 28163A is a 19-conductor, 10 AWG (7x18) bare copper cable with PVC/nylon insulation and a black PVC outer jacket, rated 600 V TC-ER for 90 °C dry/wet use. It is intended for power and control applications up to 600 V, including Class 1 Division 2 hazardous locations, and is rated for indoor, outdoor, sunlight/UV resistance and direct burial. It has no overall shield and includes a ripcord.

Who manufactures 28163A?

28163A is manufactured by Belden.

Where can I download the 28163A datasheet PDF?

The 28163A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 28163A specifications

AI Powered

Click to ask a quick question:

Parameters

Bulk cable weight890 lbs/1000ft
Conductors / size / stranding / material19 conductors, 10 AWG, 7x18 stranding, bare copper
InsulationPVC/Nylon (Polyvinyl Chloride + Nylon), 0.028 in (0.71 mm) nominal thickness
Max. current20 Amps per Conductor at 30ºC
Max. pull tension2929.2 lbs (1328.7 kg)
Nominal conductor DCR1.07 Ohm/1000ft
Outer jacketPVC, 0.083 in (2.1 mm) nominal thickness, ripcord yes
Overall cable diameter (nominal)0.986 in
Temperature rating90°C Dry, 90°C Wet; operating Wet/Dry -30°C To +90°C
UL voltage rating600 V