27149A Datasheet

BeldenBulk Wire Cable

Belden 27149A is a UL Type TC power and control cable with two 8 AWG bare copper conductors (7x16 stranding) and one 10 AWG bare copper ground wire (7x18 stranding). It uses PVC/nylon conductor insulation and a black PVC jacket, rated 600 V and 90°C Dry / 75°C Wet, and is suitable for indoor, outdoor, sunlight-resistant, direct burial, and Class 1 Division 2 hazardous locations. No pinout or absolute maximum ratings table applies to this cable product.\n\n"}]}

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

27149A Key Specifications

Max current
55 Amps per Conductor at 30ºC (conductors); 42 Amps per Conductor at 25ºC (ground wire)
UL Voltage Rating
600 V
Temperature rating
90°C Dry, 75°C Wet (UL); operating -30°C To +75°C Wet/90°C Dry
Conductors
2 x 8 AWG (7x16 bare copper) + 1 x 10 AWG ground wire (7x18 bare copper)
Insulation
PVC/Nylon, 0.038 in (0.97 mm) nominal thickness
Jacket
Black PVC, 0.063 in (1.6 mm) nominal thickness
Max pull tension
573.6 lbs (260.2 kg)
Overall cable diameter
0.561 in

Characteristics (datasheet)

Conductors
2 x 8 AWG (7x16 bare copper) + 1 x 10 AWG ground wire (7x18 bare copper)
Insulation
PVC/Nylon, 0.038 in (0.97 mm) nominal thickness
Jacket
Black PVC, 0.063 in (1.6 mm) nominal thickness
Overall cable diameter
0.561 in
UL Voltage Rating
600 V
Temperature rating
90°C Dry, 75°C Wet (UL); operating -30°C To +75°C Wet/90°C Dry
Max current
55 Amps per Conductor at 30ºC (conductors); 42 Amps per Conductor at 25ºC (ground wire)
Max pull tension
573.6 lbs (260.2 kg)

27149A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 25388 — Belden part 25388 is an XTRAGUARD 2 cable with 8 conductors of 18 AWG (16/30) ti...
  • 29547 — Belden 29547 is a flexible VFD motor supply cable with three 4/0 AWG tinned copp...
  • 28156A — The Belden 28156A is a UL Type TC power and control cable with three 4 AWG bare...
  • 74001 — The Belden 74001 is a high-performance 4-conductor, 22 AWG tinned copper cable f...
  • 78021 — The Belden 78021 is a multi-conductor cable featuring 15 conductors of 26 AWG ti...
  • 5690 — The Belden 5690 is a 2-pair, 26 AWG tinned copper cable with semi-rigid PVC insu...
  • 83010 — The Belden 83010 is a high-temperature plastic lead wire featuring a 16 AWG (19x...
  • 1793C — The Belden 1793C is a 2-conductor, 22 AWG solid tinned copper communication and...

More Bulk Wire Cable

  • 65404 — The Belden 65404 is an XTRAGUARD FLEX flexible control cable featuring four 14 A...
  • 1407B — The Belden 1407B is a highly flexible RGB video coaxial cable designed for trans...
  • 1323C — The Belden 1323C is a communication and control cable consisting of 9 pairs of 2...
  • 1761 — The Belden 1761 is a 3-conductor, 12 AWG tinned copper control and communication...
  • 7710A — The Belden 7710A is a VideoFLEX Digital Coax Snake Cable with a riser-CMR rating...
  • 7026 — The Belden 7026 is a single-conductor hook-up wire featuring an 18 AWG tinned co...
  • 43906LW — The Belden 43906LW is a 2-pair 22 AWG/0.34 mm² DMX512 lighting control cable wit...
  • 6634 — The Belden 6634 is a 4-conductor, 22 AWG tinned copper control cable with PVC ir...

27149A FAQ

What is 27149A?

27149A is a Bulk Wire Cable from Belden. Belden 27149A is a UL Type TC power and control cable with two 8 AWG bare copper conductors (7x16 stranding) and one 10 AWG bare copper ground wire (7x18 stranding). It uses PVC/nylon conductor insulation and a black PVC jacket, rated 600 V and 90°C Dry / 75°C Wet, and is suitable for indoor, outdoor, sunlight-resistant, direct burial, and Class 1 Division 2 hazardous locations. No pinout or absolute maximum ratings table applies to this cable product.\n\n"}]}.

Who manufactures 27149A?

27149A is manufactured by Belden.

Where can I download the 27149A datasheet PDF?

The 27149A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 27149A specifications

AI Powered

Click to ask a quick question:

Parameters

Conductors2 x 8 AWG (7x16 bare copper) + 1 x 10 AWG ground wire (7x18 bare copper)
InsulationPVC/Nylon, 0.038 in (0.97 mm) nominal thickness
JacketBlack PVC, 0.063 in (1.6 mm) nominal thickness
Max current55 Amps per Conductor at 30ºC (conductors); 42 Amps per Conductor at 25ºC (ground wire)
Max pull tension573.6 lbs (260.2 kg)
Overall cable diameter0.561 in
Temperature rating90°C Dry, 75°C Wet (UL); operating -30°C To +75°C Wet/90°C Dry
UL Voltage Rating600 V