28168A Datasheet

BeldenBulk Wire Cable

The Belden 28168A is a UL Type TC (1277) power and control cable with three 1/0 AWG bare copper conductors plus one 6 AWG bare copper ground conductor. It features PVC/nylon insulation and a black PVC outer jacket, rated for 600 V and 90 °C dry/wet operation. It is suitable for indoor, outdoor, sunlight-resistant, and direct burial use, including Class 1 Division 2 hazardous locations.\n\n

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

28168A Key Specifications

Max. Current (Conductors)
170 Amps per Conductor at 30ºC
Max. Current (Ground)
75 Amps per Conductor at 30ºC
UL Voltage Rating
600 V (TC-ER)
Temperature Rating
90°C Dry, 90°C Wet
Bend Radius (Stationary / Installation Min.)
6.1 in (150 mm) / 6.1 in (150 mm)
Conductor Nom. DCR
0.106 Ohm/1000ft
Ground Nom. DCR
0.4 Ohm/1000ft (1.3 Ohm/km)
Max. Pull Tension
4108.1 lbs (1863.4 kg)

Characteristics (datasheet)

UL Voltage Rating
600 V (TC-ER)
Conductor Nom. DCR
0.106 Ohm/1000ft
Max. Current (Conductors)
170 Amps per Conductor at 30ºC
Ground Nom. DCR
0.4 Ohm/1000ft (1.3 Ohm/km)
Max. Current (Ground)
75 Amps per Conductor at 30ºC
Temperature Rating
90°C Dry, 90°C Wet
Bend Radius (Stationary / Installation Min.)
6.1 in (150 mm) / 6.1 in (150 mm)
Max. Pull Tension
4108.1 lbs (1863.4 kg)

28168A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 89696 — The Belden 89696 is a plenum-rated computer point-of-sale (POS) cable designed f...
  • 70082 — The Belden 70082 is a discontinued 75 Ohm SDI coaxial cable built with an RG-6 t...
  • 1561 — The Belden 1561 is a single-conductor, 22 AWG solid tinned copper hook-up wire w...
  • 9961 — The Belden 9961 is a single-conductor electronic cable featuring a 20 AWG strand...
  • 78719ELZ — The Belden 78719ELZ is a shielded, 2-conductor 16 AWG tinned copper cable with f...
  • 932146101 — HIRSCHMANN TEST AND MEASUREMENT 932146101 CROCODILE CLIP, 4MM...
  • 1303E — The Belden 1303E is a field-deployable CAT6A patch horizontal and building backb...
  • 8185 — The Belden 8185 is a computer EIA RS-232/422 digital audio cable featuring 25 in...

More Bulk Wire Cable

  • 31014 — The Belden 31014 is a 14 AWG stranded tinned copper lead wire with XLPO/XLP/XLPE...
  • 9880 — The Belden 9880 is a Thicknet 10BASE5 coaxial cable designed for IEEE 802.3 Ethe...
  • 5689 — The Belden 5689 is a 15-conductor, 26 AWG stranded tinned copper cable with semi...
  • 79001 — The Belden 79001 is an ECOFLEX two-conductor 20 AWG tinned copper cable with mod...
  • 2471 — The Belden 2471 is a communication and control cable designed for data, communic...
  • 1216C — The Belden 1216C is a 6-conductor, 24 AWG tinned copper communication and contro...
  • 1364A — The Belden 1364A is a 12-pair 16 AWG tinned copper fieldbus cable with polypropy...
  • 48331AS — The Belden 48331AS is a UL Type TC power and control cable with three 16 AWG bar...

28168A FAQ

What is 28168A?

28168A is a Bulk Wire Cable from Belden. The Belden 28168A is a UL Type TC (1277) power and control cable with three 1/0 AWG bare copper conductors plus one 6 AWG bare copper ground conductor. It features PVC/nylon insulation and a black PVC outer jacket, rated for 600 V and 90 °C dry/wet operation. It is suitable for indoor, outdoor, sunlight-resistant, and direct burial use, including Class 1 Division 2 hazardous locations.\n\n.

Who manufactures 28168A?

28168A is manufactured by Belden.

Where can I download the 28168A datasheet PDF?

The 28168A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 28168A specifications

AI Powered

Click to ask a quick question:

Parameters

Bend Radius (Stationary / Installation Min.)6.1 in (150 mm) / 6.1 in (150 mm)
Conductor Nom. DCR0.106 Ohm/1000ft
Ground Nom. DCR0.4 Ohm/1000ft (1.3 Ohm/km)
Max. Current (Conductors)170 Amps per Conductor at 30ºC
Max. Current (Ground)75 Amps per Conductor at 30ºC
Max. Pull Tension4108.1 lbs (1863.4 kg)
Temperature Rating90°C Dry, 90°C Wet
UL Voltage Rating600 V (TC-ER)