BeldenBulk Wire Cable

The Belden 1364A is a 12-pair 16 AWG tinned copper fieldbus cable with polypropylene insulation, individual and overall Beldfoil shields, and an orange PVC outer jacket. It is designed for harsh environment digital and serial two-way communication, suitable for use in oil and gas extraction, petrochemical plants, Profibus, and Foundation FieldBus process automation.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

1364A Key Specifications

Max. Current
5.2 Amps per Conductor
Nom. Capacitance Cond-to-Shield
45 pF/ft (150 pF/m)
UL Voltage Rating
300 V RMS
Operating Temperature
-40°C to +105°C
Conductor
12 pairs, 16 AWG (7x24) TC - Tinned Copper
Nom. Characteristic Impedance
100 Ohm
Nom. Conductor DCR
4.2 Ohm/1000ft (14 Ohm/km)
Nom. Outer Diameter
1.105 in

Characteristics (datasheet)

Conductor
12 pairs, 16 AWG (7x24) TC - Tinned Copper
Nom. Conductor DCR
4.2 Ohm/1000ft (14 Ohm/km)
Nom. Characteristic Impedance
100 Ohm
Nom. Capacitance Cond-to-Shield
45 pF/ft (150 pF/m)
Max. Current
5.2 Amps per Conductor
UL Voltage Rating
300 V RMS
Operating Temperature
-40°C to +105°C
Nom. Outer Diameter
1.105 in

1364A Applications

  • harsh environment digital and serial two-way communication
  • oil and gas extraction and refining sites
  • petrochemical
  • Profibus process automation
  • Foundation FieldBus process automation
  • extreme temperature environments
  • exposure to humidity/moisture, dust, and oil
  • remote locations long distance applications

Other Belden parts

  • 9904 — The Belden 9904 is a low-temperature plastic lead wire featuring a 4 AWG strande...
  • 1121 — The Belden 1121 is a 3-conductor, 28 AWG tinned copper cable with PVC insulation...
  • 6002UE — The Belden 6002UE is a plenum-rated, CL2P/FPLP security and sound cable featurin...
  • 29007 — The Belden 29007 is a Canadian Instrumentation Cable (TC-ACIC) rated 600 V, cont...
  • 2260 — The Belden 2260 is a 2-conductor 16 AWG tinned copper communication and control...
  • 9778 — The Belden 9778 is a 1-conductor 20 AWG stranded tinned copper microphone cable...
  • 1077A — The Belden 1077A is a UL-listed instrumentation cable designed with 8 pairs of 2...
  • 6228C — The 6228C is a shielded, 8-pair communication and control cable constructed with...

More Bulk Wire Cable

  • 5006C — The Belden 5006C is a 6-conductor, 22 AWG tinned copper cable with semi-rigid PV...
  • 1331A — The Belden 1331A is a 16-pair 18AWG tinned copper fieldbus cable with polypropyl...
  • 8735 — The Belden 8735 is a 3-conductor, 22AWG tinned copper cable with PVC insulation,...
  • 2141A — The Belden 2141A is a Category 6A Premise Horizontal Cable (500 MHz) designed fo...
  • 58431 — The Belden 58431 is a plenum-rated, shielded 2-conductor 18 AWG bare copper cabl...
  • 78341 — The Belden 78341 ECOCABLE is a high-performance multi-conductor cable featuring...
  • 45293 — Belden part 45293 is an XTRAGUARD 4 cable containing 3 pairs of 20 AWG (7x28) st...
  • 5425 — The Belden 5425 is a multi-conductor, 18 AWG tinned copper cable with PVC insula...

1364A FAQ

What is 1364A?

1364A is a Bulk Wire Cable from Belden. The Belden 1364A is a 12-pair 16 AWG tinned copper fieldbus cable with polypropylene insulation, individual and overall Beldfoil shields, and an orange PVC outer jacket. It is designed for harsh environment digital and serial two-way communication, suitable for use in oil and gas extraction, petrochemical plants, Profibus, and Foundation FieldBus process automation.

Who manufactures 1364A?

1364A is manufactured by Belden.

Where can I download the 1364A datasheet PDF?

The 1364A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 1364A specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor12 pairs, 16 AWG (7x24) TC - Tinned Copper
Max. Current5.2 Amps per Conductor
Nom. Capacitance Cond-to-Shield45 pF/ft (150 pF/m)
Nom. Characteristic Impedance100 Ohm
Nom. Conductor DCR4.2 Ohm/1000ft (14 Ohm/km)
Nom. Outer Diameter1.105 in
Operating Temperature-40°C to +105°C
UL Voltage Rating300 V RMS