BeldenBulk Wire Cable

The Belden 28159A is a UL Type TC (1277) power and control cable with three 2 AWG (7x10) bare copper conductors and one 6 AWG (7x14) bare copper ground, PVC/nylon insulation, and a black PVC outer jacket. It is rated 600 V (TC-ER), 90 °C dry/wet, sunlight resistant, and suitable for direct burial and Class 1 Division 2 hazardous locations. A recommended cable gland is Belden BTC100A1041RA.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

28159A Key Specifications

Max current
130 Amps per Conductor at 30ºC (conductors); 78 Amps per Conductor at 25ºC (ground)
Voltage rating
600 V (TC-ER)
Temperature
90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
Conductor DCR
0.16 Ohm/1000ft (conductors); 0.4 Ohm/1000ft (1.3 Ohm/km) (ground)
Conductors / ground
3 conductors 2 AWG (7x10) BC; 1 ground 6 AWG (7x14) BC
Insulation
PVC/Nylon, 0.042 in (1.1 mm) nominal thickness, 0.367 in (9.32 mm) nominal insulation diameter
Mechanical
Bend radius 3.92 in (99.6 mm) stationary / 4.9 in (120 mm) installation; max pull tension 2671.7 lbs (1211.9 kg); weight 923 lbs/1000ft
Outer jacket
PVC, 0.083 in (2.1 mm), 0.987 in (25.1 mm) nominal diameter, ripcord yes

Characteristics (datasheet)

Voltage rating
600 V (TC-ER)
Conductors / ground
3 conductors 2 AWG (7x10) BC; 1 ground 6 AWG (7x14) BC
Insulation
PVC/Nylon, 0.042 in (1.1 mm) nominal thickness, 0.367 in (9.32 mm) nominal insulation diameter
Outer jacket
PVC, 0.083 in (2.1 mm), 0.987 in (25.1 mm) nominal diameter, ripcord yes
Temperature
90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
Max current
130 Amps per Conductor at 30ºC (conductors); 78 Amps per Conductor at 25ºC (ground)
Conductor DCR
0.16 Ohm/1000ft (conductors); 0.4 Ohm/1000ft (1.3 Ohm/km) (ground)
Mechanical
Bend radius 3.92 in (99.6 mm) stationary / 4.9 in (120 mm) installation; max pull tension 2671.7 lbs (1211.9 kg); weight 923 lbs/1000ft

28159A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 87503 — The Belden 87503 (Alpha Wire) is a 3-conductor, 14 AWG XTRAGUARD FLEX flexible t...
  • 7122W — The 7122W is a MachFlex™ high-flex cable featuring 2+1 conductors of 16 AWG bare...
  • 7447W — The Belden 7447W is a high-flex, 3-conductor plus ground, 10 AWG bare copper cab...
  • 28628A — Belden 28628A is a 50-conductor, 16 AWG (7x24 bare copper) UL Type TC power and...
  • 65409 — The Belden 65409 (Alpha Wire P/N 65409) is a flexible 9-conductor, 14 AWG contro...
  • 77031 — The Belden 77031 ECOCABLE is a 5-conductor, 16 AWG tinned copper cable with mPPE...
  • 934082100 — HIRSCHMANN TEST AND MEASUREMENT 934082100 Test Lead, 4mm Right Angle Banana...
  • 77249 — The Belden 77249 is a high-performance 4-conductor, 26 AWG tinned copper cable w...

More Bulk Wire Cable

  • 3306 — The Belden 3306 is a communication and control cable featuring 6 conductors of 2...
  • 2100A — The Belden 2100A is a fieldbus cable featuring one 18AWG tinned copper pair with...
  • 5421FE — The Belden 5421FE is a security and sound cable with three 20 AWG solid bare cop...
  • 5876 — The Belden 5876 is a single-conductor hook-up wire featuring a 20 AWG silver-pla...
  • 78048 — The Belden 78048 is an 8-conductor, 20 AWG tinned copper cable with modified pol...
  • 45064 — Belden 45064 is an XTRAGUARD 4 cable with four 18 AWG (16x30) tinned copper cond...
  • 22685D — Belden 22685D is a Canadian Instrumentation Cable (CIC) rated 300 V, built with...
  • 79042 — The Belden 79042 is a 4-conductor 10 AWG tinned copper cable with modified polyp...

28159A FAQ

What is 28159A?

28159A is a Bulk Wire Cable from Belden. The Belden 28159A is a UL Type TC (1277) power and control cable with three 2 AWG (7x10) bare copper conductors and one 6 AWG (7x14) bare copper ground, PVC/nylon insulation, and a black PVC outer jacket. It is rated 600 V (TC-ER), 90 °C dry/wet, sunlight resistant, and suitable for direct burial and Class 1 Division 2 hazardous locations. A recommended cable gland is Belden BTC100A1041RA.

Who manufactures 28159A?

28159A is manufactured by Belden.

Where can I download the 28159A datasheet PDF?

The 28159A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 28159A specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor DCR0.16 Ohm/1000ft (conductors); 0.4 Ohm/1000ft (1.3 Ohm/km) (ground)
Conductors / ground3 conductors 2 AWG (7x10) BC; 1 ground 6 AWG (7x14) BC
InsulationPVC/Nylon, 0.042 in (1.1 mm) nominal thickness, 0.367 in (9.32 mm) nominal insulation diameter
Max current130 Amps per Conductor at 30ºC (conductors); 78 Amps per Conductor at 25ºC (ground)
MechanicalBend radius 3.92 in (99.6 mm) stationary / 4.9 in (120 mm) installation; max pull tension 2671.7 lbs (1211.9 kg); weight 923 lbs/1000ft
Outer jacketPVC, 0.083 in (2.1 mm), 0.987 in (25.1 mm) nominal diameter, ripcord yes
Temperature90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
Voltage rating600 V (TC-ER)