28159A Datasheet
The Belden 28159A is a UL Type TC (1277) power and control cable with three 2 AWG (7x10) bare copper conductors and one 6 AWG (7x14) bare copper ground, PVC/nylon insulation, and a black PVC outer jacket. It is rated 600 V (TC-ER), 90 °C dry/wet, sunlight resistant, and suitable for direct burial and Class 1 Division 2 hazardous locations. A recommended cable gland is Belden BTC100A1041RA.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28159A Key Specifications
- Max current
- 130 Amps per Conductor at 30ºC (conductors); 78 Amps per Conductor at 25ºC (ground)
- Voltage rating
- 600 V (TC-ER)
- Temperature
- 90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
- Conductor DCR
- 0.16 Ohm/1000ft (conductors); 0.4 Ohm/1000ft (1.3 Ohm/km) (ground)
- Conductors / ground
- 3 conductors 2 AWG (7x10) BC; 1 ground 6 AWG (7x14) BC
- Insulation
- PVC/Nylon, 0.042 in (1.1 mm) nominal thickness, 0.367 in (9.32 mm) nominal insulation diameter
- Mechanical
- Bend radius 3.92 in (99.6 mm) stationary / 4.9 in (120 mm) installation; max pull tension 2671.7 lbs (1211.9 kg); weight 923 lbs/1000ft
- Outer jacket
- PVC, 0.083 in (2.1 mm), 0.987 in (25.1 mm) nominal diameter, ripcord yes
Characteristics (datasheet)
- Voltage rating
- 600 V (TC-ER)
- Conductors / ground
- 3 conductors 2 AWG (7x10) BC; 1 ground 6 AWG (7x14) BC
- Insulation
- PVC/Nylon, 0.042 in (1.1 mm) nominal thickness, 0.367 in (9.32 mm) nominal insulation diameter
- Outer jacket
- PVC, 0.083 in (2.1 mm), 0.987 in (25.1 mm) nominal diameter, ripcord yes
- Temperature
- 90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
- Max current
- 130 Amps per Conductor at 30ºC (conductors); 78 Amps per Conductor at 25ºC (ground)
- Conductor DCR
- 0.16 Ohm/1000ft (conductors); 0.4 Ohm/1000ft (1.3 Ohm/km) (ground)
- Mechanical
- Bend radius 3.92 in (99.6 mm) stationary / 4.9 in (120 mm) installation; max pull tension 2671.7 lbs (1211.9 kg); weight 923 lbs/1000ft
28159A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 87503 — The Belden 87503 (Alpha Wire) is a 3-conductor, 14 AWG XTRAGUARD FLEX flexible t...
- 7122W — The 7122W is a MachFlex™ high-flex cable featuring 2+1 conductors of 16 AWG bare...
- 7447W — The Belden 7447W is a high-flex, 3-conductor plus ground, 10 AWG bare copper cab...
- 28628A — Belden 28628A is a 50-conductor, 16 AWG (7x24 bare copper) UL Type TC power and...
- 65409 — The Belden 65409 (Alpha Wire P/N 65409) is a flexible 9-conductor, 14 AWG contro...
- 77031 — The Belden 77031 ECOCABLE is a 5-conductor, 16 AWG tinned copper cable with mPPE...
- 934082100 — HIRSCHMANN TEST AND MEASUREMENT 934082100 Test Lead, 4mm Right Angle Banana...
- 77249 — The Belden 77249 is a high-performance 4-conductor, 26 AWG tinned copper cable w...
More Bulk Wire Cable
- 3306 — The Belden 3306 is a communication and control cable featuring 6 conductors of 2...
- 2100A — The Belden 2100A is a fieldbus cable featuring one 18AWG tinned copper pair with...
- 5421FE — The Belden 5421FE is a security and sound cable with three 20 AWG solid bare cop...
- 5876 — The Belden 5876 is a single-conductor hook-up wire featuring a 20 AWG silver-pla...
- 78048 — The Belden 78048 is an 8-conductor, 20 AWG tinned copper cable with modified pol...
- 45064 — Belden 45064 is an XTRAGUARD 4 cable with four 18 AWG (16x30) tinned copper cond...
- 22685D — Belden 22685D is a Canadian Instrumentation Cable (CIC) rated 300 V, built with...
- 79042 — The Belden 79042 is a 4-conductor 10 AWG tinned copper cable with modified polyp...
28159A FAQ
What is 28159A?
28159A is a Bulk Wire Cable from Belden. The Belden 28159A is a UL Type TC (1277) power and control cable with three 2 AWG (7x10) bare copper conductors and one 6 AWG (7x14) bare copper ground, PVC/nylon insulation, and a black PVC outer jacket. It is rated 600 V (TC-ER), 90 °C dry/wet, sunlight resistant, and suitable for direct burial and Class 1 Division 2 hazardous locations. A recommended cable gland is Belden BTC100A1041RA.
Who manufactures 28159A?
28159A is manufactured by Belden.
Where can I download the 28159A datasheet PDF?
The 28159A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28159A specifications
Click to ask a quick question:
Parameters
| Conductor DCR | 0.16 Ohm/1000ft (conductors); 0.4 Ohm/1000ft (1.3 Ohm/km) (ground) |
| Conductors / ground | 3 conductors 2 AWG (7x10) BC; 1 ground 6 AWG (7x14) BC |
| Insulation | PVC/Nylon, 0.042 in (1.1 mm) nominal thickness, 0.367 in (9.32 mm) nominal insulation diameter |
| Max current | 130 Amps per Conductor at 30ºC (conductors); 78 Amps per Conductor at 25ºC (ground) |
| Mechanical | Bend radius 3.92 in (99.6 mm) stationary / 4.9 in (120 mm) installation; max pull tension 2671.7 lbs (1211.9 kg); weight 923 lbs/1000ft |
| Outer jacket | PVC, 0.083 in (2.1 mm), 0.987 in (25.1 mm) nominal diameter, ripcord yes |
| Temperature | 90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C |
| Voltage rating | 600 V (TC-ER) |