27159A Datasheet

BeldenBulk Wire Cable

Belden 27159A is a UL Type TC power and control cable with three 2 AWG bare copper conductors plus one 6 AWG bare copper ground wire. It has PVC/nylon insulation, a black PVC outer jacket, and is rated 600 V, 90 °C dry / 75 °C wet, with sunlight resistance and direct burial approval. It is suitable for power and control applications up to 600 V and Class 1 Division 2 hazardous locations.{

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

27159A Key Specifications

Max. Current
130 Amps per Conductor at 30ºC; Ground Wire 78 Amps per Conductor at 25ºC
UL Voltage Rating
600 V
Operating Temperature
-30°C To +75°C Wet/90°C Dry
UL Temperature
90°C Dry, 75°C Wet
Bulk Cable Weight
942 lbs/1000ft
Conductors
3 x 2 AWG bare copper, 7x10 stranding
Ground Wire
1 x 6 AWG bare copper, 7x14 stranding
Max. Pull Tension
2781.7 lbs (1261.8 kg)

Characteristics (datasheet)

UL Voltage Rating
600 V
UL Temperature
90°C Dry, 75°C Wet
Operating Temperature
-30°C To +75°C Wet/90°C Dry
Conductors
3 x 2 AWG bare copper, 7x10 stranding
Ground Wire
1 x 6 AWG bare copper, 7x14 stranding
Max. Current
130 Amps per Conductor at 30ºC; Ground Wire 78 Amps per Conductor at 25ºC
Nom. Conductor DCR
0.166 Ohm/1000ft
Overall Cable Diameter (Nominal)
0.987 in
Max. Pull Tension
2781.7 lbs (1261.8 kg)
Bulk Cable Weight
942 lbs/1000ft

27159A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 78140 — The Belden 78140 is a 10-conductor, 22 AWG tinned copper cable with modified pol...
  • 74043E — The Belden 74043E is an industrial-grade DataTuff Single Pair Ethernet (SPE) cab...
  • 21581 — Belden 21581 is a CSA Type TC-CIC tray cable rated 600 V, containing 33 conducto...
  • 8847MN — The Belden 8847MN is a SpaceMaker™ multi-conductor cable featuring 9 conductors...
  • 6545FE — The Belden 6545FE is a plenum-rated (CMP) indoor security and sound cable design...
  • 8632MN — The 8632MN is a SpaceMaker™ 15-conductor 16 AWG tinned copper cable with polypro...
  • 2101A — The Belden 2101A is a 2-pair 18AWG tinned copper fieldbus cable with XLPO insula...
  • 29540 — Belden 29540 is a flexible 3-conductor-plus-ground VFD motor supply cable built...

More Bulk Wire Cable

  • 70009PU — The Belden 70009PU is a DataTuff® 5E PROFINET Type C industrial Ethernet cable d...
  • 1858A — The Belden 1858A is an RG11-type video triax cable featuring a 15 AWG stranded b...
  • 85805 — The 85805 is an XTRAGUARD FLEX continuous flex control cable with 5 bare copper...
  • 78454 — The Belden 78454 is a highly flexible 25-conductor, 22 AWG tinned copper cable w...
  • 70100E — The Belden 70100E is a Profibus PA cable designed for instrumentation and data t...
  • 83562 — The Belden 83562 is a high-temperature, shielded multi-conductor cable featuring...
  • 4813 — The Belden 4813 is a discontinued Category 6+ enhanced premise horizontal cable...
  • 77056 — The Belden 77056 is a 2-conductor 20 AWG tinned copper cable featuring mPPE insu...

27159A FAQ

What is 27159A?

27159A is a Bulk Wire Cable from Belden. Belden 27159A is a UL Type TC power and control cable with three 2 AWG bare copper conductors plus one 6 AWG bare copper ground wire. It has PVC/nylon insulation, a black PVC outer jacket, and is rated 600 V, 90 °C dry / 75 °C wet, with sunlight resistance and direct burial approval. It is suitable for power and control applications up to 600 V and Class 1 Division 2 hazardous locations.{.

Who manufactures 27159A?

27159A is manufactured by Belden.

Where can I download the 27159A datasheet PDF?

The 27159A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 27159A specifications

AI Powered

Click to ask a quick question:

Parameters

Bulk Cable Weight942 lbs/1000ft
Conductors3 x 2 AWG bare copper, 7x10 stranding
Ground Wire1 x 6 AWG bare copper, 7x14 stranding
Max. Current130 Amps per Conductor at 30ºC; Ground Wire 78 Amps per Conductor at 25ºC
Max. Pull Tension2781.7 lbs (1261.8 kg)
Nom. Conductor DCR0.166 Ohm/1000ft
Operating Temperature-30°C To +75°C Wet/90°C Dry
Overall Cable Diameter (Nominal)0.987 in
UL Temperature90°C Dry, 75°C Wet
UL Voltage Rating600 V