27152A Datasheet

BeldenBulk Wire Cable

The Belden 27152A is a UL Type TC power and control cable with two 6 AWG bare copper conductors and one 8 AWG bare copper ground wire, insulated with PVC/nylon and jacketed in black PVC. It is rated for 600 V and 90 °C dry / 75 °C wet operation and is suitable for indoor, outdoor, sunlight-resistant, and direct burial installations, including Class 1 Division 2 hazardous locations. The cable has no outer shield and includes a ripcord in the jacket.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

27152A Key Specifications

Conductor DCR and current rating
0.42 Ohm/1000ft; 75 Amps per Conductor at 30ºC
Ground wire DCR and current rating
0.67 Ohm/1000ft (2.2 Ohm/km); 55 Amps per Conductor at 30ºC
UL voltage rating
600 V
Temperature rating
90°C Dry, 75°C Wet; Wet/Dry: -30°C To 90°C
Conductor / ground wire size and stranding
2 conductors 6 AWG 7x14 bare copper; 1 ground wire 8 AWG 7x16 bare copper
Insulation material and thickness
PVC/Nylon; 0.035 in (0.89 mm) nominal thickness
Jacket material, thickness, and overall diameter
Black PVC; 0.063 in (1.6 mm) nominal thickness; 0.630 in overall diameter
Max pull tension and bulk weight
914 lbs (415 kg); 316 lbs/1000ft

Characteristics (datasheet)

Conductor / ground wire size and stranding
2 conductors 6 AWG 7x14 bare copper; 1 ground wire 8 AWG 7x16 bare copper
Insulation material and thickness
PVC/Nylon; 0.035 in (0.89 mm) nominal thickness
Jacket material, thickness, and overall diameter
Black PVC; 0.063 in (1.6 mm) nominal thickness; 0.630 in overall diameter
UL voltage rating
600 V
Temperature rating
90°C Dry, 75°C Wet; Wet/Dry: -30°C To 90°C
Conductor DCR and current rating
0.42 Ohm/1000ft; 75 Amps per Conductor at 30ºC
Ground wire DCR and current rating
0.67 Ohm/1000ft (2.2 Ohm/km); 55 Amps per Conductor at 30ºC
Max pull tension and bulk weight
914 lbs (415 kg); 316 lbs/1000ft

27152A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 9159 — The Belden 9159 is a 5-pair 18 AWG tinned copper electronic cable with PVC insul...
  • 29726C — The Belden 29726C is a 3-conductor VFD power cable using 4 AWG (7x12) bare coppe...
  • 77211 — The Belden 77211 is a multi-conductor ECOCABLE featuring 12 conductors of 20 AWG...
  • 86603CY — The Belden 86603CY is an XTRAGUARD FLEX continuous flex data cable with three 24...
  • 1852 — The Belden 1852 is a single-conductor 28 AWG tinned copper hook-up wire with PVC...
  • 80135 — The Belden 80135 (ECOFLEX PUR) is a 5-conductor, 18 AWG stranded tinned copper c...
  • 5021C — The Belden 5021C is a XTRAGUARD 1, single-pair 22 AWG stranded tinned copper cab...
  • 79009FF — The Belden 79009FF is a Safe-T-Line fire-resistant multi-conductor cable featuri...

More Bulk Wire Cable

  • 58124 — The Belden 58124 is a plenum-rated communication and control cable featuring fou...
  • 65825 — The Belden 65825 is a 25-conductor, 18 AWG bare copper XTRAGUARD FLEX flexible c...
  • 8333 — The Belden 8333 is a computer EIA RS-232 cable featuring 3 pairs of 24 AWG stran...
  • 76104WS — The 76104WS is a MachFlex™ high-flex 4-conductor 26 AWG tinned copper cable with...
  • 8208 — The Belden 8208 is a 2-conductor 18 AWG tinned copper cable with EPDM insulation...
  • 78341 — The Belden 78341 ECOCABLE is a high-performance multi-conductor cable featuring...
  • 1037A — The 1037A is a black-jacketed instrumentation cable designed for industrial cont...
  • 9489 — The Belden 9489 is a high-performance instrumentation cable featuring one pair o...

27152A FAQ

What is 27152A?

27152A is a Bulk Wire Cable from Belden. The Belden 27152A is a UL Type TC power and control cable with two 6 AWG bare copper conductors and one 8 AWG bare copper ground wire, insulated with PVC/nylon and jacketed in black PVC. It is rated for 600 V and 90 °C dry / 75 °C wet operation and is suitable for indoor, outdoor, sunlight-resistant, and direct burial installations, including Class 1 Division 2 hazardous locations. The cable has no outer shield and includes a ripcord in the jacket.

Who manufactures 27152A?

27152A is manufactured by Belden.

Where can I download the 27152A datasheet PDF?

The 27152A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 27152A specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor DCR and current rating0.42 Ohm/1000ft; 75 Amps per Conductor at 30ºC
Conductor / ground wire size and stranding2 conductors 6 AWG 7x14 bare copper; 1 ground wire 8 AWG 7x16 bare copper
Ground wire DCR and current rating0.67 Ohm/1000ft (2.2 Ohm/km); 55 Amps per Conductor at 30ºC
Insulation material and thicknessPVC/Nylon; 0.035 in (0.89 mm) nominal thickness
Jacket material, thickness, and overall diameterBlack PVC; 0.063 in (1.6 mm) nominal thickness; 0.630 in overall diameter
Max pull tension and bulk weight914 lbs (415 kg); 316 lbs/1000ft
Temperature rating90°C Dry, 75°C Wet; Wet/Dry: -30°C To 90°C
UL voltage rating600 V