24505D Datasheet

BeldenBulk Wire Cable

Belden 24505D is a Canadian TC-ACIC 600 V instrumentation cable containing 2 pairs of 16 AWG (7x24) stranded tinned copper conductors with XLPE insulation, individual and overall Beldfoil shielding, a PVC inner jacket, aluminum interlock armor, and a PVC outer jacket. It is rated for -40 °C to 90 °C wet / 105 °C dry service, is sunlight resistant, and is intended for industrial control, raceways, cable trays and ducts, digital control, instrument and process control circuits.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

24505D Key Specifications

Max Current
15.2 Amps per Conductor at 30ºC
Voltage Rating
600 V
Operating Temperature
-40°C To +90°C Wet / 105°C Dry
Conductor
2 Pair 16 AWG 7x24 Tinned Copper
Insulation
XLPE, 0.030 in (0.76 mm) nominal thickness
Max Pull Tension
401 lbs (182 kg)
Nominal Conductor DCR
4.6 Ohm/1000ft
Overall Cable Diameter
0.911 in

Characteristics (datasheet)

Voltage Rating
600 V
Conductor
2 Pair 16 AWG 7x24 Tinned Copper
Insulation
XLPE, 0.030 in (0.76 mm) nominal thickness
Operating Temperature
-40°C To +90°C Wet / 105°C Dry
Nominal Conductor DCR
4.6 Ohm/1000ft
Max Current
15.2 Amps per Conductor at 30ºC
Max Pull Tension
401 lbs (182 kg)
Overall Cable Diameter
0.911 in

24505D Applications

  • Industrial Control
  • Raceways
  • Cable trays and ducts
  • Digital Control
  • Instruments (4-20ma, 0-10v)
  • Low voltage digital control (24v)
  • Encoders
  • Control circuits
  • Distributed control system (DCS)
  • Programmable logic controller (PLC)
  • Solenoids
  • Valves
  • Actuators
  • Positioners

Other Belden parts

  • 85607 — The Belden 85607 is an XTRAGUARD FLEX continuous flex control cable featuring se...
  • 1590 — The Belden 1590 is a heavy-duty TW-75 600V bulk cable featuring a single 1 AWG 1...
  • 5937 — The Belden 5937 is an XTRAGUARD 1 shielded cable consisting of eight 28 AWG tinn...
  • 975163103 — 1kV 10A Copper-Gold Plug Connector
  • 77233 — The Belden 77233 is a 4-conductor 14 AWG tinned copper cable with mPPE insulatio...
  • 6307 — The Belden 6307 is a multi-conductor communication and control cable with 15 con...
  • 5220C — The Belden 5220C is a multi-conductor shielded/unshielded control cable featurin...
  • 1175A — The Belden 1175A is a shielded, single-pair cable designed for T1/DS1 central of...

More Bulk Wire Cable

  • 6301FE — The Belden 6301FE is a plenum-rated CMP security and commercial audio cable feat...
  • 29532 — Belden 29532 is a flexible 600/1000 V VFD motor supply cable with three 4/0 AWG...
  • 3220 — The Belden 3220 is a single-conductor communication and control cable designed f...
  • 85204 — The Belden 85204 is an XTRAGUARD FLEX continuous flex control cable featuring 4...
  • 79104 — The Belden 79104 is a 5-conductor, 20 AWG tinned copper cable with mPPE insulati...
  • 9898 — The Belden 9898 is an IEEE 802.3 Ethernet transceiver cable designed for 10BASE5...
  • 78122 — The Belden 78122 is a shielded multi-conductor cable (ECOCABLE) consisting of tw...
  • 77031 — The Belden 77031 ECOCABLE is a 5-conductor, 16 AWG tinned copper cable with mPPE...

24505D FAQ

What is 24505D?

24505D is a Bulk Wire Cable from Belden. Belden 24505D is a Canadian TC-ACIC 600 V instrumentation cable containing 2 pairs of 16 AWG (7x24) stranded tinned copper conductors with XLPE insulation, individual and overall Beldfoil shielding, a PVC inner jacket, aluminum interlock armor, and a PVC outer jacket. It is rated for -40 °C to 90 °C wet / 105 °C dry service, is sunlight resistant, and is intended for industrial control, raceways, cable trays and ducts, digital control, instrument and process control circuits.

Who manufactures 24505D?

24505D is manufactured by Belden.

Where can I download the 24505D datasheet PDF?

The 24505D datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 24505D specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor2 Pair 16 AWG 7x24 Tinned Copper
InsulationXLPE, 0.030 in (0.76 mm) nominal thickness
Max Current15.2 Amps per Conductor at 30ºC
Max Pull Tension401 lbs (182 kg)
Nominal Conductor DCR4.6 Ohm/1000ft
Operating Temperature-40°C To +90°C Wet / 105°C Dry
Overall Cable Diameter0.911 in
Voltage Rating600 V