21672 Datasheet
The Belden 21672 is a CSA Type TC-CIC 600 V tray cable with three 2/0 AWG bare copper conductors and one 6 AWG bare copper ground conductor. It has XLPE/XLPE-type insulation, a black PVC outer jacket with ripcord, and is rated 90 °C dry/wet for indoor/outdoor direct burial use in CEC power and control applications. It complies with TC/CIC standards, FT4 flammability, and RoHS/WEEE/China RoHS II directives.{
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
21672 Key Specifications
- Max. Current
- 195 Amps per Conductor at 30ºC
- Voltage Rating
- 600 V (CSA TC); UL Voltage Rating 600 V
- Temperature Rating
- 90°C Dry, 90°C Wet; Operating Wet/Dry: -40°C to 90°C
- Bulk Cable Weight
- 1731 lbs/1000ft (2576 kg/km)
- Conductors
- 3 x 2/0 AWG bare copper, 19x11.5 stranding; Ground 1 x 6 AWG bare copper, 7x14 stranding
- Insulation
- XLP, XLPO, XLPE (Thermoset), 0.0550 in (1.40 mm) nominal thickness
- Nom. Conductor DCR
- 1.6 Ohm/1000ft (5.2 Ohm/km)
- Outer Jacket
- PVC - Polyvinyl Chloride, 0.095 in (2.4 mm) nominal thickness, 1.271 in (32.28 mm) nominal diameter, ripcord Yes
Characteristics (datasheet)
- Voltage Rating
- 600 V (CSA TC); UL Voltage Rating 600 V
- Conductors
- 3 x 2/0 AWG bare copper, 19x11.5 stranding; Ground 1 x 6 AWG bare copper, 7x14 stranding
- Max. Current
- 195 Amps per Conductor at 30ºC
- Nom. Conductor DCR
- 1.6 Ohm/1000ft (5.2 Ohm/km)
- Temperature Rating
- 90°C Dry, 90°C Wet; Operating Wet/Dry: -40°C to 90°C
- Insulation
- XLP, XLPO, XLPE (Thermoset), 0.0550 in (1.40 mm) nominal thickness
- Outer Jacket
- PVC - Polyvinyl Chloride, 0.095 in (2.4 mm) nominal thickness, 1.271 in (32.28 mm) nominal diameter, ripcord Yes
- Bulk Cable Weight
- 1731 lbs/1000ft (2576 kg/km)
21672 Applications
- CEC Power and Control Applications
Other Belden parts
- 74043E — The Belden 74043E is an industrial-grade DataTuff Single Pair Ethernet (SPE) cab...
- 9913 — The Belden 9913 is a 50 Ohm wireless transmission coaxial cable of RG-8 type, co...
- 9855 — The Belden 9855 is a computer POS cable with 22 AWG solid tinned copper conducto...
- 5667 — The Belden 5667 is a multi-conductor cable featuring three 26 AWG stranded tinne...
- 1091A — The Belden 1091A is a multi-conductor instrumentation cable featuring 20 pairs o...
- 9825 — The Belden 9825 is a 25-pair computer EIA RS-232/422 cable with 28 AWG stranded...
- 82742 — The Belden 82742 is a high-temperature electronic cable featuring three pairs of...
- 6356 — The Belden 6356 is an 8-conductor, 24 AWG tinned copper communication and contro...
More Bulk Wire Cable
- 26320FL — Belden 26320FL is an armored plenum-rated fire alarm cable (FPLP) with two 18 AW...
- 8908 — The Belden 8908 is a low-temp plastic lead wire with an 8 AWG tinned copper cond...
- 6335 — The Belden 6335 is a multi-conductor communication and control cable featuring 1...
- 1040A — The Belden 1040A is a UL-listed instrumentation cable consisting of 6 pairs of 1...
- 82444 — The Belden 82444 is a 4-conductor, 22 AWG (7x30 stranded) tinned copper electron...
- 3042A — The Belden 3042A is a 50-pair instrumentation cable featuring 18 AWG pairs and a...
- 8619 — The Belden 8619 is a 19-conductor 18 AWG tinned copper cable with PVC insulation...
- 28090A — The Belden 28090A is a UL Type TC (1277) power and control cable with 12 conduct...
21672 FAQ
What is 21672?
21672 is a Bulk Wire Cable from Belden. The Belden 21672 is a CSA Type TC-CIC 600 V tray cable with three 2/0 AWG bare copper conductors and one 6 AWG bare copper ground conductor. It has XLPE/XLPE-type insulation, a black PVC outer jacket with ripcord, and is rated 90 °C dry/wet for indoor/outdoor direct burial use in CEC power and control applications. It complies with TC/CIC standards, FT4 flammability, and RoHS/WEEE/China RoHS II directives.{.
Who manufactures 21672?
21672 is manufactured by Belden.
Where can I download the 21672 datasheet PDF?
The 21672 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 21672 specifications
Click to ask a quick question:
Parameters
| Bulk Cable Weight | 1731 lbs/1000ft (2576 kg/km) |
| Conductors | 3 x 2/0 AWG bare copper, 19x11.5 stranding; Ground 1 x 6 AWG bare copper, 7x14 stranding |
| Insulation | XLP, XLPO, XLPE (Thermoset), 0.0550 in (1.40 mm) nominal thickness |
| Max. Current | 195 Amps per Conductor at 30ºC |
| Nom. Conductor DCR | 1.6 Ohm/1000ft (5.2 Ohm/km) |
| Outer Jacket | PVC - Polyvinyl Chloride, 0.095 in (2.4 mm) nominal thickness, 1.271 in (32.28 mm) nominal diameter, ripcord Yes |
| Temperature Rating | 90°C Dry, 90°C Wet; Operating Wet/Dry: -40°C to 90°C |
| Voltage Rating | 600 V (CSA TC); UL Voltage Rating 600 V |