45062 Datasheet
Belden part 45062 is an XTRAGUARD 4 cable containing 2 conductors of 18 AWG (16x30) tinned copper with TPE insulation and a slate TPE outer jacket. It is rated 300 V for PLTC and AWM 21916 applications and is intended for data, communication, audio, low-level signal transmission, industrial networking, serial communication, control panels, automation equipment, and instrumentation systems. The cable has a nominal overall diameter of 0.252 in (6.40 mm), operates from -50°C to +125°C, and includes a ripcord.}
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
45062 Key Specifications
- Nominal capacitance cond-to-cond
- 17 pF/ft (56 pF/m)
- Nominal inductance
- 0.18 µH/ft (0.59 µH/m)
- Voltage rating
- 300 V (PLTC, AWM 21916); 300 V (CSA AWM)
- Operating temperature
- -50°C To +125°C (UL Temperature 125°C)
- Conductor
- 2 Conductors, 18 AWG 16x30 TC - Tinned Copper
- Max pull tension
- 17.6 lbs (7.98 kg)
- Nominal characteristic impedance
- 90 Ohm
- Overall cable diameter
- 0.252 in (6.40 mm)
Characteristics (datasheet)
- Conductor
- 2 Conductors, 18 AWG 16x30 TC - Tinned Copper
- Voltage rating
- 300 V (PLTC, AWM 21916); 300 V (CSA AWM)
- Operating temperature
- -50°C To +125°C (UL Temperature 125°C)
- Nominal capacitance cond-to-cond
- 17 pF/ft (56 pF/m)
- Nominal characteristic impedance
- 90 Ohm
- Nominal inductance
- 0.18 µH/ft (0.59 µH/m)
- Overall cable diameter
- 0.252 in (6.40 mm)
- Max pull tension
- 17.6 lbs (7.98 kg)
45062 Applications
- Data, communication, audio, and low-level signal transmission
- Industrial networking
- Serial communication
- Control panels
- Automation equipment
- Instrumentation systems
Other Belden parts
- 5125C — The Belden 5125C is a multi-conductor shielded cable containing 5 pairs of 22 AW...
- 8635MN — The Belden 8635MN is a SpaceMaker™ 5-conductor cable built with 24AWG tinned cop...
- 28088A — The Belden 28088A is a UL Type TC power and control cable with 10 conductors of...
- 6157 — The Belden 6157 is a heavy-duty Teck90 1000V cable featuring four 2/0 AWG bare c...
- 77020 — The Belden 77020 is an ECOCABLE featuring two 18 AWG stranded tinned copper cond...
- 7130 — The Belden 7130 is a single-conductor hook-up wire featuring a 24 AWG tinned cop...
- 934059103 — Yellow 60V 32A Test Probe, 250mm Leads, -15°C to 70°C
- 30812 — The Belden 30812 is a 12 AWG stranded tinned copper lead wire with silicone rubb...
More Bulk Wire Cable
- 27110AS — The Belden 27110AS is a 3-conductor, 12 AWG (7x20) bare copper tray cable with P...
- 7035 — The Belden 7035 is a single-conductor hook-up wire featuring 14 AWG tinned coppe...
- 8332 — The Belden 8332 is a computer EIA RS-232 cable designed for extended distance ap...
- 6455 — The Belden 6455 is a 2-pair, 22 AWG tinned copper cable with foam HDPE insulatio...
- 6357 — The Belden 6357 is a 9-conductor, 24 AWG tinned copper communication and control...
- 9890 — The Belden 9890 is a 10-conductor electronic cable featuring 20 AWG solid tinned...
- 7969A — The Belden 7969A is an Industrial Ethernet Category 6 cable featuring four bonde...
- 78355 — The Belden 78355 is a 15-conductor, 20 AWG tinned copper cable with modified pol...
45062 FAQ
What is 45062?
45062 is a Bulk Wire Cable from Belden. Belden part 45062 is an XTRAGUARD 4 cable containing 2 conductors of 18 AWG (16x30) tinned copper with TPE insulation and a slate TPE outer jacket. It is rated 300 V for PLTC and AWM 21916 applications and is intended for data, communication, audio, low-level signal transmission, industrial networking, serial communication, control panels, automation equipment, and instrumentation systems. The cable has a nominal overall diameter of 0.252 in (6.40 mm), operates from -50°C to +125°C, and includes a ripcord.}.
Who manufactures 45062?
45062 is manufactured by Belden.
Where can I download the 45062 datasheet PDF?
The 45062 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 45062 specifications
Click to ask a quick question:
Parameters
| Conductor | 2 Conductors, 18 AWG 16x30 TC - Tinned Copper |
| Max pull tension | 17.6 lbs (7.98 kg) |
| Nominal capacitance cond-to-cond | 17 pF/ft (56 pF/m) |
| Nominal characteristic impedance | 90 Ohm |
| Nominal inductance | 0.18 µH/ft (0.59 µH/m) |
| Operating temperature | -50°C To +125°C (UL Temperature 125°C) |
| Overall cable diameter | 0.252 in (6.40 mm) |
| Voltage rating | 300 V (PLTC, AWM 21916); 300 V (CSA AWM) |