9962 Datasheet
The Belden 9962 is a 2-conductor, 20 AWG tinned copper electronic cable with PVC-nylon insulation, a 90% overall tinned copper braid shield, and a PVC outer jacket. It is designed for indoor use and is suitable for MIL-W-16878 (Type B) specifications, supporting up to 600V analog signals and up to 600V voltage control. The cable features a nominal diameter of 0.192 in (4.88 mm), an operating temperature range of -20°C to +105°C, and a maximum current capacity of 3.8 Amps per conductor at 25°C.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
9962 Key Specifications
- Max. Current
- 3.8 Amps per Conductor at 25ºC
- Nom. Capacitance Cond-to-Cond
- 53 pF/ft (170 pF/m)
- Nom. Capacitance Cond-to-Other (Conds + Shield)
- 91 pF/ft (300 pF/m)
- Nom. Inductance
- 0.134 µH/ft (0.440 µH/m)
- Voltage Rating
- 600 V
- UL Temperature / Operating Temperature
- 105°C / -20°C to +105°C
- Bend Radius (Stationary Min. / Installation Min.)
- 1.9 in (48 mm) / 1.9 in (48 mm)
- Bulk Cable Weight
- 22 lbs/1000ft (33 kg/km)
Characteristics (datasheet)
- Conductor configuration
- 2 conductors, 20 AWG, 19x32 stranding, Tinned Copper (TC)
- Insulation material
- PVC/Nylon - Polyvinyl Chloride + Nylon, nominal thickness 0.011 in (0.28 mm), color code White, Black
- Outer Shield
- Braid, Tinned Copper (TC), 90% coverage
- Outer Jacket
- PVC - Polyvinyl Chloride, nominal thickness 0.016 in (0.41 mm), nominal diameter 0.192 in (4.88 mm)
- Overall Cable Diameter (Nominal)
- 0.192 in (4.88 mm)
- Voltage Rating
- 600 V
- Max. Current
- 3.8 Amps per Conductor at 25ºC
- Nom. Conductor DCR
- 9.1 Ohm/1000ft (30 Ohm/km)
- Nom. Capacitance Cond-to-Cond
- 53 pF/ft (170 pF/m)
- Nom. Capacitance Cond-to-Other (Conds + Shield)
- 91 pF/ft (300 pF/m)
- Nom. Inductance
- 0.134 µH/ft (0.440 µH/m)
- Nom Outer Shield DCR
- 6.8 Ohm/1000ft (22 Ohm/km)
- UL Temperature / Operating Temperature
- 105°C / -20°C to +105°C
- Bend Radius (Stationary Min. / Installation Min.)
- 1.9 in (48 mm) / 1.9 in (48 mm)
- Max. Pull Tension
- 30 lbs (14 kg)
- Bulk Cable Weight
- 22 lbs/1000ft (33 kg/km)
9962 Applications
- MIL-W-16878 (Type B) Spec
- up to 600V analog signals
- up to 600V voltage control
Other Belden parts
- 4100FE — The Belden 4100FE is a security and commercial audio cable featuring two 14 AWG...
- 74030E — The Belden 74030E is a DataTuff industrial single-pair Ethernet (SPE) cable with...
- 28611A — The Belden 28611A is a 25-conductor Type TC power and control cable with 18 AWG...
- 77137 — The Belden 77137 is a 7-conductor, 16 AWG tinned copper ECOCABLE with MPPE insul...
- 78002 — The Belden 78002 is a 2-conductor 28 AWG tinned copper ECOCABLE with modified po...
- 2401C — The Belden 2401C is a 2-conductor, 22 AWG tinned copper communication and contro...
- 1116A — The Belden 1116A is a Type KX thermocouple cable featuring a single pair of 16 A...
- 6213C — The Belden 6213C is a communication and control cable featuring three pairs of 2...
More Bulk Wire Cable
- 7133 — The Belden 7133 is a single-conductor 18 AWG tinned copper hook-up wire with irr...
- 25100UE — The Belden 25100UE is an armored security and commercial audio cable with two 14...
- 50094LS — The Belden 50094LS is an RS-485 cable consisting of 4 pairs of 22 AWG stranded t...
- 78134 — The Belden 78134 is a 4-conductor 22 AWG stranded tinned copper ECOCABLE featuri...
- 79120 — The Belden 79120 is a multi-conductor shielded cable featuring seven 16 AWG stra...
- 80152 — The Belden 80152 is a zero-halogen, 5-conductor 14 AWG tinned copper cable with...
- 1068A — The Belden 1068A is a 24-pair, 18 AWG bare copper instrumentation cable with PVC...
- 1499A — The Belden 1499A is a multi-pair instrumentation and control cable consisting of...
9962 FAQ
What is 9962?
9962 is a Bulk Wire Cable from Belden. The Belden 9962 is a 2-conductor, 20 AWG tinned copper electronic cable with PVC-nylon insulation, a 90% overall tinned copper braid shield, and a PVC outer jacket. It is designed for indoor use and is suitable for MIL-W-16878 (Type B) specifications, supporting up to 600V analog signals and up to 600V voltage control. The cable features a nominal diameter of 0.192 in (4.88 mm), an operating temperature range of -20°C to +105°C, and a maximum current capacity of 3.8 Amps per conductor at 25°C.
Who manufactures 9962?
9962 is manufactured by Belden.
Where can I download the 9962 datasheet PDF?
The 9962 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 9962 specifications
Click to ask a quick question:
Parameters
| Bend Radius (Stationary Min. / Installation Min.) | 1.9 in (48 mm) / 1.9 in (48 mm) |
| Bulk Cable Weight | 22 lbs/1000ft (33 kg/km) |
| Conductor configuration | 2 conductors, 20 AWG, 19x32 stranding, Tinned Copper (TC) |
| Insulation material | PVC/Nylon - Polyvinyl Chloride + Nylon, nominal thickness 0.011 in (0.28 mm), color code White, Black |
| Max. Current | 3.8 Amps per Conductor at 25ºC |
| Max. Pull Tension | 30 lbs (14 kg) |
| Nom. Capacitance Cond-to-Cond | 53 pF/ft (170 pF/m) |
| Nom. Capacitance Cond-to-Other (Conds + Shield) | 91 pF/ft (300 pF/m) |
| Nom. Conductor DCR | 9.1 Ohm/1000ft (30 Ohm/km) |
| Nom. Inductance | 0.134 µH/ft (0.440 µH/m) |
| Nom Outer Shield DCR | 6.8 Ohm/1000ft (22 Ohm/km) |
| Outer Jacket | PVC - Polyvinyl Chloride, nominal thickness 0.016 in (0.41 mm), nominal diameter 0.192 in (4.88 mm) |
| Outer Shield | Braid, Tinned Copper (TC), 90% coverage |
| Overall Cable Diameter (Nominal) | 0.192 in (4.88 mm) |
| UL Temperature / Operating Temperature | 105°C / -20°C to +105°C |
| Voltage Rating | 600 V |