29529 Datasheet

BeldenBulk Wire Cable

Belden part 29529 is a flexible motor supply cable built for Variable Frequency Drives (VFD) and AC motor and drive systems, including Class 1 Division 2 hazardous locations. It contains three 1/0 AWG tinned copper conductors with XLPE insulation plus a symmetrical segmented bare copper ground, an overall dual copper tape shield, and a black PVC jacket rated 600/1000 V TC-ER.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

29529 Key Specifications

Max current
170 Amps per Conductor at 30ºC
Nom. capacitance cond-to-cond
37 pF/ft (120 pF/m)
Voltage rating
1000 V (TC, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC)
Temperature rating
90°C Dry, 90°C Wet; Operating -40°C To +90°C
Bulk cable weight
1708 lbs/1000ft (2542 kg/km)
Conductors
3 x 1/0 AWG (7x19x21) Tinned Copper
Ground wire
Segmented Ground Wire, 3 x 4 AWG (7x19x25) Bare Copper, totaling 1/0
Insulation
XLPE, 0.057 in (1.4 mm) nom. thickness

Characteristics (datasheet)

Conductors
3 x 1/0 AWG (7x19x21) Tinned Copper
Ground wire
Segmented Ground Wire, 3 x 4 AWG (7x19x25) Bare Copper, totaling 1/0
Insulation
XLPE, 0.057 in (1.4 mm) nom. thickness
Shield
Dual helical bare copper tape, 100% coverage, 2 mil
Jacket
Black PVC, 0.083 in (2.1 mm) nom. thickness
Overall cable diameter
1.258 in (31.95 mm)
Voltage rating
1000 V (TC, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC)
Temperature rating
90°C Dry, 90°C Wet; Operating -40°C To +90°C
Max current
170 Amps per Conductor at 30ºC
Nom. conductor DCR
0.094 Ohm/1000ft (0.31 Ohm/km)
Nom. capacitance cond-to-cond
37 pF/ft (120 pF/m)
Nom. characteristic impedance
50 Ohm
Max pull tension
5530 lbs (2510 kg)
Bulk cable weight
1708 lbs/1000ft (2542 kg/km)

29529 Applications

  • Variable Frequency Drives (VFD)
  • AC Motor and Drive Systems
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 973647103 — 60V 32A Yellow Cable Plug Connector
  • 21661 — Belden 21661 is a 600 V Type TC/CIC power and control cable containing four stra...
  • 76305WS — The 76305WS is a MachFlex™ high-flex 5-conductor 22AWG tinned copper cable with...
  • 5687 — The Belden 5687 is an XTRAGUARD 1 shielded cable featuring eight 26 AWG tinned c...
  • 82108 — The Belden 82108 is a discontinued, plenum-rated RG59 coaxial cable designed for...
  • 65407 — The Belden 65407 is an XTRAGUARD FLEX flexible control cable consisting of seven...
  • 973659101 — HIRSCHMANN TEST AND MEASUREMENT 973659101 PROBE, TEST, 4MM, RED, PKI
  • 932959001 — HIRSCHMANN TEST AND MEASUREMENT 932959001 TEST LEAD KIT

More Bulk Wire Cable

  • 23525D — The Belden 23525D is a Canadian Instrumentation Cable (TC-ACIC) rated 300 V with...
  • 89705 — The Belden 89705 is a plenum-rated, 5-pair digital audio and computer communicat...
  • 9274 — The Belden 9274 is a discontinued RG59 coaxial cable designed for analog video a...
  • 8521 — The Belden 8521 is a low-temperature plastic lead wire featuring a 16 AWG tinned...
  • 8849MN — The Belden 8849MN is a SpaceMaker™ multi-conductor cable featuring 15 conductors...
  • 37114 — Belden 37114 is a 14 AWG (41x30) stranded tinned copper lead wire with EPDM insu...
  • 9682 — The Belden 9682 is a computer EIA RS-232/422 low-capacitance cable with 24 AWG s...
  • 2232RW — The Belden 2232RW is an indoor/outdoor stadium cable, specifically an RG-59/U tr...

29529 FAQ

What is 29529?

29529 is a Bulk Wire Cable from Belden. Belden part 29529 is a flexible motor supply cable built for Variable Frequency Drives (VFD) and AC motor and drive systems, including Class 1 Division 2 hazardous locations. It contains three 1/0 AWG tinned copper conductors with XLPE insulation plus a symmetrical segmented bare copper ground, an overall dual copper tape shield, and a black PVC jacket rated 600/1000 V TC-ER.

Who manufactures 29529?

29529 is manufactured by Belden.

Where can I download the 29529 datasheet PDF?

The 29529 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 29529 specifications

AI Powered

Click to ask a quick question:

Parameters

Bulk cable weight1708 lbs/1000ft (2542 kg/km)
Conductors3 x 1/0 AWG (7x19x21) Tinned Copper
Ground wireSegmented Ground Wire, 3 x 4 AWG (7x19x25) Bare Copper, totaling 1/0
InsulationXLPE, 0.057 in (1.4 mm) nom. thickness
JacketBlack PVC, 0.083 in (2.1 mm) nom. thickness
Max current170 Amps per Conductor at 30ºC
Max pull tension5530 lbs (2510 kg)
Nom. capacitance cond-to-cond37 pF/ft (120 pF/m)
Nom. characteristic impedance50 Ohm
Nom. conductor DCR0.094 Ohm/1000ft (0.31 Ohm/km)
Overall cable diameter1.258 in (31.95 mm)
ShieldDual helical bare copper tape, 100% coverage, 2 mil
Temperature rating90°C Dry, 90°C Wet; Operating -40°C To +90°C
Voltage rating1000 V (TC, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC)