29512 Datasheet

BeldenBulk Wire Cable

Belden 29512 is a flexible 600 V/1000 V motor supply cable built for variable frequency drives (VFD), AC motor and drive systems, and Class 1 Division 2 hazardous locations. It contains three 12 AWG tinned copper power conductors with a 12 AWG ground conductor and one shielded 16 AWG control/brake pair, all enclosed in a black PVC jacket with Beldfoil plus tinned copper braid shielding. The cable is rated for sunlight resistance, direct burial, and indoor/outdoor use.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

29512 Key Specifications

Max current
30 Amps per Conductor at 30ºC (conductors); 18 Amps per Conductor at 30ºC per NEC (pair)
Nominal DC resistance
Conductor(s): 1.569 Ohm/1000ft (5.148 Ohm/km); Pair(s): 4.0 Ohm/1000ft (13 Ohm/km); Ground: 1.6 Ohm/1000ft (5.2 Ohm/km); Nom Outer Shield DCR: 0.9 Ohm/1000ft (3.0 Ohm/km)
Voltage rating
1000 V (UL Flexible Motor Supply Cable), 600 V (TC, C(UL) TC), 1000 V (AWM I/II A/B)
Temperature rating
UL Temperature: 90°C Dry, 90°C Wet; Operating: -40°C To +90°C
Conductor / ground / pair construction
3 × 12 AWG (65x30) tinned copper conductors; 1 × 12 AWG (65x30) tinned copper ground wire; 1 × 16 AWG (26x30) tinned copper pair used as control or brake pair
Insulation / jacket
XLPE conductor insulation (ICEA Chart M4 color code), PVC ground wire insulation (green/yellow stripe), black PVC outer jacket; nominal overall diameter 0.895 in (22.7 mm), ripcord yes
Mechanical
Bend radius stationary min. 10.7 in (272 mm); installation min. 10.7 in (272 mm); max. pull tension 597 lbs (271 kg); bulk cable weight 373 lbs/1000ft (555 kg/km)
Shielding
Overall Beldfoil® + tinned copper braid (85%) shield on power conductors and ground; shielded pair has its own Beldfoil shield (bi-laminate alum+poly, 100%) with 18 AWG drainwire; outer shield tri-laminate tape 100%

Characteristics (datasheet)

Conductor / ground / pair construction
3 × 12 AWG (65x30) tinned copper conductors; 1 × 12 AWG (65x30) tinned copper ground wire; 1 × 16 AWG (26x30) tinned copper pair used as control or brake pair
Insulation / jacket
XLPE conductor insulation (ICEA Chart M4 color code), PVC ground wire insulation (green/yellow stripe), black PVC outer jacket; nominal overall diameter 0.895 in (22.7 mm), ripcord yes
Shielding
Overall Beldfoil® + tinned copper braid (85%) shield on power conductors and ground; shielded pair has its own Beldfoil shield (bi-laminate alum+poly, 100%) with 18 AWG drainwire; outer shield tri-laminate tape 100%
Nominal DC resistance
Conductor(s): 1.569 Ohm/1000ft (5.148 Ohm/km); Pair(s): 4.0 Ohm/1000ft (13 Ohm/km); Ground: 1.6 Ohm/1000ft (5.2 Ohm/km); Nom Outer Shield DCR: 0.9 Ohm/1000ft (3.0 Ohm/km)
Voltage rating
1000 V (UL Flexible Motor Supply Cable), 600 V (TC, C(UL) TC), 1000 V (AWM I/II A/B)
Temperature rating
UL Temperature: 90°C Dry, 90°C Wet; Operating: -40°C To +90°C
Mechanical
Bend radius stationary min. 10.7 in (272 mm); installation min. 10.7 in (272 mm); max. pull tension 597 lbs (271 kg); bulk cable weight 373 lbs/1000ft (555 kg/km)
Max current
30 Amps per Conductor at 30ºC (conductors); 18 Amps per Conductor at 30ºC per NEC (pair)

29512 Applications

  • Variable Frequency Drives (VFD)
  • AC Motor and Drive Systems
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 6056 — The Belden 6056 is a Teck90 1000V industrial cable featuring 3+G bare copper con...
  • 9867 — The Belden 9867 is a low-temperature plastic lead wire designed for internal wir...
  • 8503 — The Belden 8503 is a low-temperature plastic lead wire with a 22 AWG tinned copp...
  • 8897 — The Belden 8897 is a low-temperature rubber lead wire featuring an 18 AWG (65x36...
  • 6023C — The Belden 6023C is a shielded communication and control cable featuring three p...
  • 5354C — The Belden 5354C is a 19-pair, 20 AWG tinned copper conductor cable with semi-ri...
  • 45054 — Belden part 45054 is an XTRAGUARD 4 cable containing 4 conductors of 20 AWG (7/2...
  • 1119A — The Belden 1119A is a UL-listed instrumentation cable featuring one 16 AWG triad...

More Bulk Wire Cable

  • 70032 — The Belden 70032 is a discontinued analog audio cable featuring four pairs of 26...
  • 9791 — The Belden 9791 is a low-capacitance computer EIA RS-232/423 cable designed for...
  • 21652 — Belden 21652 is a 600 V Type TC/CIC power and control cable with four 8 AWG stra...
  • 80150 — The Belden 80150 is a high-flexibility, 3-conductor 14 AWG tinned copper cable w...
  • 78242 — The Belden 78242 is a 2-pair 20 AWG ECOCABLE featuring tinned copper conductors,...
  • 5695 — The Belden 5695 is a shielded, semi-rigid PVC multi-conductor cable with 2 pairs...
  • 83045 — The Belden 83045 is a high-temperature plastic lead wire featuring a 28 AWG (7x3...
  • 5509UE — The Belden 5509UE is a riser-CMR security and sound cable containing 12 stranded...

29512 FAQ

What is 29512?

29512 is a Bulk Wire Cable from Belden. Belden 29512 is a flexible 600 V/1000 V motor supply cable built for variable frequency drives (VFD), AC motor and drive systems, and Class 1 Division 2 hazardous locations. It contains three 12 AWG tinned copper power conductors with a 12 AWG ground conductor and one shielded 16 AWG control/brake pair, all enclosed in a black PVC jacket with Beldfoil plus tinned copper braid shielding. The cable is rated for sunlight resistance, direct burial, and indoor/outdoor use.

Who manufactures 29512?

29512 is manufactured by Belden.

Where can I download the 29512 datasheet PDF?

The 29512 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 29512 specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor / ground / pair construction3 × 12 AWG (65x30) tinned copper conductors; 1 × 12 AWG (65x30) tinned copper ground wire; 1 × 16 AWG (26x30) tinned copper pair used as control or brake pair
Insulation / jacketXLPE conductor insulation (ICEA Chart M4 color code), PVC ground wire insulation (green/yellow stripe), black PVC outer jacket; nominal overall diameter 0.895 in (22.7 mm), ripcord yes
Max current30 Amps per Conductor at 30ºC (conductors); 18 Amps per Conductor at 30ºC per NEC (pair)
MechanicalBend radius stationary min. 10.7 in (272 mm); installation min. 10.7 in (272 mm); max. pull tension 597 lbs (271 kg); bulk cable weight 373 lbs/1000ft (555 kg/km)
Nominal DC resistanceConductor(s): 1.569 Ohm/1000ft (5.148 Ohm/km); Pair(s): 4.0 Ohm/1000ft (13 Ohm/km); Ground: 1.6 Ohm/1000ft (5.2 Ohm/km); Nom Outer Shield DCR: 0.9 Ohm/1000ft (3.0 Ohm/km)
ShieldingOverall Beldfoil® + tinned copper braid (85%) shield on power conductors and ground; shielded pair has its own Beldfoil shield (bi-laminate alum+poly, 100%) with 18 AWG drainwire; outer shield tri-laminate tape 100%
Temperature ratingUL Temperature: 90°C Dry, 90°C Wet; Operating: -40°C To +90°C
Voltage rating1000 V (UL Flexible Motor Supply Cable), 600 V (TC, C(UL) TC), 1000 V (AWM I/II A/B)