29505 Datasheet
Belden 29505 is a flexible 600/1000 V motor supply cable designed for variable frequency drives (VFD) and AC motor and drive systems. It contains three 6 AWG tinned copper conductors with XLPE insulation, one insulated 6 AWG PVC ground, four 12 AWG uninsulated tinned copper ground/drain wires, and an overall Beldfoil plus 85% tinned copper braid shield under a black PVC jacket. It is rated TC-ER and WTTC for 90°C dry/wet operation and is suitable for indoor, outdoor, sunlight-resistant, and direct burial installations.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
29505 Key Specifications
- Max current
- 75 Amps per conductor at 30°C; 18 Amps per conductor for insulated ground at 30°C (per NEC)
- Voltage rating
- 1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable); 600 V (C(UL) CIC TC); 1000 V (AWM I/II A/B)
- Temperature rating
- 90°C dry, 90°C wet (UL); operating -40°C to +90°C
- Conductors
- 3 × 6 AWG (7x19x27) tinned copper
- Ground wires
- 1 × 6 AWG insulated PVC (green/yellow stripe) + 4 × 12 AWG uninsulated tinned copper drains (4 totaling 6 AWG)
- Jacket / overall diameter
- Black PVC, 0.095 in (2.4 mm), 1.002 in (25.45 mm) nominal
- Max pull tension / weight
- 1562 lbs (708.5 kg); 793 lbs/1000 ft (1180 kg/km)
- Shield
- 100% tri-laminate tape + 85% tinned copper braid, 12 AWG drain wire
Characteristics (datasheet)
- Conductors
- 3 × 6 AWG (7x19x27) tinned copper
- Ground wires
- 1 × 6 AWG insulated PVC (green/yellow stripe) + 4 × 12 AWG uninsulated tinned copper drains (4 totaling 6 AWG)
- Shield
- 100% tri-laminate tape + 85% tinned copper braid, 12 AWG drain wire
- Jacket / overall diameter
- Black PVC, 0.095 in (2.4 mm), 1.002 in (25.45 mm) nominal
- Voltage rating
- 1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable); 600 V (C(UL) CIC TC); 1000 V (AWM I/II A/B)
- Temperature rating
- 90°C dry, 90°C wet (UL); operating -40°C to +90°C
- Max current
- 75 Amps per conductor at 30°C; 18 Amps per conductor for insulated ground at 30°C (per NEC)
- Max pull tension / weight
- 1562 lbs (708.5 kg); 793 lbs/1000 ft (1180 kg/km)
29505 Applications
- Variable Frequency Drives (VFD)
- AC Motor and Drive Systems
Other Belden parts
- 934061709 — HIRSCHMANN TEST AND MEASUREMENT 934061709 Test Lead, 4mm Banana Plug to 4mm...
- AX100910 — Cleave Inspection Microscope
- 79201 — The part 79201 is an ECOFLEX 2-conductor 20 AWG tinned copper cable with modifie...
- 83702 — The Belden 83702 is a high-temperature, shielded 2-conductor 16 AWG tinned coppe...
- 8279 — The Belden 8279 is a miniature precision video coaxial cable designed for transm...
- 80105 — The Belden 80105 is a 4-conductor, 26 AWG tinned copper cable with mPPE insulati...
- 975163103 — 1kV 10A Copper-Gold Plug Connector
- 85223CY — The Belden 85223CY is a 3-conductor, 22 AWG bare copper continuous flex control...
More Bulk Wire Cable
- 1090A — The Belden 1090A is a 50-pair, 16 AWG bare copper instrumentation cable with PVC...
- 83009 — The Belden 83009 is a high-temperature plastic lead wire featuring an 18 AWG sil...
- 25504D — The Belden 25504D is a Canadian Instrumentation Cable (TC-ACIC) rated 600 V, con...
- 79101 — The Belden 79101 (ECOFLEX) is a high-flexibility, 2-conductor, 20 AWG tinned cop...
- 82777 — The Belden 82777 is an audio, control, and instrument cable designed for indoor...
- 5330C — The Belden 5330C is a shielded multi-conductor cable featuring five 24 AWG tinne...
- 78062 — The Belden 78062 is a 2-pair 26 AWG tinned copper ECOCABLE with modified polyphe...
- 77144 — The Belden 77144 is a 5-conductor 14 AWG ECOCABLE designed for data, communicati...
29505 FAQ
What is 29505?
29505 is a Bulk Wire Cable from Belden. Belden 29505 is a flexible 600/1000 V motor supply cable designed for variable frequency drives (VFD) and AC motor and drive systems. It contains three 6 AWG tinned copper conductors with XLPE insulation, one insulated 6 AWG PVC ground, four 12 AWG uninsulated tinned copper ground/drain wires, and an overall Beldfoil plus 85% tinned copper braid shield under a black PVC jacket. It is rated TC-ER and WTTC for 90°C dry/wet operation and is suitable for indoor, outdoor, sunlight-resistant, and direct burial installations.
Who manufactures 29505?
29505 is manufactured by Belden.
Where can I download the 29505 datasheet PDF?
The 29505 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 29505 specifications
Click to ask a quick question:
Parameters
| Conductors | 3 × 6 AWG (7x19x27) tinned copper |
| Ground wires | 1 × 6 AWG insulated PVC (green/yellow stripe) + 4 × 12 AWG uninsulated tinned copper drains (4 totaling 6 AWG) |
| Jacket / overall diameter | Black PVC, 0.095 in (2.4 mm), 1.002 in (25.45 mm) nominal |
| Max current | 75 Amps per conductor at 30°C; 18 Amps per conductor for insulated ground at 30°C (per NEC) |
| Max pull tension / weight | 1562 lbs (708.5 kg); 793 lbs/1000 ft (1180 kg/km) |
| Shield | 100% tri-laminate tape + 85% tinned copper braid, 12 AWG drain wire |
| Temperature rating | 90°C dry, 90°C wet (UL); operating -40°C to +90°C |
| Voltage rating | 1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable); 600 V (C(UL) CIC TC); 1000 V (AWM I/II A/B) |