29501 Datasheet
Belden 29501 is a 600/1000 V flexible motor supply cable built for variable frequency drive and AC motor systems. It has three 14 AWG tinned copper phase conductors with XLPE insulation, a 300% ground arrangement (insulated and uninsulated 14 AWG grounds), and an overall foil-plus-braid shield with a black PVC jacket. It is rated TC-ER WTTC and is suitable for Class 1 Division 2 hazardous locations, indoor/outdoor use, sunlight resistance, and direct burial.\n","key_specs":["Conductors: 3 x 14 AWG 41x30 tinned copper phase; 1 x 14 AWG insulated ground; 1 x 14 AWG uninsulated ground","Insulation: XLPE 0.046 in (1.2 mm); conductor nominal diameter 0.173 in (4.39 mm)","Shield: Tri-Laminate (Alum+Poly+Alum) tape 100% plus tinned copper braid 85% with 14 AWG drainwire","Jacket: black PVC 0.073 in (1.9 mm); overall cable diameter 0.604 in (15.3 mm)","Voltage rating: 1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC), 1000 V (AWM I/II A/B)","Temperature: UL 90°C Dry, 90°C Wet; operating -40°C To +90°C; installation -40C","Current: 25 Amps per Conductor at 30ºC (per NEC)","Mechanical: max pull tension 347 lbs (157 kg); weight 224 lbs/1000ft (333 kg/km); bend radius 6.0 in (150 mm) stationary, 7.2 in (180 mm) installation"],"absolute_max_ratings":[],"pin_table":[],"marking_code":null,"applications":["Variable Frequency Drives (VFD)","AC Motor and Drive Systems","Class 1 Division 2 Hazardous Locations"]}
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
29501 Key Specifications
- Current rating
- 25 Amps per Conductor at 30ºC (per NEC)
- Voltage rating
- 1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC), 1000 V (AWM I/II A/B)
- Temperature
- UL 90°C Dry, 90°C Wet; operating -40°C To +90°C; installation -40C
- Conductor configuration
- 3 x 14 AWG 41x30 tinned copper phase conductors; 1 x 14 AWG 41x30 tinned copper insulated ground; 1 x 14 AWG 41x30 tinned copper uninsulated ground
- Insulation
- XLPE 0.046 in (1.2 mm); nominal insulation diameter 0.173 in (4.39 mm)
- Jacket / diameter
- Black PVC 0.073 in (1.9 mm); overall diameter 0.604 in (15.3 mm)
- Mechanical
- Max pull tension 347 lbs (157 kg); weight 224 lbs/1000ft (333 kg/km); bend radius 6.0 in (150 mm) stationary, 7.2 in (180 mm) installation
- Shield
- Tri-Laminate tape 100% + tinned copper braid 85% with 14 AWG drainwire
Characteristics (datasheet)
- Conductor configuration
- 3 x 14 AWG 41x30 tinned copper phase conductors; 1 x 14 AWG 41x30 tinned copper insulated ground; 1 x 14 AWG 41x30 tinned copper uninsulated ground
- Insulation
- XLPE 0.046 in (1.2 mm); nominal insulation diameter 0.173 in (4.39 mm)
- Shield
- Tri-Laminate tape 100% + tinned copper braid 85% with 14 AWG drainwire
- Jacket / diameter
- Black PVC 0.073 in (1.9 mm); overall diameter 0.604 in (15.3 mm)
- Voltage rating
- 1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC), 1000 V (AWM I/II A/B)
- Temperature
- UL 90°C Dry, 90°C Wet; operating -40°C To +90°C; installation -40C
- Current rating
- 25 Amps per Conductor at 30ºC (per NEC)
- Mechanical
- Max pull tension 347 lbs (157 kg); weight 224 lbs/1000ft (333 kg/km); bend radius 6.0 in (150 mm) stationary, 7.2 in (180 mm) installation
29501 Applications
- Variable Frequency Drives (VFD)
- AC Motor and Drive Systems
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 3543 — The Belden 3543 is a 30-conductor hook-up wire cable featuring 24 AWG stranded t...
- 76503TS — The Belden 76503TS is a high-flex, 3-pair 26AWG tinned copper cable with SRPVC i...
- 70251PU — The Belden 70251PU is a PUR sensor and actuator cable with 4 conductors (copper...
- 33316 — Belden 33316 is a 16 AWG (26x30) stranded tinned copper lead wire with silicone...
- 34406 — Belden 34406 is a single-conductor 6 AWG lead wire with 84x25 stranded tinned co...
- 3046A — The 3046A is a UL-listed instrumentation cable featuring four 16 AWG triads and...
- 21632 — The Belden 21632 is a CSA TC-CIC 600 V tray cable with 34 conductors: thirty 10...
- 82778 — The Belden 82778 is an audio, control, and instrument cable featuring 6 individu...
More Bulk Wire Cable
- 70031 — The Belden 70031 is a 1-pair 22AWG halogen-free screened pair cable designed for...
- 7047 — The Belden 7047 is a single-conductor hook-up wire with a 12 AWG tinned copper c...
- 9222 — The Belden 9222 is a 50Ω triaxial RG-58A/U type cable featuring a 20 AWG strande...
- 45056 — Belden 45056 is an XTRAGUARD 4 cable with 6 conductors of 20 AWG (7/28) tinned c...
- 77101 — The Belden 77101 is an ECOCABLE featuring 12 conductors of 24 AWG stranded tinne...
- 9807 — The Belden 9807 is a computer EIA RS-232/422 cable featuring five pairs of 28 AW...
- 70046 — The Belden 70046 is a flexible, low smoke zero halogen (LSZH) speaker cable with...
- 6062 — The Belden 6062 is a Teck90 600V, 7+G conductor cable featuring 14 AWG bare copp...
29501 FAQ
What is 29501?
29501 is a Bulk Wire Cable from Belden. Belden 29501 is a 600/1000 V flexible motor supply cable built for variable frequency drive and AC motor systems. It has three 14 AWG tinned copper phase conductors with XLPE insulation, a 300% ground arrangement (insulated and uninsulated 14 AWG grounds), and an overall foil-plus-braid shield with a black PVC jacket. It is rated TC-ER WTTC and is suitable for Class 1 Division 2 hazardous locations, indoor/outdoor use, sunlight resistance, and direct burial.\n","key_specs":["Conductors: 3 x 14 AWG 41x30 tinned copper phase; 1 x 14 AWG insulated ground; 1 x 14 AWG uninsulated ground","Insulation: XLPE 0.046 in (1.2 mm); conductor nominal diameter 0.173 in (4.39 mm)","Shield: Tri-Laminate (Alum+Poly+Alum) tape 100% plus tinned copper braid 85% with 14 AWG drainwire","Jacket: black PVC 0.073 in (1.9 mm); overall cable diameter 0.604 in (15.3 mm)","Voltage rating: 1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC), 1000 V (AWM I/II A/B)","Temperature: UL 90°C Dry, 90°C Wet; operating -40°C To +90°C; installation -40C","Current: 25 Amps per Conductor at 30ºC (per NEC)","Mechanical: max pull tension 347 lbs (157 kg); weight 224 lbs/1000ft (333 kg/km); bend radius 6.0 in (150 mm) stationary, 7.2 in (180 mm) installation"],"absolute_max_ratings":[],"pin_table":[],"marking_code":null,"applications":["Variable Frequency Drives (VFD)","AC Motor and Drive Systems","Class 1 Division 2 Hazardous Locations"]}.
Who manufactures 29501?
29501 is manufactured by Belden.
Where can I download the 29501 datasheet PDF?
The 29501 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 29501 specifications
Click to ask a quick question:
Parameters
| Conductor configuration | 3 x 14 AWG 41x30 tinned copper phase conductors; 1 x 14 AWG 41x30 tinned copper insulated ground; 1 x 14 AWG 41x30 tinned copper uninsulated ground |
| Current rating | 25 Amps per Conductor at 30ºC (per NEC) |
| Insulation | XLPE 0.046 in (1.2 mm); nominal insulation diameter 0.173 in (4.39 mm) |
| Jacket / diameter | Black PVC 0.073 in (1.9 mm); overall diameter 0.604 in (15.3 mm) |
| Mechanical | Max pull tension 347 lbs (157 kg); weight 224 lbs/1000ft (333 kg/km); bend radius 6.0 in (150 mm) stationary, 7.2 in (180 mm) installation |
| Shield | Tri-Laminate tape 100% + tinned copper braid 85% with 14 AWG drainwire |
| Temperature | UL 90°C Dry, 90°C Wet; operating -40°C To +90°C; installation -40C |
| Voltage rating | 1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC), 1000 V (AWM I/II A/B) |