29501 Datasheet

BeldenBulk Wire Cable

Belden 29501 is a 600/1000 V flexible motor supply cable built for variable frequency drive and AC motor systems. It has three 14 AWG tinned copper phase conductors with XLPE insulation, a 300% ground arrangement (insulated and uninsulated 14 AWG grounds), and an overall foil-plus-braid shield with a black PVC jacket. It is rated TC-ER WTTC and is suitable for Class 1 Division 2 hazardous locations, indoor/outdoor use, sunlight resistance, and direct burial.\n","key_specs":["Conductors: 3 x 14 AWG 41x30 tinned copper phase; 1 x 14 AWG insulated ground; 1 x 14 AWG uninsulated ground","Insulation: XLPE 0.046 in (1.2 mm); conductor nominal diameter 0.173 in (4.39 mm)","Shield: Tri-Laminate (Alum+Poly+Alum) tape 100% plus tinned copper braid 85% with 14 AWG drainwire","Jacket: black PVC 0.073 in (1.9 mm); overall cable diameter 0.604 in (15.3 mm)","Voltage rating: 1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC), 1000 V (AWM I/II A/B)","Temperature: UL 90°C Dry, 90°C Wet; operating -40°C To +90°C; installation -40C","Current: 25 Amps per Conductor at 30ºC (per NEC)","Mechanical: max pull tension 347 lbs (157 kg); weight 224 lbs/1000ft (333 kg/km); bend radius 6.0 in (150 mm) stationary, 7.2 in (180 mm) installation"],"absolute_max_ratings":[],"pin_table":[],"marking_code":null,"applications":["Variable Frequency Drives (VFD)","AC Motor and Drive Systems","Class 1 Division 2 Hazardous Locations"]}

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

29501 Key Specifications

Current rating
25 Amps per Conductor at 30ºC (per NEC)
Voltage rating
1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC), 1000 V (AWM I/II A/B)
Temperature
UL 90°C Dry, 90°C Wet; operating -40°C To +90°C; installation -40C
Conductor configuration
3 x 14 AWG 41x30 tinned copper phase conductors; 1 x 14 AWG 41x30 tinned copper insulated ground; 1 x 14 AWG 41x30 tinned copper uninsulated ground
Insulation
XLPE 0.046 in (1.2 mm); nominal insulation diameter 0.173 in (4.39 mm)
Jacket / diameter
Black PVC 0.073 in (1.9 mm); overall diameter 0.604 in (15.3 mm)
Mechanical
Max pull tension 347 lbs (157 kg); weight 224 lbs/1000ft (333 kg/km); bend radius 6.0 in (150 mm) stationary, 7.2 in (180 mm) installation
Shield
Tri-Laminate tape 100% + tinned copper braid 85% with 14 AWG drainwire

Characteristics (datasheet)

Conductor configuration
3 x 14 AWG 41x30 tinned copper phase conductors; 1 x 14 AWG 41x30 tinned copper insulated ground; 1 x 14 AWG 41x30 tinned copper uninsulated ground
Insulation
XLPE 0.046 in (1.2 mm); nominal insulation diameter 0.173 in (4.39 mm)
Shield
Tri-Laminate tape 100% + tinned copper braid 85% with 14 AWG drainwire
Jacket / diameter
Black PVC 0.073 in (1.9 mm); overall diameter 0.604 in (15.3 mm)
Voltage rating
1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC), 1000 V (AWM I/II A/B)
Temperature
UL 90°C Dry, 90°C Wet; operating -40°C To +90°C; installation -40C
Current rating
25 Amps per Conductor at 30ºC (per NEC)
Mechanical
Max pull tension 347 lbs (157 kg); weight 224 lbs/1000ft (333 kg/km); bend radius 6.0 in (150 mm) stationary, 7.2 in (180 mm) installation

29501 Applications

  • Variable Frequency Drives (VFD)
  • AC Motor and Drive Systems
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 3543 — The Belden 3543 is a 30-conductor hook-up wire cable featuring 24 AWG stranded t...
  • 76503TS — The Belden 76503TS is a high-flex, 3-pair 26AWG tinned copper cable with SRPVC i...
  • 70251PU — The Belden 70251PU is a PUR sensor and actuator cable with 4 conductors (copper...
  • 33316 — Belden 33316 is a 16 AWG (26x30) stranded tinned copper lead wire with silicone...
  • 34406 — Belden 34406 is a single-conductor 6 AWG lead wire with 84x25 stranded tinned co...
  • 3046A — The 3046A is a UL-listed instrumentation cable featuring four 16 AWG triads and...
  • 21632 — The Belden 21632 is a CSA TC-CIC 600 V tray cable with 34 conductors: thirty 10...
  • 82778 — The Belden 82778 is an audio, control, and instrument cable featuring 6 individu...

More Bulk Wire Cable

  • 70031 — The Belden 70031 is a 1-pair 22AWG halogen-free screened pair cable designed for...
  • 7047 — The Belden 7047 is a single-conductor hook-up wire with a 12 AWG tinned copper c...
  • 9222 — The Belden 9222 is a 50Ω triaxial RG-58A/U type cable featuring a 20 AWG strande...
  • 45056 — Belden 45056 is an XTRAGUARD 4 cable with 6 conductors of 20 AWG (7/28) tinned c...
  • 77101 — The Belden 77101 is an ECOCABLE featuring 12 conductors of 24 AWG stranded tinne...
  • 9807 — The Belden 9807 is a computer EIA RS-232/422 cable featuring five pairs of 28 AW...
  • 70046 — The Belden 70046 is a flexible, low smoke zero halogen (LSZH) speaker cable with...
  • 6062 — The Belden 6062 is a Teck90 600V, 7+G conductor cable featuring 14 AWG bare copp...

29501 FAQ

What is 29501?

29501 is a Bulk Wire Cable from Belden. Belden 29501 is a 600/1000 V flexible motor supply cable built for variable frequency drive and AC motor systems. It has three 14 AWG tinned copper phase conductors with XLPE insulation, a 300% ground arrangement (insulated and uninsulated 14 AWG grounds), and an overall foil-plus-braid shield with a black PVC jacket. It is rated TC-ER WTTC and is suitable for Class 1 Division 2 hazardous locations, indoor/outdoor use, sunlight resistance, and direct burial.\n","key_specs":["Conductors: 3 x 14 AWG 41x30 tinned copper phase; 1 x 14 AWG insulated ground; 1 x 14 AWG uninsulated ground","Insulation: XLPE 0.046 in (1.2 mm); conductor nominal diameter 0.173 in (4.39 mm)","Shield: Tri-Laminate (Alum+Poly+Alum) tape 100% plus tinned copper braid 85% with 14 AWG drainwire","Jacket: black PVC 0.073 in (1.9 mm); overall cable diameter 0.604 in (15.3 mm)","Voltage rating: 1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC), 1000 V (AWM I/II A/B)","Temperature: UL 90°C Dry, 90°C Wet; operating -40°C To +90°C; installation -40C","Current: 25 Amps per Conductor at 30ºC (per NEC)","Mechanical: max pull tension 347 lbs (157 kg); weight 224 lbs/1000ft (333 kg/km); bend radius 6.0 in (150 mm) stationary, 7.2 in (180 mm) installation"],"absolute_max_ratings":[],"pin_table":[],"marking_code":null,"applications":["Variable Frequency Drives (VFD)","AC Motor and Drive Systems","Class 1 Division 2 Hazardous Locations"]}.

Who manufactures 29501?

29501 is manufactured by Belden.

Where can I download the 29501 datasheet PDF?

The 29501 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 29501 specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor configuration3 x 14 AWG 41x30 tinned copper phase conductors; 1 x 14 AWG 41x30 tinned copper insulated ground; 1 x 14 AWG 41x30 tinned copper uninsulated ground
Current rating25 Amps per Conductor at 30ºC (per NEC)
InsulationXLPE 0.046 in (1.2 mm); nominal insulation diameter 0.173 in (4.39 mm)
Jacket / diameterBlack PVC 0.073 in (1.9 mm); overall diameter 0.604 in (15.3 mm)
MechanicalMax pull tension 347 lbs (157 kg); weight 224 lbs/1000ft (333 kg/km); bend radius 6.0 in (150 mm) stationary, 7.2 in (180 mm) installation
ShieldTri-Laminate tape 100% + tinned copper braid 85% with 14 AWG drainwire
TemperatureUL 90°C Dry, 90°C Wet; operating -40°C To +90°C; installation -40C
Voltage rating1000 V (TC-ER, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC), 1000 V (AWM I/II A/B)