28335A Datasheet
The Belden 28335A is a 5-conductor, 18 AWG (7x26) bare copper power and control cable with PVC/nylon insulation and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF), with an operating temperature range of -30°C to 90°C wet/dry, and is suitable for power and control applications up to 600V and Class 1 Division 2 hazardous locations.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28335A Key Specifications
- Max. Current
- 11.2 Amps per Conductor at 30ºC
- UL Voltage Rating
- 600 V (TC-ER), 150 V (NPLF)
- Operating Temperature Wet/Dry
- -30°C to 90°C
- Bulk Cable Weight
- 66 lbs/1000ft
- Conductors
- 5
- Conductor Size / Stranding / Material
- 18 AWG 7x26 BC - Bare Copper
- Insulation Material / Nom. Thickness / Nom. Diameter
- PVC/Nylon - Polyvinyl Chloride + Nylon, 0.020 in (0.51 mm), 0.087 in (2.2 mm)
- Max. Pull Tension
- 110 lbs (50 kg)
Characteristics (datasheet)
- Conductors
- 5
- Conductor Size / Stranding / Material
- 18 AWG 7x26 BC - Bare Copper
- Insulation Material / Nom. Thickness / Nom. Diameter
- PVC/Nylon - Polyvinyl Chloride + Nylon, 0.020 in (0.51 mm), 0.087 in (2.2 mm)
- Outer Jacket Material / Nom. Thickness / Overall Diameter
- PVC - Polyvinyl Chloride, 0.047 in (1.2 mm), 0.329 in
- Nom. Conductor DCR
- 6.7 Ohm/1000ft
- Max. Current
- 11.2 Amps per Conductor at 30ºC
- UL Voltage Rating
- 600 V (TC-ER), 150 V (NPLF)
- Operating Temperature Wet/Dry
- -30°C to 90°C
- Max. Pull Tension
- 110 lbs (50 kg)
- Bulk Cable Weight
- 66 lbs/1000ft
28335A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 3104A — The Belden 3104A is a shielded, 3-conductor 12 AWG bare copper cable with PVC-Ny...
- 79061 — The Belden 79061 (ECOFLEX) is a 2-conductor 28 AWG tinned copper cable with modi...
- 25113 — Belden part 25113 is an XTRAGUARD 2 cable with three 24 AWG (7/32) tinned copper...
- 9843 — The Belden 9843 is an RS-485 communication cable featuring three 24 AWG tinned c...
- 2630 — The Belden 2630 is a single-conductor hook-up wire featuring a 30 AWG nickel-pla...
- 9161 — The Belden 9161 is an electronic cable consisting of 8 pairs of 18 AWG tinned co...
- 8725 — The Belden 8725 is a multi-conductor audio, control, and instrumentation cable f...
- 9368 — The Belden 9368 is a high-performance instrumentation cable consisting of two pa...
More Bulk Wire Cable
- 25004 — The Belden 25004 is an XTRAGUARD 2 cable with four 22 AWG (7/30) tinned copper c...
- 5283C — The Belden 5283C is an XTRAGUARD 1 multi-conductor cable featuring 3 pairs of 20...
- 85244CY — The 85244CY is an XTRAGUARD FLEX continuous flex control cable featuring 4 condu...
- 79010 — The Belden 79010 is a 2-conductor 18 AWG tinned copper cable with modified polyp...
- 78384 — The part 78384 is a 4-pair 22 AWG tinned copper conductor ECOCABLE with modified...
- 78405 — The Belden 78405 is an ECOCABLE featuring 20 conductors of 20 AWG tinned copper...
- 1555 — The Belden 1555 is a single-conductor, 10 AWG solid bare copper wire with PVC in...
- 89292 — The Belden 89292 is a plenum-rated, RG11 analog video cable featuring a 14 AWG s...
28335A FAQ
What is 28335A?
28335A is a Bulk Wire Cable from Belden. The Belden 28335A is a 5-conductor, 18 AWG (7x26) bare copper power and control cable with PVC/nylon insulation and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF), with an operating temperature range of -30°C to 90°C wet/dry, and is suitable for power and control applications up to 600V and Class 1 Division 2 hazardous locations.
Who manufactures 28335A?
28335A is manufactured by Belden.
Where can I download the 28335A datasheet PDF?
The 28335A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28335A specifications
Click to ask a quick question:
Parameters
| Bulk Cable Weight | 66 lbs/1000ft |
| Conductors | 5 |
| Conductor Size / Stranding / Material | 18 AWG 7x26 BC - Bare Copper |
| Insulation Material / Nom. Thickness / Nom. Diameter | PVC/Nylon - Polyvinyl Chloride + Nylon, 0.020 in (0.51 mm), 0.087 in (2.2 mm) |
| Max. Current | 11.2 Amps per Conductor at 30ºC |
| Max. Pull Tension | 110 lbs (50 kg) |
| Nom. Conductor DCR | 6.7 Ohm/1000ft |
| Operating Temperature Wet/Dry | -30°C to 90°C |
| Outer Jacket Material / Nom. Thickness / Overall Diameter | PVC - Polyvinyl Chloride, 0.047 in (1.2 mm), 0.329 in |
| UL Voltage Rating | 600 V (TC-ER), 150 V (NPLF) |