28326A Datasheet

BeldenBulk Wire Cable

The Belden 28326A is a 4-conductor, 18 AWG (7x26 stranded bare copper) power and control cable with PVC/nylon conductor insulation and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF), with a 90 °C dry/wet rating and an operating range of -30 °C to 90 °C. It is intended for power and control applications up to 600 V and Class 1 Division 2 hazardous locations, and is sunlight resistant and suitable for direct burial.\n\n

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

28326A Key Specifications

Maximum current
11.2 Amps per Conductor at 30ºC
Voltage rating
600 V (TC-ER), 150 V (NPLF)
Temperature rating
90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C
Conductor
4 conductors, 18 AWG, 7x26 stranding, BC - Bare Copper
Insulation
PVC/Nylon - Polyvinyl Chloride + Nylon, 0.020 in (0.51 mm) nominal thickness, 0.087 in (2.2 mm) nominal insulation diameter
Maximum pull tension
88 lbs (40 kg)
Nominal conductor DCR
6.66 Ohm/1000ft
Overall cable diameter (nominal)
0.304 in (7.72 mm)

Characteristics (datasheet)

Conductor
4 conductors, 18 AWG, 7x26 stranding, BC - Bare Copper
Insulation
PVC/Nylon - Polyvinyl Chloride + Nylon, 0.020 in (0.51 mm) nominal thickness, 0.087 in (2.2 mm) nominal insulation diameter
Voltage rating
600 V (TC-ER), 150 V (NPLF)
Temperature rating
90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C
Nominal conductor DCR
6.66 Ohm/1000ft
Maximum current
11.2 Amps per Conductor at 30ºC
Overall cable diameter (nominal)
0.304 in (7.72 mm)
Maximum pull tension
88 lbs (40 kg)

28326A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 21610 — The Belden 21610 is a CSA TC-CIC 600 V tray cable rated 90 °C for dry/wet locati...
  • 5390C — The Belden 5390C is a 10-conductor, 18 AWG tinned copper shielded cable with PVC...
  • 1310 — The part 1310 is a heavy-duty RW90 rated power and control cable with a 3/0 AWG...
  • 5938 — The Belden 5938 is a 2-pair, 28 AWG tinned copper cable with semi-rigid PVC insu...
  • 76601TS — The Belden 76601TS is a high-flex, 2-conductor 24AWG tinned copper cable with SR...
  • 25373 — Belden 25373 is an XTRAGUARD 2 cable with 3 shielded pairs of 18 AWG (16x30) tin...
  • 5062C — The Belden 5062C is an XTRAGUARD 1, 2-conductor, 18 AWG tinned copper cable with...
  • 7439W — The Belden 7439W is a high-flex MachFlex cable featuring 8+1 conductors of 14AWG...

More Bulk Wire Cable

  • 78354 — The part 78354 is a 4-pair 28 AWG tinned copper ECOCABLE with modified polypheny...
  • 6216C — The Belden 6216C is a communication and control cable consisting of 6 pairs of 2...
  • 28630A — The Belden 28630A is a 37-conductor, 12 AWG (7x20 stranded bare copper) UL Type...
  • 21591 — The Belden 21591 is a Canadian TC-CIC instrumentation and control cable rated 60...
  • 79203 — The Belden 79203 is a flexible 4-conductor, 20 AWG tinned copper cable with mPPE...
  • 5022C — The Belden 5022C is a 2-pair, 22 AWG tinned copper conductor cable with semi-rig...
  • 3515 — The Belden 3515 is a 15-conductor hook-up wire featuring 22 AWG tinned copper co...
  • 7933A — The Belden 7933A is a DataTuff Category 5e industrial Ethernet cable featuring t...

28326A FAQ

What is 28326A?

28326A is a Bulk Wire Cable from Belden. The Belden 28326A is a 4-conductor, 18 AWG (7x26 stranded bare copper) power and control cable with PVC/nylon conductor insulation and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF), with a 90 °C dry/wet rating and an operating range of -30 °C to 90 °C. It is intended for power and control applications up to 600 V and Class 1 Division 2 hazardous locations, and is sunlight resistant and suitable for direct burial.\n\n.

Who manufactures 28326A?

28326A is manufactured by Belden.

Where can I download the 28326A datasheet PDF?

The 28326A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 28326A specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor4 conductors, 18 AWG, 7x26 stranding, BC - Bare Copper
InsulationPVC/Nylon - Polyvinyl Chloride + Nylon, 0.020 in (0.51 mm) nominal thickness, 0.087 in (2.2 mm) nominal insulation diameter
Maximum current11.2 Amps per Conductor at 30ºC
Maximum pull tension88 lbs (40 kg)
Nominal conductor DCR6.66 Ohm/1000ft
Overall cable diameter (nominal)0.304 in (7.72 mm)
Temperature rating90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C
Voltage rating600 V (TC-ER), 150 V (NPLF)