28178A Datasheet

BeldenBulk Wire Cable

The Belden 28178A is a UL Type TC power and control cable with four 4/0 AWG bare copper conductors plus one 4 AWG bare copper ground conductor. It features PVC/nylon insulation, a black PVC outer jacket with ripcord, and is rated 600 V, 90 °C dry/wet, with sunlight resistance and suitability for direct burial and Class 1 Division 2 hazardous locations.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

28178A Key Specifications

Max. Current
208 Amps per Conductor at 30 °C (conductors); 95 Amps per Conductor at 30 °C (ground)
UL Voltage Rating
600 V (TC-ER)
Operating Temperature
-30 °C to 90 °C Dry/Wet
UL Temperature
90 °C Dry, 90 °C Wet
Conductors
4 x 4/0 AWG (19x10) bare copper plus 1 x 4 AWG (7x12) bare copper ground
Max. Pull Tension / Weight
10691 lbs (4849.4 kg); 3386 lbs/1000ft
Nominal Jacket Thickness
0.116 in (2.95 mm)
Nominal Overall Diameter
1.775 in (45.09 mm)

Characteristics (datasheet)

UL Voltage Rating
600 V (TC-ER)
Conductors
4 x 4/0 AWG (19x10) bare copper plus 1 x 4 AWG (7x12) bare copper ground
Max. Current
208 Amps per Conductor at 30 °C (conductors); 95 Amps per Conductor at 30 °C (ground)
UL Temperature
90 °C Dry, 90 °C Wet
Operating Temperature
-30 °C to 90 °C Dry/Wet
Nominal Overall Diameter
1.775 in (45.09 mm)
Nominal Jacket Thickness
0.116 in (2.95 mm)
Max. Pull Tension / Weight
10691 lbs (4849.4 kg); 3386 lbs/1000ft

28178A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 1565 — The Belden 1565 is a TW-75 600V, 8 AWG 7 strand bare copper cable with PVC insul...
  • 83010006500 — HOOK-UP STRND 16AWG BLUE 500
  • 9808 — The Belden 9808 is a computer EIA RS-232/RS-422 cable featuring 7 pairs of 28 AW...
  • 82760 — The Belden 82760 is a 2-conductor 18 AWG tinned copper electronic cable with FEP...
  • 8503 — The Belden 8503 is a low-temperature plastic lead wire with a 22 AWG tinned copp...
  • 39116 — Belden 39116 is a 16 AWG (26x30) stranded tinned copper lead wire with PPO (poly...
  • 9832 — The Belden 9832 is a computer EIA RS-232/422 cable featuring 5 pairs of 24 AWG s...
  • 25193 — The Belden 25193 is an XTRAGUARD 2 cable with 3 conductors of 22 AWG (7/30) tinn...

More Bulk Wire Cable

  • 80013 — The Belden 80013 (ECOFLEX PUR) is a highly flexible, zero-halogen 10-conductor c...
  • 80024 — The part 80024 is a 7-conductor, 20 AWG tinned copper cable with mPPE insulation...
  • 29032 — Belden part 29032 is a Canadian ACIC 600 V instrumentation cable with four 18 AW...
  • 85247CY — The Belden 85247CY (Alpha Wire) is a 7-conductor, 24 AWG XTRAGUARD FLEX continuo...
  • 9762MN — The Belden 9762MN SpaceMaker™ is a multi-pair cable consisting of five 16 AWG (6...
  • 9525 — The Belden 9525 is a computer EIA RS-232 cable designed for RS-232 applications,...
  • 7045 — The Belden 7045 is a single-conductor, 16 AWG tinned copper hook-up wire with cr...
  • 8058 — The Belden 8058 is a 36 AWG solid bare copper magnet wire with PUR/Nylon (polyur...

28178A FAQ

What is 28178A?

28178A is a Bulk Wire Cable from Belden. The Belden 28178A is a UL Type TC power and control cable with four 4/0 AWG bare copper conductors plus one 4 AWG bare copper ground conductor. It features PVC/nylon insulation, a black PVC outer jacket with ripcord, and is rated 600 V, 90 °C dry/wet, with sunlight resistance and suitability for direct burial and Class 1 Division 2 hazardous locations.

Who manufactures 28178A?

28178A is manufactured by Belden.

Where can I download the 28178A datasheet PDF?

The 28178A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 28178A specifications

AI Powered

Click to ask a quick question:

Parameters

Conductors4 x 4/0 AWG (19x10) bare copper plus 1 x 4 AWG (7x12) bare copper ground
Max. Current208 Amps per Conductor at 30 °C (conductors); 95 Amps per Conductor at 30 °C (ground)
Max. Pull Tension / Weight10691 lbs (4849.4 kg); 3386 lbs/1000ft
Nominal Jacket Thickness0.116 in (2.95 mm)
Nominal Overall Diameter1.775 in (45.09 mm)
Operating Temperature-30 °C to 90 °C Dry/Wet
UL Temperature90 °C Dry, 90 °C Wet
UL Voltage Rating600 V (TC-ER)