28154A Datasheet
The Belden 28154A is a UL Type TC (1277) power and control cable with four 6 AWG bare copper conductors and one 8 AWG bare copper ground wire, using PVC/nylon insulation and a black PVC outer jacket. It is rated 600 V and 90 °C dry/wet, with an operating range of -30 °C to 90 °C wet/dry, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, direct burial, and Class 1 Division 2 hazardous location applications.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28154A Key Specifications
- Max current
- 60 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 30ºC (ground wire)
- Voltage rating
- 600 V
- Temperature rating
- 90°C Dry, 90°C Wet; operating Wet/Dry: -30°C to 90°C
- Conductor configuration
- 4 conductors 6 AWG (7x14) bare copper plus 1 ground wire 8 AWG (7x16) bare copper
- Insulation
- PVC/Nylon - Polyvinyl Chloride + Nylon, 0.035 in (0.89 mm) nominal thickness
- Jacket
- Black PVC, 0.063 in (1.6 mm) nominal thickness
- Max pull tension / weight
- 1610 lbs (730 kg); 519 lbs/1000ft
- Overall cable diameter
- 0.734 in (18.6 mm) nominal
Characteristics (datasheet)
- Conductor configuration
- 4 conductors 6 AWG (7x14) bare copper plus 1 ground wire 8 AWG (7x16) bare copper
- Insulation
- PVC/Nylon - Polyvinyl Chloride + Nylon, 0.035 in (0.89 mm) nominal thickness
- Jacket
- Black PVC, 0.063 in (1.6 mm) nominal thickness
- Overall cable diameter
- 0.734 in (18.6 mm) nominal
- Voltage rating
- 600 V
- Temperature rating
- 90°C Dry, 90°C Wet; operating Wet/Dry: -30°C to 90°C
- Max current
- 60 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 30ºC (ground wire)
- Max pull tension / weight
- 1610 lbs (730 kg); 519 lbs/1000ft
28154A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 8766 — The Belden 8766 is a multi-conductor audio, control, and instrument cable featur...
- 8020 — The Belden 8020 is a single-conductor bus bar wire made of a solid 20 AWG tinned...
- 6624 — The Belden 6624 is a 4-conductor, 24 AWG tinned copper control cable with irradi...
- 5302C — The Belden 5302C is a heavy-duty, shielded multi-conductor cable featuring 12 st...
- 77154 — The Belden 77154 is a 4-conductor 28 AWG tinned copper cable featuring mPPE insu...
- 25063 — Belden part 25063 is an XTRAGUARD 2, 3-conductor 18 AWG (16/30) tinned copper ca...
- 78353 — The 78353 is a shielded, 3-pair 28 AWG tinned copper cable with modified polyphe...
- 9903 — The Belden 9903 is an IEEE 802.3 Ethernet transceiver cable designed for 10BASE5...
More Bulk Wire Cable
- 6141 — The Belden 6141 is a Teck90 1000V heavy-duty power cable featuring 4 bare copper...
- 45363 — Belden part 45363 is a 3-conductor 16 AWG (19x29 stranded tinned copper) XTRAGUA...
- 83046 — The Belden 83046 is a high-temperature plastic lead wire featuring a 26 AWG silv...
- 1932 — The Belden 1932 is a 2-conductor, 18 AWG bare copper signal cord with EPDM rubbe...
- 1060A — The Belden 1060A is a multi-conductor instrumentation cable featuring 24 pairs o...
- 9224 — The Belden 9224 is a low-noise audio coaxial cable of RG-59 type, featuring a 22...
- 5624UG — The Belden 5624UG is a nurse call and paging cable rated for CM applications, co...
- 29543 — Belden 29543 is a flexible 2000 V motor supply cable with three 1 AWG tinned cop...
28154A FAQ
What is 28154A?
28154A is a Bulk Wire Cable from Belden. The Belden 28154A is a UL Type TC (1277) power and control cable with four 6 AWG bare copper conductors and one 8 AWG bare copper ground wire, using PVC/nylon insulation and a black PVC outer jacket. It is rated 600 V and 90 °C dry/wet, with an operating range of -30 °C to 90 °C wet/dry, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, direct burial, and Class 1 Division 2 hazardous location applications.
Who manufactures 28154A?
28154A is manufactured by Belden.
Where can I download the 28154A datasheet PDF?
The 28154A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28154A specifications
Click to ask a quick question:
Parameters
| Conductor configuration | 4 conductors 6 AWG (7x14) bare copper plus 1 ground wire 8 AWG (7x16) bare copper |
| Insulation | PVC/Nylon - Polyvinyl Chloride + Nylon, 0.035 in (0.89 mm) nominal thickness |
| Jacket | Black PVC, 0.063 in (1.6 mm) nominal thickness |
| Max current | 60 Amps per Conductor at 30ºC (conductors); 55 Amps per Conductor at 30ºC (ground wire) |
| Max pull tension / weight | 1610 lbs (730 kg); 519 lbs/1000ft |
| Overall cable diameter | 0.734 in (18.6 mm) nominal |
| Temperature rating | 90°C Dry, 90°C Wet; operating Wet/Dry: -30°C to 90°C |
| Voltage rating | 600 V |