28152A Datasheet
The Belden 28152A is a UL Type TC (1277) tray cable with two 6 AWG bare copper conductors and one 8 AWG bare copper ground conductor, insulated with PVC/nylon and covered by a black PVC outer jacket. It is rated 600 V RMS (Type TC / TC-ER) for 90°C dry and 75°C wet service, with an operating temperature range of -25°C to +90°C. It is intended for harsh environments such as oil and gas extraction and refining sites, petrochemical facilities, and Profibus or Foundation FieldBus process automation, with suitability for direct burial, sunlight resistance, and exposure to moisture, dust, and oil.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28152A Key Specifications
- Max current
- 75 Amps per Conductor at 30ºC
- Voltage rating
- 600 V RMS (Type TC) (TC-ER)
- Temperature rating
- 90°C Dry, 75°C Wet UL; Operating -25°C To +90°C
- Compliance
- TC-ER, UL1685 Vertical Tray Flame Test, IEEE 1202, EU CE Mark, RoHS 2, China RoHS II
- Insulation
- PVC/Nylon (Polyvinyl Chloride + Nylon), 0.254 in (6.45 mm) nominal diameter
- Nominal conductor DCR
- 0.41 Ohm/1000ft (1.3 Ohm/km)
- Outer jacket
- Black PVC, 0.063 in (1.6 mm) nominal thickness, 0.634 in nominal diameter
Characteristics (datasheet)
- Insulation
- PVC/Nylon (Polyvinyl Chloride + Nylon), 0.254 in (6.45 mm) nominal diameter
- Outer jacket
- Black PVC, 0.063 in (1.6 mm) nominal thickness, 0.634 in nominal diameter
- Voltage rating
- 600 V RMS (Type TC) (TC-ER)
- Max current
- 75 Amps per Conductor at 30ºC
- Nominal conductor DCR
- 0.41 Ohm/1000ft (1.3 Ohm/km)
- Temperature rating
- 90°C Dry, 75°C Wet UL; Operating -25°C To +90°C
- Compliance
- TC-ER, UL1685 Vertical Tray Flame Test, IEEE 1202, EU CE Mark, RoHS 2, China RoHS II
28152A Applications
- Harsh environment digital and serial two-way communication
- Oil and gas extraction and refining sites
- Petrochemical
- Profibus process automation
- Foundation FieldBus process automation
- Extreme temperature environments
- Exposure to humidity/moisture, dust, and oil
- Remote locations long distance applications
Other Belden parts
- 5180C — The Belden 5180C is an XTRAGUARD 1 shielded cable featuring 10 conductors of 16...
- 83512 — The Belden 83512 is a high-temperature, plenum-rated (CMP) multi-conductor cable...
- 70043 — The Belden 70043 is an analog audio cable featuring 8 pairs of 26 AWG conductors...
- 3464C — The Belden 3464C is a 4-conductor, 28 AWG tinned copper shielded communication a...
- 45433 — Belden part 45433 is an XTRAGUARD 4 3-conductor, 16 AWG stranded tinned copper c...
- 32822 — Belden 32822 is a low-temperature PVC-insulated lead wire built with 22 AWG (7x3...
- 9272 — The Belden 9272 is a 78 Ohm twinaxial cable constructed with 20 AWG stranded tin...
- 8051 — The Belden 8051 is a 22 AWG solid bare copper magnet wire with PUR/Nylon insulat...
More Bulk Wire Cable
- 8212 — The Belden 8212 is a discontinued RG59 analog video coaxial cable featuring a 20...
- 9851 — The Belden 9851 is a single-conductor coaxial cable constructed with a 30 AWG si...
- 70066 — The Belden 70066 is an audio 8 x quad snake cable with a PVC outer jacket and 26...
- 1811A — The Belden 1811A is a discontinued speaker cable consisting of eight 14 AWG stra...
- 86706CY — The 86706CY is a continuous flex data cable featuring six pairs of 22 AWG tinned...
- 5363C — The Belden 5363C is a heavy-duty, shielded 3-conductor cable built with 16 AWG s...
- 5201C — The Belden 5201C is a 7-conductor, 24 AWG tinned copper cable with semi-rigid PV...
- 83043 — The Belden 83043 is a high-temperature plastic lead wire featuring a 30 AWG silv...
28152A FAQ
What is 28152A?
28152A is a Bulk Wire Cable from Belden. The Belden 28152A is a UL Type TC (1277) tray cable with two 6 AWG bare copper conductors and one 8 AWG bare copper ground conductor, insulated with PVC/nylon and covered by a black PVC outer jacket. It is rated 600 V RMS (Type TC / TC-ER) for 90°C dry and 75°C wet service, with an operating temperature range of -25°C to +90°C. It is intended for harsh environments such as oil and gas extraction and refining sites, petrochemical facilities, and Profibus or Foundation FieldBus process automation, with suitability for direct burial, sunlight resistance, and exposure to moisture, dust, and oil.
Who manufactures 28152A?
28152A is manufactured by Belden.
Where can I download the 28152A datasheet PDF?
The 28152A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28152A specifications
Click to ask a quick question:
Parameters
| Compliance | TC-ER, UL1685 Vertical Tray Flame Test, IEEE 1202, EU CE Mark, RoHS 2, China RoHS II |
| Insulation | PVC/Nylon (Polyvinyl Chloride + Nylon), 0.254 in (6.45 mm) nominal diameter |
| Max current | 75 Amps per Conductor at 30ºC |
| Nominal conductor DCR | 0.41 Ohm/1000ft (1.3 Ohm/km) |
| Outer jacket | Black PVC, 0.063 in (1.6 mm) nominal thickness, 0.634 in nominal diameter |
| Temperature rating | 90°C Dry, 75°C Wet UL; Operating -25°C To +90°C |
| Voltage rating | 600 V RMS (Type TC) (TC-ER) |