The Belden 28094A is a 16-conductor, 14 AWG (7x22) bare copper power and control cable with PVC/nylon insulation and a black PVC outer jacket. It is rated for 600 V (TC-ER) and 150 V (NPLF), with 90°C dry/wet temperature rating, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial installations, including Class 1 Division 2 hazardous locations. The unshielded cable includes a ripcord and has an overall diameter of 0.652 in (16.6 mm).
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28094A Key Specifications
- Max current
- 12.5 Amps per Conductor at 30ºC
- Voltage rating
- 600 V (TC-ER), 150 V (NPLF)
- Temperature rating
- 90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
- Bulk cable weight
- 334 lbs/1000ft
- Conductors
- 16 conductors, 14 AWG, 7x22 stranding, bare copper
- Max pull tension
- 837.6 lbs (379.9 kg)
- Nominal conductor DCR
- 2.67 Ohm/1000ft
- Overall cable diameter
- 0.652 in (16.6 mm)
Characteristics (datasheet)
- Conductors
- 16 conductors, 14 AWG, 7x22 stranding, bare copper
- Voltage rating
- 600 V (TC-ER), 150 V (NPLF)
- Max current
- 12.5 Amps per Conductor at 30ºC
- Nominal conductor DCR
- 2.67 Ohm/1000ft
- Temperature rating
- 90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C
- Overall cable diameter
- 0.652 in (16.6 mm)
- Max pull tension
- 837.6 lbs (379.9 kg)
- Bulk cable weight
- 334 lbs/1000ft
28094A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 8677 — The Belden 8677 is a 2-conductor electronic cable featuring 16AWG bare copper co...
- 1712 — The Belden 1712 is a 2-conductor 20 AWG tinned copper communication and control...
- 5110C — The Belden 5110C is a 10-conductor, 22 AWG tinned copper control cable featuring...
- 21587 — The Belden 21587 is a CSA Tray TC-CIC 600V cable with 39 conductors of 12 AWG ba...
- 1114A — The Belden 1114A is a Type EX thermocouple cable containing a single pair of 16...
- 22632D — The Belden 22632D is a Canadian Instrumentation Cable (CIC) rated 300 V, constru...
- 1492A — The Belden 1492A is a UL-listed instrumentation and control cable featuring two...
- 77607W — The Belden 77607W is a MachFlex™ high-flexibility cable featuring a 7+G conducto...
More Bulk Wire Cable
- 6101FE — The Belden 6101FE is a plenum-rated security and commercial audio cable designed...
- 34918 — Belden 34918 is an 18 AWG (16x30 stranding) tinned copper lead wire with CSPE (c...
- 80065 — The part 80065 is a 3-conductor 10 AWG tinned copper cable with MPPE insulation...
- 7892A — The Belden 7892A is a discontinued digital audio snake cable with CM rating, fea...
- 9342 — The Belden 9342 is a high-performance instrumentation cable featuring a single p...
- 78455 — The Belden 78455 is a 25-conductor, 20 AWG tinned copper multi-conductor cable (...
- 29503 — Belden 29503 is a flexible 600/1000 V motor supply cable built for variable freq...
- 80150 — The Belden 80150 is a high-flexibility, 3-conductor 14 AWG tinned copper cable w...
28094A FAQ
What is 28094A?
28094A is a Bulk Wire Cable from Belden. The Belden 28094A is a 16-conductor, 14 AWG (7x22) bare copper power and control cable with PVC/nylon insulation and a black PVC outer jacket. It is rated for 600 V (TC-ER) and 150 V (NPLF), with 90°C dry/wet temperature rating, and is suitable for indoor, outdoor, sunlight-resistant, UV-resistant, and direct burial installations, including Class 1 Division 2 hazardous locations. The unshielded cable includes a ripcord and has an overall diameter of 0.652 in (16.6 mm).
Who manufactures 28094A?
28094A is manufactured by Belden.
Where can I download the 28094A datasheet PDF?
The 28094A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28094A specifications
Click to ask a quick question:
Parameters
| Bulk cable weight | 334 lbs/1000ft |
| Conductors | 16 conductors, 14 AWG, 7x22 stranding, bare copper |
| Max current | 12.5 Amps per Conductor at 30ºC |
| Max pull tension | 837.6 lbs (379.9 kg) |
| Nominal conductor DCR | 2.67 Ohm/1000ft |
| Overall cable diameter | 0.652 in (16.6 mm) |
| Temperature rating | 90°C Dry, 90°C Wet; Wet/Dry: -30°C to 90°C |
| Voltage rating | 600 V (TC-ER), 150 V (NPLF) |