28085A Datasheet
The Belden 28085A is a UL Type TC (1277) power and control cable with seven 14 AWG (7x22) bare copper conductors, PVC/nylon insulation (E2 color code), and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF), with UL temperature of 90 °C dry / 90 °C wet and an operating range of -30 °C to 90 °C wet/dry. It is suitable for power and control applications up to 600 V, including Class 1 Division 2 hazardous locations.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
28085A Key Specifications
- Voltage Rating
- 600 V (TC-ER), 150 V (NPLF)
- Temperature
- UL Temperature 90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C
- Conductors
- 7 conductors, 14 AWG, 7x22 stranding, BC - Bare Copper
- Electrical
- Nom. Conductor DCR 2.67 Ohm/1000ft; Max. Current 17.5 Amps per Conductor at 30ºC
- Insulation
- PVC/Nylon - Polyvinyl Chloride + Nylon, Nom. Thickness 0.019 in (0.48 mm), Nom. Insulation Diameter 0.112 in (2.84 mm), Color Code Black, Red, Blue, Orange, Yellow, Brown, Red/Black
- Mechanical
- Max. Pull Tension 382.2 lbs (173.4 kg); Bulk Cable Weight 148 lbs/1000ft
- Outer Jacket
- PVC - Polyvinyl Chloride, Nom. Thickness 0.047 in (1.2 mm), Nom. Diameter 0.430 in (10.9 mm), Ripcord Yes
- Overall Cable Diameter (Nominal)
- 0.430 in (10.9 mm)
Characteristics (datasheet)
- Conductors
- 7 conductors, 14 AWG, 7x22 stranding, BC - Bare Copper
- Insulation
- PVC/Nylon - Polyvinyl Chloride + Nylon, Nom. Thickness 0.019 in (0.48 mm), Nom. Insulation Diameter 0.112 in (2.84 mm), Color Code Black, Red, Blue, Orange, Yellow, Brown, Red/Black
- Outer Jacket
- PVC - Polyvinyl Chloride, Nom. Thickness 0.047 in (1.2 mm), Nom. Diameter 0.430 in (10.9 mm), Ripcord Yes
- Overall Cable Diameter (Nominal)
- 0.430 in (10.9 mm)
- Voltage Rating
- 600 V (TC-ER), 150 V (NPLF)
- Temperature
- UL Temperature 90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C
- Electrical
- Nom. Conductor DCR 2.67 Ohm/1000ft; Max. Current 17.5 Amps per Conductor at 30ºC
- Mechanical
- Max. Pull Tension 382.2 lbs (173.4 kg); Bulk Cable Weight 148 lbs/1000ft
28085A Applications
- Power and Control Applications up to 600V
- Class 1 Division 2 Hazardous Locations
Other Belden parts
- 21630 — Belden 21630 is a CSA TC-CIC 600 V tray cable intended for CEC power and control...
- 32414 — Belden part 32414 is a 14 AWG stranded tinned copper lead wire with silicone rub...
- 1806 — The Belden 1806 is a single-conductor hook-up wire featuring a 28 AWG solid silv...
- 9402 — The Belden 9402 is a chrome-colored, 2-pair audio, control, and instrument cable...
- 9156 — The Belden 9156 is a multi-conductor electronic cable featuring 2 pairs of 18 AW...
- 1387 — The Belden 1387 is a heavy-duty RWU90 power and control cable rated for 1000 V,...
- 6710 — The Belden 6710 is a single-conductor hook-up wire with a 28 AWG tinned copper c...
- 65223CY — The 65223CY is a flexible 3-conductor 22 AWG bare copper control cable with PVC...
More Bulk Wire Cable
- 79219 — The Belden 79219 is a 3-conductor, 16 AWG tinned copper cable with mPPE insulati...
- 8691 — The Belden 8691 is an electronic cable consisting of six pairs of 18 AWG tinned...
- 7145W — The Belden 7145W is a high-flex MachFlex™ power cable featuring three 12 AWG num...
- 5275C — The Belden 5275C is a semi-rigid, shielded multi-conductor cable featuring 5 pai...
- 9550 — The Belden 9550 is a computer EIA RS-232 cable consisting of 50 twisted pairs of...
- 78026 — The Belden 78026 is a 6-conductor, 24 AWG tinned copper ECOCABLE with modified p...
- 25004 — The Belden 25004 is an XTRAGUARD 2 cable with four 22 AWG (7/30) tinned copper c...
- 25272 — Belden 25272 is an XTRAGUARD 2 cable with 2 pairs of 24 AWG (7x32) stranded tinn...
28085A FAQ
What is 28085A?
28085A is a Bulk Wire Cable from Belden. The Belden 28085A is a UL Type TC (1277) power and control cable with seven 14 AWG (7x22) bare copper conductors, PVC/nylon insulation (E2 color code), and a black PVC outer jacket. It is rated 600 V (TC-ER) and 150 V (NPLF), with UL temperature of 90 °C dry / 90 °C wet and an operating range of -30 °C to 90 °C wet/dry. It is suitable for power and control applications up to 600 V, including Class 1 Division 2 hazardous locations.
Who manufactures 28085A?
28085A is manufactured by Belden.
Where can I download the 28085A datasheet PDF?
The 28085A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 28085A specifications
Click to ask a quick question:
Parameters
| Conductors | 7 conductors, 14 AWG, 7x22 stranding, BC - Bare Copper |
| Electrical | Nom. Conductor DCR 2.67 Ohm/1000ft; Max. Current 17.5 Amps per Conductor at 30ºC |
| Insulation | PVC/Nylon - Polyvinyl Chloride + Nylon, Nom. Thickness 0.019 in (0.48 mm), Nom. Insulation Diameter 0.112 in (2.84 mm), Color Code Black, Red, Blue, Orange, Yellow, Brown, Red/Black |
| Mechanical | Max. Pull Tension 382.2 lbs (173.4 kg); Bulk Cable Weight 148 lbs/1000ft |
| Outer Jacket | PVC - Polyvinyl Chloride, Nom. Thickness 0.047 in (1.2 mm), Nom. Diameter 0.430 in (10.9 mm), Ripcord Yes |
| Overall Cable Diameter (Nominal) | 0.430 in (10.9 mm) |
| Temperature | UL Temperature 90°C Dry, 90°C Wet; Operating Wet/Dry: -30°C to 90°C |
| Voltage Rating | 600 V (TC-ER), 150 V (NPLF) |