27153A Datasheet

BeldenBulk Wire Cable

Belden 27153A is a UL Type TC (1277) power and control cable with three 6 AWG bare copper conductors plus one 8 AWG bare copper ground wire, PVC/nylon insulation, and a black PVC jacket. It is rated 600 V, 90 °C wet/dry, sunlight resistant and suitable for direct burial, and is recommended for power and control applications up to 600 V including Class 1 Division 2 hazardous locations.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

27153A Key Specifications

DC resistance
Conductors 0.42 Ohm/1000 ft; ground 0.68 Ohm/1000 ft (2.2 Ohm/km)
Max current
75 Amps per conductor at 30 °C; ground 57 Amps per conductor at 25 °C
Voltage rating
600 V
Temperature rating
90 °C dry, 90 °C wet; operating wet/dry -30 °C to 90 °C
Bend radius
Stationary min 2.72 in (69.1 mm); installation min 3.4 in (86 mm)
Cable dimensions
Overall diameter 0.68 in (17 mm); jacket thickness 0.063 in (1.6 mm)
Conductor / ground configuration
3 conductors 6 AWG (7x14) bare copper + 1 ground 8 AWG (7x16) bare copper
Mechanical
Max pull tension 1262.1 lbs (572.48 kg); bulk weight 410 lbs/1000 ft

Characteristics (datasheet)

Conductor / ground configuration
3 conductors 6 AWG (7x14) bare copper + 1 ground 8 AWG (7x16) bare copper
Voltage rating
600 V
Temperature rating
90 °C dry, 90 °C wet; operating wet/dry -30 °C to 90 °C
Max current
75 Amps per conductor at 30 °C; ground 57 Amps per conductor at 25 °C
DC resistance
Conductors 0.42 Ohm/1000 ft; ground 0.68 Ohm/1000 ft (2.2 Ohm/km)
Cable dimensions
Overall diameter 0.68 in (17 mm); jacket thickness 0.063 in (1.6 mm)
Bend radius
Stationary min 2.72 in (69.1 mm); installation min 3.4 in (86 mm)
Mechanical
Max pull tension 1262.1 lbs (572.48 kg); bulk weight 410 lbs/1000 ft

27153A Applications

  • Power and Control Applications up to 600V
  • Class 1 Division 2 Hazardous Locations

Other Belden parts

  • 45482 — Belden part 45482 is an XTRAGUARD 4 cable containing 2 pairs of 22 AWG (7x30) st...
  • 65412 — The Belden 65412 is a 12-conductor, 14 AWG XTRAGUARD FLEX flexible control cable...
  • 5682 — The Belden 5682 is a 2-conductor, 26 AWG tinned copper shielded cable designed f...
  • 83910 — The Belden 83910 is a Type T thermocouple cable consisting of a single pair of 2...
  • 21632 — The Belden 21632 is a CSA TC-CIC 600 V tray cable with 34 conductors: thirty 10...
  • 5108C — The Belden 5108C is an XTRAGUARD 1 multi-conductor shielded cable featuring eigh...
  • 8241 — The Belden 8241 is an RG-59 75 Ohm analog video coaxial cable featuring a 23 AWG...
  • 45462 — Belden part 45462 is an XTRAGUARD 4 cable with 2 conductors of 20 AWG (7/28) tin...

More Bulk Wire Cable

  • 77031 — The Belden 77031 ECOCABLE is a 5-conductor, 16 AWG tinned copper cable with mPPE...
  • 6300FC — The Belden 6300FC is a discontinued plenum-rated 2-conductor 18 AWG stranded bar...
  • 1310 — The part 1310 is a heavy-duty RW90 rated power and control cable with a 3/0 AWG...
  • 78216 — The Belden 78216 (Alpha Wire P/N 78216) is a multi-pair cable featuring 6 pairs...
  • 1575 — The Belden 1575 is a single-conductor, 600V, 4 AWG 7-strand bare copper cable wi...
  • 7127W — The Belden 7127W is a MachFlex™ high-flex cable designed with 11+1 conductors of...
  • 8263 — The Belden 8263 is an analog video coaxial cable of RG59 type, built with a 23 A...
  • 6390 — The Belden 6390 is a high-performance shielded communication and control cable c...

27153A FAQ

What is 27153A?

27153A is a Bulk Wire Cable from Belden. Belden 27153A is a UL Type TC (1277) power and control cable with three 6 AWG bare copper conductors plus one 8 AWG bare copper ground wire, PVC/nylon insulation, and a black PVC jacket. It is rated 600 V, 90 °C wet/dry, sunlight resistant and suitable for direct burial, and is recommended for power and control applications up to 600 V including Class 1 Division 2 hazardous locations.

Who manufactures 27153A?

27153A is manufactured by Belden.

Where can I download the 27153A datasheet PDF?

The 27153A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 27153A specifications

AI Powered

Click to ask a quick question:

Parameters

Bend radiusStationary min 2.72 in (69.1 mm); installation min 3.4 in (86 mm)
Cable dimensionsOverall diameter 0.68 in (17 mm); jacket thickness 0.063 in (1.6 mm)
Conductor / ground configuration3 conductors 6 AWG (7x14) bare copper + 1 ground 8 AWG (7x16) bare copper
DC resistanceConductors 0.42 Ohm/1000 ft; ground 0.68 Ohm/1000 ft (2.2 Ohm/km)
Max current75 Amps per conductor at 30 °C; ground 57 Amps per conductor at 25 °C
MechanicalMax pull tension 1262.1 lbs (572.48 kg); bulk weight 410 lbs/1000 ft
Temperature rating90 °C dry, 90 °C wet; operating wet/dry -30 °C to 90 °C
Voltage rating600 V