21666 Datasheet

BeldenBulk Wire Cable

The Belden 21666 is a CSA Type TC tray cable rated 600 V, built with three 1 AWG (19x14) bare copper power conductors and one 6 AWG (7x14) bare copper ground conductor, all insulated with XLPE. It carries a black PVC outer jacket 0.095 in thick with a 1.097 in nominal diameter and includes a ripcord, and it is rated 90°C dry/wet with an operating range of -40°C to 90°C. The cable is intended for CEC power and control applications and is approved for direct burial, indoor/outdoor use, sunlight resistance, and FT4 flammability.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

21666 Key Specifications

Voltage rating
600 V (UL) / 600 V (CSA TC)
Temperature
90°C dry, 90°C wet; operating -40°C to 90°C wet/dry
Compliance
FT4, TC, CIC, CE Mark, RoHS 2, WEEE, China RoHS II
Conductor DCR
1.6 Ohm/1000ft (5.2 Ohm/km)
Conductors
3 x 1 AWG (19x14) bare copper + 1 ground 6 AWG (7x14) bare copper
Insulation
XLPE/XLPO/XLP thermoset, 0.040 in nominal thickness, 0.366 in (9.30 mm) nominal diameter
Outer jacket
Black PVC, 0.095 in (2.4 mm) nominal thickness, 1.097 in nominal diameter, ripcord yes

Characteristics (datasheet)

Voltage rating
600 V (UL) / 600 V (CSA TC)
Conductors
3 x 1 AWG (19x14) bare copper + 1 ground 6 AWG (7x14) bare copper
Insulation
XLPE/XLPO/XLP thermoset, 0.040 in nominal thickness, 0.366 in (9.30 mm) nominal diameter
Outer jacket
Black PVC, 0.095 in (2.4 mm) nominal thickness, 1.097 in nominal diameter, ripcord yes
Conductor DCR
1.6 Ohm/1000ft (5.2 Ohm/km)
Temperature
90°C dry, 90°C wet; operating -40°C to 90°C wet/dry
Weight
1210 lbs/1000ft (1800 kg/km)
Compliance
FT4, TC, CIC, CE Mark, RoHS 2, WEEE, China RoHS II

21666 Applications

  • CEC Power and Control Applications

Other Belden parts

  • 6084C — The 6084C is a 4-pair 24 AWG tinned copper shielded communication and control ca...
  • 78392 — The 78392 is a shielded 2-pair, 20 AWG tinned copper cable with modified polyphe...
  • 9462 — The Belden 9462 is a 2-conductor 22AWG tinned copper cable with PVC insulation,...
  • 8479 — The part 8479 is a 3-conductor portable cordage cable featuring 14AWG (41x30) ba...
  • 4440FDW — The 4440FDW is a 1-pair OSDP RS-485 instrumentation and computer cable designed...
  • 23548D — Belden 23548D is a Canadian Instrumentation Cable (TC-ACIC) rated 300 V, contain...
  • 80055 — The Belden 80055 (Alpha Wire) is a 7-conductor, 14 AWG tinned copper control cab...
  • 80123 — The Belden 80123 is a 6-conductor, 20 AWG tinned copper cable with mPPE insulati...

More Bulk Wire Cable

  • 21658 — Belden part 21658 is a CSA Tray TC-CIC 600V power and control cable with four 4...
  • 1585 — The Belden 1585 is a single-conductor, 600V, 2 AWG 7-strand bare copper hook-up...
  • 8732 — The Belden 8732 is a shielded, 2-pair 22 AWG tinned copper electronic cable with...
  • 2243C — The Belden 2243C is a communication and control cable featuring three 18 AWG tin...
  • 1355 — The Belden 1355 is a single-conductor, 14 AWG bare copper cable with cross-linke...
  • 85604 — The part 85604 is an XTRAGUARD FLEX 4-conductor, 16 AWG bare copper control cabl...
  • 2190A — The Belden 2190A is a discontinued composite outdoor cable designed for broadcas...
  • 21629 — Belden part 21629 is a CSA Tray TC-CIC 600 V cable containing 31 conductors of 1...

21666 FAQ

What is 21666?

21666 is a Bulk Wire Cable from Belden. The Belden 21666 is a CSA Type TC tray cable rated 600 V, built with three 1 AWG (19x14) bare copper power conductors and one 6 AWG (7x14) bare copper ground conductor, all insulated with XLPE. It carries a black PVC outer jacket 0.095 in thick with a 1.097 in nominal diameter and includes a ripcord, and it is rated 90°C dry/wet with an operating range of -40°C to 90°C. The cable is intended for CEC power and control applications and is approved for direct burial, indoor/outdoor use, sunlight resistance, and FT4 flammability.

Who manufactures 21666?

21666 is manufactured by Belden.

Where can I download the 21666 datasheet PDF?

The 21666 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 21666 specifications

AI Powered

Click to ask a quick question:

Parameters

ComplianceFT4, TC, CIC, CE Mark, RoHS 2, WEEE, China RoHS II
Conductor DCR1.6 Ohm/1000ft (5.2 Ohm/km)
Conductors3 x 1 AWG (19x14) bare copper + 1 ground 6 AWG (7x14) bare copper
InsulationXLPE/XLPO/XLP thermoset, 0.040 in nominal thickness, 0.366 in (9.30 mm) nominal diameter
Outer jacketBlack PVC, 0.095 in (2.4 mm) nominal thickness, 1.097 in nominal diameter, ripcord yes
Temperature90°C dry, 90°C wet; operating -40°C to 90°C wet/dry
Voltage rating600 V (UL) / 600 V (CSA TC)
Weight1210 lbs/1000ft (1800 kg/km)