21608 Datasheet

BeldenBulk Wire Cable

The Belden 21608 is a CSA Type TC-CIC tray cable rated 600 V, constructed with ten 10 AWG bare copper conductors and one 12 AWG bare copper ground wire. It uses XLPE/XLPO/XLP thermoset insulation, a black PVC jacket with ripcord, and is rated 90 °C dry/wet for direct burial, sunlight-resistant indoor/outdoor use. It is intended for CEC power and control applications.\n

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

21608 Key Specifications

Max Current
28 Amps per Conductor at 30 ºC
Voltage Rating
600 V (CSA TC)
Temperature Rating
90 °C Dry, 90 °C Wet; Operating -40 °C to 90 °C; Installation -25 °C to +90 °C
Conductor Configuration
10 x 10 AWG (7x18) bare copper + 1 x 12 AWG (7x20) bare copper ground
Conductor DCR
1.06 Ohm/1000 ft (conductors); 1.68 Ohm/1000 ft (ground wire)
Insulation Material/Thickness
XLP, XLPO, XLPE (Thermoset), 0.030 in (0.76 mm) nominal
Max Pull Tension / Weight
1614.8 lbs (732.46 kg); 589 lbs/1000 ft
Outer Jacket/Diameter
PVC - Polyvinyl Chloride, 0.095 in (2.4 mm) nominal, overall 0.912 in

Characteristics (datasheet)

Voltage Rating
600 V (CSA TC)
Conductor Configuration
10 x 10 AWG (7x18) bare copper + 1 x 12 AWG (7x20) bare copper ground
Insulation Material/Thickness
XLP, XLPO, XLPE (Thermoset), 0.030 in (0.76 mm) nominal
Outer Jacket/Diameter
PVC - Polyvinyl Chloride, 0.095 in (2.4 mm) nominal, overall 0.912 in
Temperature Rating
90 °C Dry, 90 °C Wet; Operating -40 °C to 90 °C; Installation -25 °C to +90 °C
Max Current
28 Amps per Conductor at 30 ºC
Conductor DCR
1.06 Ohm/1000 ft (conductors); 1.68 Ohm/1000 ft (ground wire)
Max Pull Tension / Weight
1614.8 lbs (732.46 kg); 589 lbs/1000 ft

21608 Applications

  • CEC Power and Control Applications

Other Belden parts

  • 25272 — Belden 25272 is an XTRAGUARD 2 cable with 2 pairs of 24 AWG (7x32) stranded tinn...
  • 24512D — The Belden 24512D is a Canadian instrumentation cable (TC-ACIC) rated 600 V, con...
  • 8898 — The Belden 8898 is a low-temperature rubber lead wire featuring an 18 AWG tinned...
  • 5078C — The Belden 5078C is an XTRAGUARD 1, 8-conductor 16 AWG stranded tinned copper ca...
  • 3115A — The Belden 3115A is a Type JX thermocouple cable featuring 2 pairs of 20 AWG sol...
  • 1120A — The Belden 1120A is a single-pair 18 AWG instrumentation cable featuring bare co...
  • 1350SB — The Belden 1350SB is a digital audio cable rated CMG-LS, featuring a single pair...
  • 79015 — The Belden 79015 is an ECOFLEX multi-conductor cable featuring nine 18 AWG tinne...

More Bulk Wire Cable

  • 8690 — The Belden 8690 is a 3-pair 18 AWG tinned copper cable with PVC insulation and a...
  • 8637MN — The Belden 8637MN is a SpaceMaker™ multi-conductor cable consisting of nine colo...
  • 6226C — The Belden 6226C is a low-voltage communication and control cable featuring 6 pa...
  • 1651 — The Belden 1651 is a single-conductor hook-up wire with a 12 AWG tinned copper c...
  • 6201FE — The 6201FE is a plenum-rated (CMP) security and commercial audio cable consistin...
  • 1673A — The Belden 1673A is a conformable, unjacketed 50 Ohm coaxial cable (RG-402) feat...
  • 4281MDW — The Belden 4281MDW is an OSDP reader cable designed for access control, OSDP rea...
  • 25452 — The Belden 25452 is an XTRAGUARD 2 cable consisting of 2 pairs of 20 AWG (7x28)...

21608 FAQ

What is 21608?

21608 is a Bulk Wire Cable from Belden. The Belden 21608 is a CSA Type TC-CIC tray cable rated 600 V, constructed with ten 10 AWG bare copper conductors and one 12 AWG bare copper ground wire. It uses XLPE/XLPO/XLP thermoset insulation, a black PVC jacket with ripcord, and is rated 90 °C dry/wet for direct burial, sunlight-resistant indoor/outdoor use. It is intended for CEC power and control applications.\n.

Who manufactures 21608?

21608 is manufactured by Belden.

Where can I download the 21608 datasheet PDF?

The 21608 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 21608 specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor Configuration10 x 10 AWG (7x18) bare copper + 1 x 12 AWG (7x20) bare copper ground
Conductor DCR1.06 Ohm/1000 ft (conductors); 1.68 Ohm/1000 ft (ground wire)
Insulation Material/ThicknessXLP, XLPO, XLPE (Thermoset), 0.030 in (0.76 mm) nominal
Max Current28 Amps per Conductor at 30 ºC
Max Pull Tension / Weight1614.8 lbs (732.46 kg); 589 lbs/1000 ft
Outer Jacket/DiameterPVC - Polyvinyl Chloride, 0.095 in (2.4 mm) nominal, overall 0.912 in
Temperature Rating90 °C Dry, 90 °C Wet; Operating -40 °C to 90 °C; Installation -25 °C to +90 °C
Voltage Rating600 V (CSA TC)