21584 Datasheet
The Belden 21584 is a CSA Type TC-CIC 600 V tray cable with 36 bare copper 12 AWG conductors (7x20 stranding) plus one 14 AWG ground wire, insulated with XLPE and covered by a black PVC jacket. It is rated for wet/dry operation at 90°C and is listed for CEC power and control applications, including sunlight-resistant and direct burial use. The cable has a nominal outside diameter of 1.240 in and a bulk weight of 1218 lbs per 1000 ft.
Datasheet published by Belden
Open the PDF on catalog.belden.com with the Download PDF button
21584 Key Specifications
- Max. Current
- 25 Amps per Conductor at 30ºC
- Voltage Rating
- 600 V (CSA TC)
- Operating Temperature (Wet/Dry)
- -40°C to 90°C
- Conductor(s)
- 36 x 12 AWG bare copper, 7x20 stranding
- Ground Wire
- 1 x 14 AWG bare copper, 7x22 stranding
- Insulation
- XLPE, 0.032 in (0.81 mm) nominal thickness
- Nom. Conductor DCR
- 1.6 Ohm/1000ft (5.2 Ohm/km)
- Outer Jacket
- Black PVC, 0.095 in (2.4 mm) nominal thickness, 1.240 in nominal diameter
Characteristics (datasheet)
- Voltage Rating
- 600 V (CSA TC)
- Conductor(s)
- 36 x 12 AWG bare copper, 7x20 stranding
- Ground Wire
- 1 x 14 AWG bare copper, 7x22 stranding
- Insulation
- XLPE, 0.032 in (0.81 mm) nominal thickness
- Outer Jacket
- Black PVC, 0.095 in (2.4 mm) nominal thickness, 1.240 in nominal diameter
- Max. Current
- 25 Amps per Conductor at 30ºC
- Nom. Conductor DCR
- 1.6 Ohm/1000ft (5.2 Ohm/km)
- Operating Temperature (Wet/Dry)
- -40°C to 90°C
21584 Applications
- CEC Power and Control Applications
Other Belden parts
- 9319 — The Belden 9319 is an audio, control, and instrument cable featuring 19 pairs of...
- 9947 — The Belden 9947 is a 15-conductor computer EIA RS-232 cable designed for RS-232...
- 79246 — The Belden 79246 is a shielded, flexible 4-conductor cable (ECOFLEX) built with...
- 25116 — Belden part 25116 is an XTRAGUARD 2 cable with six 24 AWG (7x32) tinned copper c...
- 8075 — The Belden 8075 is a class 200 magnet wire featuring a single solid 18 AWG bare...
- 934073102 — HIRSCHMANN TEST AND MEASUREMENT 934073102 Test Lead, 4mm Banana Plug to 4mm...
- 78192 — The Belden 78192 is a shielded multi-conductor cable (ECOCABLE) featuring 2 pair...
- 5561C — The Belden 5561C (Alpha Wire) is a XTRAGUARD 1 shielded multi-conductor cable fe...
More Bulk Wire Cable
- 9394 — Part 9394 is a discontinued 1-conductor 20 AWG tinned copper microphone cable wi...
- 57004 — The Belden 57004 is a plenum-rated, shielded 4-conductor 24 AWG bare copper cabl...
- 30818 — Belden part 30818 is an 18 AWG (16x30) tinned copper lead wire with silicone rub...
- 5534 — The 5534 is a shielded 4-conductor, 16 AWG tinned copper cable with PVC insulati...
- 29521 — Belden 29521 is a Premium VFD power cable with three 14 AWG (41 x 30) tinned cop...
- 76203WS — The Belden 76203WS is a highly flexible, shielded 3-conductor cable designed for...
- 1336A — The Belden 1336A is a 2-conductor 14 AWG tinned copper fieldbus cable with polyp...
- 6520FE — The 6520FE is a plenum-rated security and commercial audio cable featuring two 2...
21584 FAQ
What is 21584?
21584 is a Bulk Wire Cable from Belden. The Belden 21584 is a CSA Type TC-CIC 600 V tray cable with 36 bare copper 12 AWG conductors (7x20 stranding) plus one 14 AWG ground wire, insulated with XLPE and covered by a black PVC jacket. It is rated for wet/dry operation at 90°C and is listed for CEC power and control applications, including sunlight-resistant and direct burial use. The cable has a nominal outside diameter of 1.240 in and a bulk weight of 1218 lbs per 1000 ft.
Who manufactures 21584?
21584 is manufactured by Belden.
Where can I download the 21584 datasheet PDF?
The 21584 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.
Specifications
- Manufacturer
- Belden
Ask AI Assistant
Ask questions about 21584 specifications
Click to ask a quick question:
Parameters
| Conductor(s) | 36 x 12 AWG bare copper, 7x20 stranding |
| Ground Wire | 1 x 14 AWG bare copper, 7x22 stranding |
| Insulation | XLPE, 0.032 in (0.81 mm) nominal thickness |
| Max. Current | 25 Amps per Conductor at 30ºC |
| Nom. Conductor DCR | 1.6 Ohm/1000ft (5.2 Ohm/km) |
| Operating Temperature (Wet/Dry) | -40°C to 90°C |
| Outer Jacket | Black PVC, 0.095 in (2.4 mm) nominal thickness, 1.240 in nominal diameter |
| Voltage Rating | 600 V (CSA TC) |