21584 Datasheet

BeldenBulk Wire Cable

The Belden 21584 is a CSA Type TC-CIC 600 V tray cable with 36 bare copper 12 AWG conductors (7x20 stranding) plus one 14 AWG ground wire, insulated with XLPE and covered by a black PVC jacket. It is rated for wet/dry operation at 90°C and is listed for CEC power and control applications, including sunlight-resistant and direct burial use. The cable has a nominal outside diameter of 1.240 in and a bulk weight of 1218 lbs per 1000 ft.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

21584 Key Specifications

Max. Current
25 Amps per Conductor at 30ºC
Voltage Rating
600 V (CSA TC)
Operating Temperature (Wet/Dry)
-40°C to 90°C
Conductor(s)
36 x 12 AWG bare copper, 7x20 stranding
Ground Wire
1 x 14 AWG bare copper, 7x22 stranding
Insulation
XLPE, 0.032 in (0.81 mm) nominal thickness
Nom. Conductor DCR
1.6 Ohm/1000ft (5.2 Ohm/km)
Outer Jacket
Black PVC, 0.095 in (2.4 mm) nominal thickness, 1.240 in nominal diameter

Characteristics (datasheet)

Voltage Rating
600 V (CSA TC)
Conductor(s)
36 x 12 AWG bare copper, 7x20 stranding
Ground Wire
1 x 14 AWG bare copper, 7x22 stranding
Insulation
XLPE, 0.032 in (0.81 mm) nominal thickness
Outer Jacket
Black PVC, 0.095 in (2.4 mm) nominal thickness, 1.240 in nominal diameter
Max. Current
25 Amps per Conductor at 30ºC
Nom. Conductor DCR
1.6 Ohm/1000ft (5.2 Ohm/km)
Operating Temperature (Wet/Dry)
-40°C to 90°C

21584 Applications

  • CEC Power and Control Applications

Other Belden parts

  • 9319 — The Belden 9319 is an audio, control, and instrument cable featuring 19 pairs of...
  • 9947 — The Belden 9947 is a 15-conductor computer EIA RS-232 cable designed for RS-232...
  • 79246 — The Belden 79246 is a shielded, flexible 4-conductor cable (ECOFLEX) built with...
  • 25116 — Belden part 25116 is an XTRAGUARD 2 cable with six 24 AWG (7x32) tinned copper c...
  • 8075 — The Belden 8075 is a class 200 magnet wire featuring a single solid 18 AWG bare...
  • 934073102 — HIRSCHMANN TEST AND MEASUREMENT 934073102 Test Lead, 4mm Banana Plug to 4mm...
  • 78192 — The Belden 78192 is a shielded multi-conductor cable (ECOCABLE) featuring 2 pair...
  • 5561C — The Belden 5561C (Alpha Wire) is a XTRAGUARD 1 shielded multi-conductor cable fe...

More Bulk Wire Cable

  • 9394 — Part 9394 is a discontinued 1-conductor 20 AWG tinned copper microphone cable wi...
  • 57004 — The Belden 57004 is a plenum-rated, shielded 4-conductor 24 AWG bare copper cabl...
  • 30818 — Belden part 30818 is an 18 AWG (16x30) tinned copper lead wire with silicone rub...
  • 5534 — The 5534 is a shielded 4-conductor, 16 AWG tinned copper cable with PVC insulati...
  • 29521 — Belden 29521 is a Premium VFD power cable with three 14 AWG (41 x 30) tinned cop...
  • 76203WS — The Belden 76203WS is a highly flexible, shielded 3-conductor cable designed for...
  • 1336A — The Belden 1336A is a 2-conductor 14 AWG tinned copper fieldbus cable with polyp...
  • 6520FE — The 6520FE is a plenum-rated security and commercial audio cable featuring two 2...

21584 FAQ

What is 21584?

21584 is a Bulk Wire Cable from Belden. The Belden 21584 is a CSA Type TC-CIC 600 V tray cable with 36 bare copper 12 AWG conductors (7x20 stranding) plus one 14 AWG ground wire, insulated with XLPE and covered by a black PVC jacket. It is rated for wet/dry operation at 90°C and is listed for CEC power and control applications, including sunlight-resistant and direct burial use. The cable has a nominal outside diameter of 1.240 in and a bulk weight of 1218 lbs per 1000 ft.

Who manufactures 21584?

21584 is manufactured by Belden.

Where can I download the 21584 datasheet PDF?

The 21584 datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 21584 specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor(s)36 x 12 AWG bare copper, 7x20 stranding
Ground Wire1 x 14 AWG bare copper, 7x22 stranding
InsulationXLPE, 0.032 in (0.81 mm) nominal thickness
Max. Current25 Amps per Conductor at 30ºC
Nom. Conductor DCR1.6 Ohm/1000ft (5.2 Ohm/km)
Operating Temperature (Wet/Dry)-40°C to 90°C
Outer JacketBlack PVC, 0.095 in (2.4 mm) nominal thickness, 1.240 in nominal diameter
Voltage Rating600 V (CSA TC)