1100A Datasheet

BeldenBulk Wire Cable

The Belden 1100A is a UL-listed instrumentation cable featuring 24 triads of 16 AWG (7x24) bare copper conductors with PVC-nylon insulation, individual and overall Beldfoil shields, and a black PVC outer jacket. It is rated for 600V TC and 150V NPLF, and is designed for use in industrial control, raceways, cable trays, digital control, instruments, and low-voltage control circuits connecting solenoids, valves, actuators, and positioners.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

1100A Key Specifications

Voltage Rating
600 V (TC), 150 V (NPLF)
Temperature Rating
UL: 90°C Dry, 75°C Wet; Operating: -30C to 90C Dry, 75C wet
Bulk Cable Weight
1225 lbs/1000ft
Conductor
24 Triad, 16 AWG 7x24 Bare Copper (BC)
Nom. Conductor DCR
3.67 Ohm/1000ft (12.0 Ohm/km)
Nom. Inner Shield DCR
4.99 Ohm/1000ft (16.4 Ohm/km)
Nom Outer Shield DCR
2.74 Ohm/1000ft (8.99 Ohm/km)
Overall Cable Diameter (Nominal)
1.447 in (36.75 mm)

Characteristics (datasheet)

Conductor
24 Triad, 16 AWG 7x24 Bare Copper (BC)
Nom. Conductor DCR
3.67 Ohm/1000ft (12.0 Ohm/km)
Nom. Inner Shield DCR
4.99 Ohm/1000ft (16.4 Ohm/km)
Nom Outer Shield DCR
2.74 Ohm/1000ft (8.99 Ohm/km)
Voltage Rating
600 V (TC), 150 V (NPLF)
Temperature Rating
UL: 90°C Dry, 75°C Wet; Operating: -30C to 90C Dry, 75C wet
Overall Cable Diameter (Nominal)
1.447 in (36.75 mm)
Bulk Cable Weight
1225 lbs/1000ft

1100A Applications

  • Industrial control
  • Raceways, cable trays and ducts
  • Digital control
  • Instruments (4-20mA, 0-10V, etc.)
  • Low voltage digital control (24V, etc.)
  • RTD and control circuits
  • Distributed control system (DCS)
  • Programmable logic controller (PLC)
  • Solenoids, valves, actuators, positioners

Other Belden parts

  • 83269 — The Belden 83269 is a commercial, non-QPL mil-spec coaxial cable with a 50 Ohm c...
  • 1136C — The 1136C is a communication and control cable consisting of 6 pairs of 18 AWG t...
  • 78112 — The Belden 78112 is a shielded, 2-conductor, 26 AWG tinned copper cable (ECOCABL...
  • 6208C — The Belden 6208C is an 8-pair, 24 AWG tinned copper communication and control ca...
  • 930318100 — Crocodile CLIP, 4MM, BLACK, PK5 , MKU; Connector Type:Crocodile Clip; Jaw Openin...
  • 934093101 — HIRSCHMANN TEST AND MEASUREMENT 934093101 TEST LEAD, RED, 1.5M, 60V, 16A
  • 78325 — The Belden 78325 is a shielded multi-conductor cable (ECOCABLE) featuring 5 pair...
  • 83804 — The Belden 83804 is a high-temperature, 4-conductor 12 AWG tinned copper cable w...

More Bulk Wire Cable

  • 5678 — The Belden 5678 is an XTRAGUARD 1 shielded multi-conductor cable featuring seven...
  • 2414C — The 2414C is a 4-conductor, 20 AWG tinned copper communication and control cable...
  • 77002 — The Belden 77002 is a 4-conductor, 24 AWG tinned copper cable with mPPE insulati...
  • 9397 — The Belden 9397 is a 2-conductor 24 AWG stranded high-conductivity bare copper m...
  • 89842 — The Belden 89842 is a plenum-rated (CMP) RS-485 cable consisting of two 24 AWG t...
  • 76325WS — The Belden 76325WS is a MachFlex™ high-flexibility 25-conductor cable featuring...
  • 9390 — The Belden 9390 is a high-performance instrumentation cable containing 9 pairs o...
  • 4100FE — The Belden 4100FE is a security and commercial audio cable featuring two 14 AWG...

1100A FAQ

What is 1100A?

1100A is a Bulk Wire Cable from Belden. The Belden 1100A is a UL-listed instrumentation cable featuring 24 triads of 16 AWG (7x24) bare copper conductors with PVC-nylon insulation, individual and overall Beldfoil shields, and a black PVC outer jacket. It is rated for 600V TC and 150V NPLF, and is designed for use in industrial control, raceways, cable trays, digital control, instruments, and low-voltage control circuits connecting solenoids, valves, actuators, and positioners.

Who manufactures 1100A?

1100A is manufactured by Belden.

Where can I download the 1100A datasheet PDF?

The 1100A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 1100A specifications

AI Powered

Click to ask a quick question:

Parameters

Bulk Cable Weight1225 lbs/1000ft
Conductor24 Triad, 16 AWG 7x24 Bare Copper (BC)
Nom. Conductor DCR3.67 Ohm/1000ft (12.0 Ohm/km)
Nom. Inner Shield DCR4.99 Ohm/1000ft (16.4 Ohm/km)
Nom Outer Shield DCR2.74 Ohm/1000ft (8.99 Ohm/km)
Overall Cable Diameter (Nominal)1.447 in (36.75 mm)
Temperature RatingUL: 90°C Dry, 75°C Wet; Operating: -30C to 90C Dry, 75C wet
Voltage Rating600 V (TC), 150 V (NPLF)