1087A Datasheet

BeldenBulk Wire Cable

The Belden 1087A is a 36-pair, 18 AWG bare copper instrumentation cable featuring PVC/nylon insulation with an E1 color code, an overall Beldfoil bi-laminate shield, and a black PVC outer jacket. It is rated for 600V TC-ER and 150V NPLF, with an operating temperature range of -30°C to 90°C dry and 75°C wet. This cable is designed for use in industrial control, DCS, PLC systems, and low-voltage digital instrumentation circuits.

Download PDF(catalog.belden.com)

Datasheet published by Belden

Open the PDF on catalog.belden.com with the Download PDF button

1087A Key Specifications

UL Voltage Rating
600 V (TC-ER), 150 V (NPLF)
Operating Temperature
-30C to 90C Dry, 75C wet (UL Temperature: 90°C Dry, 75°C Wet)
Conductor
36 pairs, 18 AWG 7x26 Bare Copper (BC)
Insulation
PVC/Nylon - Polyvinyl Chloride + Nylon, 0.021 in (0.53 mm) nominal thickness, Black, White and Numbered color code
Nom Conductor DCR
5.86 Ohm/1000ft (19.2 Ohm/km)
Nominal Overall Diameter
1.157 in (29.39 mm)
Nom Outer Shield DCR
4.1 Ohm/1000ft (13 Ohm/km)
Outer Jacket
PVC - Polyvinyl Chloride, 0.084 in (2.1 mm) nominal thickness, black, with ripcord

Characteristics (datasheet)

Conductor
36 pairs, 18 AWG 7x26 Bare Copper (BC)
Insulation
PVC/Nylon - Polyvinyl Chloride + Nylon, 0.021 in (0.53 mm) nominal thickness, Black, White and Numbered color code
Outer Shield
Bi-Laminate (Alum+Poly) tape, 100% coverage, with 18 AWG (7x26) TC drainwire
Outer Jacket
PVC - Polyvinyl Chloride, 0.084 in (2.1 mm) nominal thickness, black, with ripcord
Nominal Overall Diameter
1.157 in (29.39 mm)
UL Voltage Rating
600 V (TC-ER), 150 V (NPLF)
Operating Temperature
-30C to 90C Dry, 75C wet (UL Temperature: 90°C Dry, 75°C Wet)
Nom Conductor DCR
5.86 Ohm/1000ft (19.2 Ohm/km)
Nom Outer Shield DCR
4.1 Ohm/1000ft (13 Ohm/km)

1087A Applications

  • Industrial control
  • Raceways, cable trays and ducts
  • Digital control
  • Instruments (4-20ma, 0-10v, ...)
  • Low voltage digital control (24v, ...)
  • Encoders
  • Control circuits
  • Distributed control system (DCS)
  • Programmable logic controller (PLC)
  • Solenoids, valves, actuators, positioners

Other Belden parts

  • 45453 — Belden part 45453 is an XTRAGUARD 4 cable consisting of 3 pairs of 20 AWG (7x28)...
  • 5366C — The Belden 5366C is a 6-conductor, 16 AWG tinned copper cable with PVC insulatio...
  • 6369 — The Belden 6369 is a communication and control cable consisting of 12 pairs of 2...
  • 9388 — The Belden 9388 is a high-performance instrumentation cable consisting of four p...
  • 21661 — Belden 21661 is a 600 V Type TC/CIC power and control cable containing four stra...
  • 78232 — The Belden 78232 is a shielded multi-conductor cable (ECOCABLE) consisting of tw...
  • 83562 — The Belden 83562 is a high-temperature, shielded multi-conductor cable featuring...
  • 5661 — The Belden 5661 is a 4-conductor, 14 AWG bare copper motor supply cable with PVC...

More Bulk Wire Cable

  • 5194C — The Belden 5194C is a 4-conductor, 22 AWG tinned copper shielded cable with semi...
  • 1215C — The Belden 1215C is a communication and control cable featuring five 24 AWG tinn...
  • 8102 — The Belden 8102 is a computer EIA RS-232/422 low-capacitance cable designed for...
  • 1179C — The Belden 1179C is a communication and control cable featuring nine 22 AWG tinn...
  • 79258 — The 79258 is a 4-conductor, 26 AWG stranded tinned copper cable with mPPE insula...
  • 6443FE — The Belden 6443FE is a plenum-rated (CMP) security and sound cable consisting of...
  • 80018 — The Belden 80018 is a 9-conductor, 22 AWG tinned copper control cable featuring...
  • 2630 — The Belden 2630 is a single-conductor hook-up wire featuring a 30 AWG nickel-pla...

1087A FAQ

What is 1087A?

1087A is a Bulk Wire Cable from Belden. The Belden 1087A is a 36-pair, 18 AWG bare copper instrumentation cable featuring PVC/nylon insulation with an E1 color code, an overall Beldfoil bi-laminate shield, and a black PVC outer jacket. It is rated for 600V TC-ER and 150V NPLF, with an operating temperature range of -30°C to 90°C dry and 75°C wet. This cable is designed for use in industrial control, DCS, PLC systems, and low-voltage digital instrumentation circuits.

Who manufactures 1087A?

1087A is manufactured by Belden.

Where can I download the 1087A datasheet PDF?

The 1087A datasheet PDF is published by Belden; the Download PDF button on this page opens it on the manufacturer's website.

Specifications

Manufacturer
Belden

Ask AI Assistant

Ask questions about 1087A specifications

AI Powered

Click to ask a quick question:

Parameters

Conductor36 pairs, 18 AWG 7x26 Bare Copper (BC)
InsulationPVC/Nylon - Polyvinyl Chloride + Nylon, 0.021 in (0.53 mm) nominal thickness, Black, White and Numbered color code
Nom Conductor DCR5.86 Ohm/1000ft (19.2 Ohm/km)
Nominal Overall Diameter1.157 in (29.39 mm)
Nom Outer Shield DCR4.1 Ohm/1000ft (13 Ohm/km)
Operating Temperature-30C to 90C Dry, 75C wet (UL Temperature: 90°C Dry, 75°C Wet)
Outer JacketPVC - Polyvinyl Chloride, 0.084 in (2.1 mm) nominal thickness, black, with ripcord
Outer ShieldBi-Laminate (Alum+Poly) tape, 100% coverage, with 18 AWG (7x26) TC drainwire
UL Voltage Rating600 V (TC-ER), 150 V (NPLF)